6.7Manual defrosting

Press and hold down the key for 5 seconds. The manual defrosting process will be initiated.

7 Programming

Access to the second programming level:

IPress and hold down the , and keys at the same time for approx. 5 seconds

(Display: E01 for PCR-300, E00 for PCR-300RC).

IUse or key to select parameters.

ISetting: Press and hold down the key. Adjust the setpoint value to the desired figure using the or key.

IDo not display altered parameter data before saving the data, as it would be reversed to its original value in the process.

7.1 Input parameters and input ranges

Parameter in Display

Setting range

Preset

( or

)

( and or )

 

E00

Time, only for PCR-300RC

00.0 to 23.5 hours

12’0 hours

E01

Cold store temp. difference

1 to

20 K

2 K

E02

Time between 2 defrost cycles

1 to

24 hours

8 h

Once the controller has been switched on, defrosting occurs for the first time at the end of the first time interval.

After defrosting has been initiated manually, the next time defrosting takes place is after a complete time interval has elapsed.

If the time interval between two defrost cycles is changed when the system is in operation, the new time interval will not be applied until after the next time defrosting has occurred.

For PCR-300RC only:

E2’1

1st defrost time

––– (none), 00.1 to 23.5 hours

––– (none)

E2’2

2st defrost time

––– (none), 00.1 to 23.5 hours

01’0 hours

E2’3

3st defrost time

––– (none), 00.1 to 23.5 hours

07’0 hours

E2’4

4st defrost time

––– (none), 00.1 to 23.5 hours

13’0 hours

E2’5

5st defrost time

––– (none), 00.1 to 23.5 hours

19’0 hours

E2’6

6st defrost time

––– (none), 00.1 to 23.5 hours

––– (none)

 

 

 

 

13

Image 13
Contents PCR-300 PCR-300 RC Installation and Operating Instructions Table of Contents Use for the purpose intended Unpacking the unit and conditions of useSources of danger FunctionSafety precautions Housings with 1 mounting tab Housing with 2 mounting tabsElectrical installation Mounting of sensorInstructions Terminal DescriptionFor PCR-300 RC only Activation of the back-up batteryOperation of the controller Switching on the operating voltage Temperature Temperature Clear alarm Value for excess Temperature alarm Key functionsSetting the cold store temperature Access the second programming level by pressingInput parameters and input ranges E00Exiting programming mode Press the key several times Setting the time PCR-300RC onlyPCR-300RC only E2’1 E2’2Manual defrosting Access to the second programming levelE04 Important The times must be entered Ascending order E03E05 E06E15 To exit from the programming modeE16 E17Display Meaning MaintenanceClearing alarm Warranty conditionsFault Cause Remedy Only operate the unit in dry places PTCDr. Osthues + D / Production Manager EC Declaration of ConformityAutomation and Control Solutions