Emerson 848T manual 00809-0100-4697, Rev EA October Block/Transducer Error, Transducer Block Modes

Page 39

Reference Manual

00809-0100-4697, Rev EA October 2011

Table 3-9. Block/Transducer Error

 

 

Rosemount 848T

 

 

 

ERR

Condition Number, Name, and Description

 

 

0

Other(1)

_BLOCK

 

 

 

7

Input failure/process variable has bad status

 

15

Out of service: The actual mode is out of service

 

 

 

(1) If BLOCK_ERR is “other,” then see XD_ERROR.

Transducer Block Modes

The transducer block supports two modes of operation as defined by the MODE_BLK parameter:

Automatic (Auto)

The block outputs reflect the analog input measurement.

Out of Service (OOS)

The block is not processed. Channel outputs are not updated and the status is set to Bad: Out of Service for each channel. The BLOCK_ERR parameter shows Out of Service. In this mode, changes can be made to all configurable parameters. The target mode of a block may be restricted to one or more of the supported modes.

Transducer Block Alarm Detection

Alarms are not generated by the transducer block. By correctly handling the status of the channel values, the down stream block (AI or MAI) will generate the necessary alarms for the measurement. The error that generated this alarm can be determined by looking at BLOCK-ERR and XD_ERROR.

Transducer Block Status Handling

Normally, the status of the output channels reflect the status of the measurement value, the operating condition of the measurement electronics card, and any active alarm conditions. In a transducer, PV reflects the value and status quality of the output channels.

Table 3-10. Transducer Block Parameters

Number

Parameter

Description

0

BLOCK

 

1

ST_REV

The revision level of the static data associated with the function block.

2

TAG_DESC

The user description of the intended application of the block.

3

STRATEGY

The strategy field can be used to identify grouping of blocks.

4

ALERT_KEY

The identification number of the plant unit.

5

MODE_BLK

The actual, target, permitted, and normal modes of the block.

6

BLOCK_ERR

This parameter reflects the error status associated with the hardware or software

 

 

components associated with a block. Multiple errors may be shown. For a list of

 

 

enumeration values, see FF-890, Block_Err formal model.

7

UPDATE_EVENT

This alert is generated by any change to the static data.

8

BLOCK_ALM

The BLOCK-ALM is used for all configuration, hardware, connection failure or system

 

 

problems in the block. The cause of the alert is entered in the subcode field. The first alert

 

 

to become active will set the Active status in the Status attribute. As soon as the

 

 

Unreported status is cleared by the alert reporting task, another block alert may be

 

 

reported without clearing the Active status, if the subcode has changed.

9

TRANSDUCER_DIRECTORY

A directory that specified the number and stating indices of the transducers in the

 

 

transducer block.

10

TRANSDUCER_TYPE

Identifies the transducer that follows 101 – Standard Temperature with Calibration.

11

XD_ERROR

Provides additional error codes related to transducer blocks. For a list of enumeration

 

 

values, see FF-902. Please see tables below for a list of sub-parameters that pertain to

 

 

XD_ERROR messages.

3-17

Image 39
Contents 00809-0100-4697, Rev EA October Reference ManualPage Customer Central National Response Center International Rosemount 848T High Density Temperature Transmitter withPage Table of Contents TOC-2 Operation MaintenanceSection Appendix aElectrical shock could cause death or serious injury Safety MessagesSection Introduction Process leaks could result in death or serious injuryTransmitter Fieldbus host or configuration toolMaintenance of the Rosemount 848T Temperature Transmitter OverviewService Support Rosemount 848T Safety Messages Mounting Section InstallationMounting to a Panel with a Junction Box Mounting to a DIN Rail Without an EnclosureAluminum/Plastic Junction Box Stainless Steel Junction Box Mounting to a 2-in. Pipe StandLeads and terminals WiringSpur Signal Wiring Devices 1 through ConnectionsRTD or Ohm Inputs Thermocouple or Millivolt InputsAnalog Inputs Analog Input ConnectorsPower Supply Ohm resistor in the loop when switched to the leftPower Supply Surges/TransientsConnections Grounding Shielded WireFieldbus bus 848T Power Supply Sensor Wires Shield ground pointsTransmitter Enclosure optional MA loopSecurity SwitchesSimulate Enable Switch is not functionalSensor Tag TaggingCommissioning Tag Transmitter TagInstallation Using Cable GlandsUsing Conduit Entries Section Configuration Configuration Transmitter Configuration Custom Configuration MethodsStandard Rosemount 848T Block Common Configurations for High Density ApplicationsTypical Profiling Application FunctionMonitoring Application with a Single Selection Measuring Temperature Points IndividuallyMultiple Analog Input or Analog Input Block Configuration Block Configuration Resource BlockNumber Parameter Description 00809-0100-4697, Rev EA October Resource Block Parameters Failedenable SaveconfignowSaveconfigblocks StartwithdefaultsBlock is processing its normal background memory checks Block ErrorsModes Automatic AutoStatus Handling Out of Service OOSAlarm Detection PlantWeb AlertsFailedmask 00809-0100-4697, Rev EA October Failure AlarmsMaintenance Alarms/Priority Alarm Advisory AlarmsAlarm Recommended Actions for PlantWeb Alerts Alarm Type Active Event Recommended ActionTransducer Blocks RESOURCE.HARDWAREREV,RESOURCE.RBSFTWRREVALL Channel Description Transducer Block ErrorsTransducer Block Channel Definitions Channel Definitions for the 848TBlock outputs reflect the analog input measurement 00809-0100-4697, Rev EA October Block/Transducer ErrorTransducer Block Alarm Detection Transducer Block ModesSENSOR4CONFIG SENSOR1CONFIGSENSOR2CONFIG SENSOR3CONFIGChanging the Sensor Configuration in the Transducer Block 11. Xderror Sub-Parameter Structure 12. Sensorconfig Sub-Parameter StructureTransducer Block Sub-Parameter Tables 16. Transducer Status Sub-Parameter Structure 13. Sensorstatus Sub-Parameter Structure14. Sensorcal Sub-Parameter Structure 15. Calstatus StructureStructure Dual Sensor Status TableStructure 20. Validation Config Sub-Parameter Structure Sensor Calibration in the Sensor Transducer BlockStructure Parameter Description Rosemount 848T Operation and Maintenance Foundation Fieldbus InformationFoundation Commissioning Addressing Restart Processor cycling Hardware MaintenanceRestart with Defaults Sensor CheckSymptom Possible Causes Corrective Action TroubleshootingTransducer Block Troubleshooting Symptom Possible Cause Corrective ActionAppendix a Reference Data Functional SpecificationsTransient Protection Update TimeAlarms Backup Link Active Scheduler LASPhysical Specifications Function Blocks Performance SpecificationsInput Ranges Sensor Option Sensor Reference 3-Wire RTDsAccuracy for Differential Configurations AccuracyAnalog Sensors 4-20mA Sensor Option Alarm Levels AccuracyAmbient Temperature Effect Top View Dimensional DrawingsAmbient Temperature Notes Examples Rosemount 848TStainless Steel Junction Box-Cable Gland option code JS2 Side View Front ViewFront View Side View Side View Stainless Steel Junction Box-Conduit Entry option code JS3Front View Side View Mounting OptionsAluminum/Plastic Junction Box Styles JA and JP Stainless Steel Junction Box Style JSOptions Ordering InformationEnclosure Options Standard Software Configuration StandardSpecial Temperature Test Expanded Conduit Electrical Connector StandardRosemount 848T North American Approvals Table B-2. Entity Parameters for Non Incendive Field WiringAppendix B Product Certificates Hazardous Locations CertificatesPower/Bus Canadian Standards Association CSA Certifications Special Conditions for Safe Use Power/Bus SensorEuropean Approvals Atex CertificationsCi = Li = Rosemount 848T IECEx Certifications Special Conditions of Safe UseRosemount 848T China NEPSICertifications Parameters Terminals of power/loopJapanese Certifications Intrinsically Safe and NON-INCENDIVE Installations Installation Drawings Figure B-1. FM Intrinsic Safety/ Fisco 00809-0100-4697, Rev EA Rosemount 848T Figure B-2. CSA Intrinsic Safety/ Fisco Rosemount 848T Rosemount 848T Overview Function Blocks Appendix C Foundation fieldbus TechnologyLinkages Status InputOutput SnapTransducer Blocks Device Descriptions Block OperationInstrument- Specific Function Blocks Alerts Resource BlocksNetwork Communication Link Active Scheduler LASFieldbus Link MID x ST Data LAS ParametersReport Distribution Backup LASAddressing Scheduled Transfers Publisher/SubscriberUnscheduled Transfers ScheduleDevice Device Y Device Z Function Block Scheduling OUT Appendix D Function BlocksAnalog Input AI Function Block Number Parameter Units DescriptionIoopts AlarmhysXdscale Outscale63% of Change OUT mode in manOUT mode in auto FunctionalitySimulationIndirect Signal ConversionFiltering DirectConditions Indirect Square RootTable D-3. Alarm Priority Levels Manual ManValue of the block output OUT may be set manually Uncertain if Limited Uncertain if in Manual modeAdvanced Features BAD if LimitedHIHILIMIT, Lolimit AI Block TroubleshootingApplication Information XdblockTable D-4. Multiple Analog Input Function Block Parameters Multiple Analog Input MAI Function BlockCAPSTDDEV1 Simulate Figure D-4. Multiple Analog Input Function Block SchematicOption in Manual or Out of Service mode only Devices such as flowmetersTable D-5. Blockerr Conditions Block output OUT may be set manually MAI Block Troubleshooting OUT Outrange Input Selector Function BlockTable D-6. Input Selector Function Block Parameters IN1 IN2 IN3 IN4 IN5 IN6 IN7Opselect SelecttypeMingood SelectedFunctionality INn DISABLEnMode Logic Selection Alarm OUTOUT reflects the selected value Table D-8. Alarm Priority LevelsUse Uncertain as Good Block ExecutionIsel Block Troubleshooting Numerics IndexErrors Modes Automatic Configuration Errors Modes AutomaticMaintalarms Troubleshooting Alarm DetectionPage Pacific Private Limited Rosemount Inc

848T specifications

The Emerson 848T is a state-of-the-art temperature transmitter designed for accurate and reliable temperature measurement in various industrial applications. This device has gained recognition for its advanced features and robust performance, making it a popular choice among engineers and technicians in the field.

One of the key highlights of the Emerson 848T is its unique dual-channel capability, which allows it to seamlessly monitor two temperature sources simultaneously. This functionality is particularly beneficial in processes where multiple temperature points need to be assessed, optimizing efficiency and reducing the need for additional equipment. It supports various sensor types, including thermocouples, RTDs, and resistance temperature detectors, making it versatile for different applications.

The 848T is equipped with sophisticated digital processing technology, which enhances its accuracy and stability. It features a 24-bit analog-to-digital converter, ensuring precise measurement and minimizing drift over time. Moreover, the device boasts a wide operating temperature range, accommodating ambient conditions from -40°C to 85°C. This durability makes it suitable for harsh environments commonly encountered in industries such as oil and gas, pharmaceuticals, and power generation.

Another significant characteristic of the Emerson 848T is its configurable output options. Users can choose from a range of output signals, including 4-20 mA, which provides a standard interface for integration into existing control systems. Additionally, it offers a HART communication protocol, allowing for easy configuration, calibration, and diagnostics through a digital interface. This feature enhances the transmitter's usability, enabling operators to perform adjustments without direct access to the device.

The device is designed with user-friendliness in mind. Its intuitive setup procedure and robust graphical user interface simplify the commissioning process, ensuring that even those new to the technology can easily navigate the system. An integrated LCD display provides real-time readings and status information, facilitating monitoring at a glance.

In summary, the Emerson 848T temperature transmitter combines reliable performance, user-friendly design, and advanced digital technologies. Its dual-channel capability, wide sensor compatibility, and adjustable output options make it an essential tool for achieving precise temperature measurements in various industrial settings. With these compelling features, the Emerson 848T stands out as a leading choice for professionals seeking accuracy and efficiency in their temperature monitoring applications.