6.7Manual defrosting
Press and hold down the key for 5 seconds. The manual defrosting process will be initiated.
7 Programming
Access to the second programming level:
IPress and hold down the , and keys at the same time for approx. 5 seconds
(Display: E01 for
IUse or key to select parameters.
ISetting: Press and hold down the key. Adjust the setpoint value to the desired figure using the or key.
IDo not display altered parameter data before saving the data, as it would be reversed to its original value in the process.
7.1 Input parameters and input ranges
Parameter in Display | Setting range | Preset | ||
( or | ) | ( and or ) |
| |
E00 | Time, only for | 00.0 to 23.5 hours | 12’0 hours | |
E01 | Cold store temp. difference | 1 to | 20 K | 2 K |
E02 | Time between 2 defrost cycles | 1 to | 24 hours | 8 h |
☛Once the controller has been switched on, defrosting occurs for the first time at the end of the first time interval.
☛After defrosting has been initiated manually, the next time defrosting takes place is after a complete time interval has elapsed.
☛If the time interval between two defrost cycles is changed when the system is in operation, the new time interval will not be applied until after the next time defrosting has occurred.
For
E2’1 | 1st defrost time | ||
E2’2 | 2st defrost time | 01’0 hours | |
E2’3 | 3st defrost time | 07’0 hours | |
E2’4 | 4st defrost time | 13’0 hours | |
E2’5 | 5st defrost time | 19’0 hours | |
E2’6 | 6st defrost time | ||
|
|
|
|
13