Hobart AM14 ML-110976, AM14C ML-110977 manual Venting Requirements with GAS Tank Heat

Page 8

The dishwasher must be installed so that the flow of combustion and ventilation air will not be obstructed. Adequate clearances for air openings into the combustion chamber must be provided. Make sure there is an adequate supply of make-up air in the room to allow for combustion of the gas at the burner(s).

Keep the appliance area free and clear from all combustible substances. Do not obstruct the flow of combustion and ventilation air. The dishwasher must have a minimum clearance from combustible construction of 1 inch from the flue at the rear and 0 inches at the sides. A clearance of 40 inches must be provided at the front of the dishwasher for servicing and proper operation.

The burner is ignited automatically by solid state electronic circuitry; there is no pilot light. Gas flow is regulated by the temperature control circuit.

VENTING REQUIREMENTS — WITH GAS TANK HEAT

The Hobart AM14 / AM14C dishwasher equipped for gas tank heat is not provided with a flue collar and is not intended to have the flue directly connected to a ventilation system. However, the products of combustion must be vented to the outside air. The most common method of venting is a vent hood over the entire dishwasher (Fig. 4). Refer to Rate of Exhaust Flow Calculations on the next page for calculations of the proper vent rate for your hood. Another method is a small vent hood (Fig. 5) positioned about five inches above the flue exit at the rear of the dishwasher and connected to existing ductwork. In either case, an electrical interlock must be provided to allow the flow of gas to the dishwasher burner ONLY when the exhaust system is energized. For additional information, refer to the National Fuel Gas Code, ANSI Z223.1, NFPA 54.

IMPORTANT: Make sure the installation meets the local code for your area.

1' TO 4'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLEARANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 4

 

 

 

3" x 3" DUCT INTO

 

 

 

CURRENT SYSTEM

 

 

 

31/2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4"

MINIMUM

 

 

 

 

 

 

 

 

 

MINI VENT HOOD

 

 

 

 

 

 

 

 

 

 

 

 

 

OVERHANG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON ALL SIDES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18" OVERHANG

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OVER LOADING OR

 

 

 

 

 

 

 

 

 

5" GAP

 

 

 

 

 

 

 

 

 

 

UNLOADING DOORS

 

 

 

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISHWASHER FLUE EXIT

Fig. 5

– 8 –

Image 8
Contents Model AM14 & AM14C Dishwashers For Your Safety Table of Contents Model AM14 & AM14C Dishwashers General Installation Installation CodesUnpacking LocationWater Requirements Plumbing Connections Drain ConnectionWater Connection Without Electric or Gas Booster Water HeaterGAS Tank Heat When Specified With Electric Booster Water HeaterVenting Requirements with GAS Tank Heat Rate of Exhaust Flow Calculations Check Rotation Three-Phase Machines Only Electrical ConnectionsDishwasher Electric Booster Water HeaterElectrical Data Hobart Infrared Booster Gas Water HeaterChemical Sanitizer Dispenser Detergent DispenserRinse Aid Dispenser Rinse Aid and / or Sanitizer Dispenser Fig Operation PreparationDishwashing Cleaning DOs and DONTs for Your NEW Hobart Warewasher Maintenance Wash ArmsRemoving Wash / Rinse Arms AM14 / AM14C MotorsSymptom Possible Cause TroubleshootingManual Reset Button on Pump Motors Service