INSTALLATION
The following instructions are provided for qualified installers so that they may carry out installation, adjustment and technical maintenance operations correctly and in compliance with the applicable norms in force.
Important: Disconnect the appliance from the electrical and gas supply before performing any maintenance or repair.
The cooker has the following technical specifications: - Cat. II2H3+
Class 1 Class 2
The dimensions of the appliance are given in the figure on page 5, 'KNOW YOUR COOKER'. For
fig.5
min. 100mm | 700mm | |
min. | ||
|
fig.6
95÷ 155mm
Prior to installing the cooker, the 95 - 155 mm high supporting feet (provided) should be fitted into the holes to be underneath the cooker (fig. 6). These feet are screw- adjustable and whenever necessary should be used to make sure the cooker is level.
Positioning
This appliance may only be installed and operated in permanently ventilated rooms in compliance with the regulation s in force. The following requirements must be observed:
•The appliance must vent flue gases into a special hood, which must be connected to a chimney, flue pipe or directly to the outside (fig. 7).
•If it is impossible to fit a hood, the use of an electric fan is permitted, either installed on a window or on an external wall, which must be switched on at the same time as the
appliance.
fig.7
In a chimney stack or branched flue | Directly to the outside |
(reserved for cooking appliances |
|
Kitchen ventilation
The air flow into the room where the appliance is installed must equal the quantity of air that is required for regular combustion of the gas and for ventilating the same room. Air must enter naturally through permanent apertures made in the outside walls of the room or through single or branching collective ventilation ducts in compliance with the norms. The air must be taken directly from the outside, from an area far from sources of pollution. The ventilation aperture must have the following characteristics (fig. 8A):
•total free cross section of passage of at least 6 cm² for every kW of rated heating capacity of the appliance, with a minimum of 100 cm² (the heating capacity is indicated on the rating plate);
•it must be made in such a way that the aperture, both on the inside and outside of the wall, cannot be obstructed;
•it must be protected, e.g. with grates, wire mesh, etc. in such a way that the
•it must be situated as near to floor level as possible.
|
| Detail A |
|
|
| Adjacent | Room to be | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| room | ventilated | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A
Examples of ventilation | Enlarging the ventilation slot |
holes for comburant air | between window and floor |
fig. 8A | fig.8B |
The air inflow may also be obtained from an adjoining room, provided the latter is not a bedroom or a room where there is a risk of fire, such as warehouses, garages, fuel stores, etc. and is ventilated in compliance with the norms. The air flow from the adjoining room to the one to be ventilated may pass freely through permanent apertures with a cross section at least equal to that indicated above. These apertures may also be obtained by increasing the gap between the door and the floor (fig. 8B). If an electric fan is used for extracting the combustion products, the ventilation aperture must be increased in relation to its maximum performance. The electric fan should have a sufficient capacity to guarantee an hourly exchange of air equal to 3 ÷ 5 times the volume of the kitchen. Prolonged, intensive use of the appliance may require extra ventilation,