5. Install Unit.

Use a crane and spreader bar to prevent damage to unit. Lifting lugs are provided as shown in illustration.

It is highly recommended that all accessory items be lifted separately and attached after the unit is in place.

Electrical and pipe connections can be made at this time.

6. Attach Filter/Coil Section (if included) Use a crane and spreader bar hooked to factory

lifting lugs (as shown in diagram) to lift and center the filter section on the NV unit. Note that the top U- shaped flange on the filter section fits over the vertical flange of the NV unit (see detail A). Use sheet metal screws to fasten the filter section to NV unit. Mounting holes are prepunched, see diagram for approximate hole locations.

Filters ship separately. To install, remove side panel on filter section and slide into filter channels. Note arrows on filters for correct orientation.

Spreader Bar

Lifting Lugs (2)

Note:

If the optional up-stream heating coil section is included with the unit, special support for this section is required. See page 8 for requirements.

KSU Unit

Detail A

Filter/Coil Section

Fasten through both flanges.

Butt units together

Filter /Coil section fastener locations typical for entire section.

Top fasteners are accessed from outside, side fasteners are accessed from inside, bottom fasteners are accessed from underneath filter section (Note: bottom fasteners are not required for slab mounted units).

10

Image 10
Contents Greenheck Table of Contents Mounting the Unit Installation Instructions forTypical Installations Attach Ductwork to Unit DischargeNV-45 w/Downblast Discharge Install Roof Curb Equipment SupportInstall Ductwork Roof OpeningInstall Supply Unit Complete Installation1b. Install Unit 1a. Slab ConstructionRail Mounting Curb MountingOptional Up-stream Heating Coil Discharge Opening SizesAssemble Roof Curb Install CurbLocate and Cut Roof Opening Install Unit Detail aAttach Support Legs Install Birdscreen or Optional Weatherhood FiltersAttach Weatherhood For units without control centers Sequence for wiring NV unitElectrical Instructions For units with control centersSpecial Tools Required Check Voltage Air Volume Check and MeasurementSettings for Optional Components Check Blower RotationInstructions for Coils Steam CoilsDirect Expansion Coils Main SteamWater Coils Coil MaintenanceCleaning FiltersBlower Unit General Dimensions and Weights Elevation ViewEvery 3 Months MaintenanceWeeks after startup YearlyMaintenance Documentation Field Start-Up Documentation