WARNING: ELECTRICAL AND GROUNDING CONNECTION MUST COMPLY WITH THE APPLICABLE PORTION OF THE NATIONAL ELECTRICAL CODE AND/OR OTHER LOCAL ELECTRICAL CODES.
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY AND PLACE A TAG AT THE DISCONNECT SWITCH INDICATING THAT YOU ARE WORKING ON THE CIRCUIT.
ELECTRICAL DATA
Models | Volts / Hz / Ph | Rated | Circuit Size | Fuse Size * | 60°C Copper | Circuit Size | Circuit Breaker ** | 60°C Copper | |
Amps | (Amps) | (Amps) | Wire Size | (Amps) | (Amps) | Wire Size | |||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
D340 | 120 / 60 / 1 | 25.0 | 35 | 35 | 8 | 35 | 35 | 8 | |
D340 | 208 / 60 / 1 | 14.0 | 20 | 20 | 12 | 20 | 20 | 12 | |
D340 | 240 / 60 / 1 | 12.5 | 20 | 20 | 12 | 20 | 20 | 12 | |
D340 | 208 / 60 / 3 | 5.0 | 15 | 6 | 14 | 15 | 10 | 14 | |
D340 | 240 / 60 / 3 | 5.0 | 15 | 6 | 14 | 15 | 10 | 14 | |
D340 | 480 / 60 / 3 | 2.5 | 15 | 3 | 14 | 15 | 6 | 14 | |
|
|
|
| * Dual Element |
|
| ** Inverse Time |
| |
|
|
|
|
| Circuit Breaker |
| |||
|
|
|
|
|
|
|
|
|
Circuit Size (Minimum) & Fuse / Circuit Breaker Size (Maximum) compiled in accordance with the National Electrical Code (ANSI/NFPA 70), 1993 Edition.
Ahole for 3⁄4" trade size conduit is located at the top of the pedestal (Fig. 1). Make electrical connections per the wiring diagram located on the inside of the Top Cover.
Fig. 1
Check Rotation (Three-Phase Machines Only)
Set the gear shift lever on 1.
Apply power to the mixer, set the
If rotation is incorrect, DISCONNECT ELECTRICAL POWER SUPPLY and interchange any two of the incoming power supply leads.
– 4 –