Carrier 23 XL installation instructions General

Page 33

IMPORTANT: Refer to certi®ed drawings for addi- tional information. Certi®ed drawings are available upon request.

LEGEND

Required Power Wiring

Required Control Wiring

Options Wiring

NOTES:

I.GENERAL

1.0Starters shall be designed and manufactured in accordance with Carrier Engineering Requirement Z-375.

1.1All ®eld-supplied conductors, devices, ®eld-installation wiring, and ter- mination of conductors and devices, must be in compliance with all applicable codes and job speci®cations.

1.2The routing of ®eld-installed conduit and conductors and the location of ®eld-installed, devices must not interfere with equipment access or the reading, adjusting, or servicing of any component.

1.3Equipment installation and all starting and control devices must com- ply with details in equipment submittal drawings and literature.

1.4Contacts and switches are shown in the position they would assume with the circuit deenergized and the chiller shut down.

1.5WARNING Ð Do not use aluminum conductors.

II.POWER WIRING TO STARTER

2.0Power conductor rating must meet minimum unit nameplate voltage and compressor motor RLA (rated load amps).

When (3) conductors are used:

Minimum ampacity per conductor = 1.25 x compressor RLA

When (6) conductors are used:

Minimum ampacity per conductor = 0.721 x compressor RLA

2.1Lug adapters may be required if installation conditions dictate that con- ductors be sized beyond the minimum ampacity required. Solid-state starters are provided with:

A.Two (2) 0-250 MCM lugs provided per phase for power conductor terminations when compressor motor RLA is 400 amps or less.

B.Three (3), 250-500 MCM lugs provided per phase for power con- ductor terminations when compressor motor RLA is more than 400 amps.

Wye-Delta starters are provided with:

A.Two (2) 250-500 MCM lugs provided per phase for power conduc- tor terminators when compressor motor RLA is 420 amps or less.

B.Two (2) #1-500 MCM lugs provided per phase for power conductor terminations when compressor motor RLA is more than 420 amps.

2.2Power conductors to starter must enter through top of enclosure. Flex- ible conduit should be used for the last few feet to the enclosure to provide unit vibration isolation.

2.3Compressor motor and controls must be grounded by using equip- ment grounding lugs provided inside starter enclosure.

2.4Wye-Delta starters require the assembly and the installation of a ``Top Hat'' (located inside enclosure) to provide the required wire bending space for incoming power leads.

III.CONTROL WIRING

3.0Field supplied control conductors to be at least 18 AWG (American Wire Gage) or larger.

3.1Chilled water and condenser water ¯ow switch contacts, optional re- mote start device contacts and optional spare safety device contacts, must have 24 vdc rating. Max current is 60 ma, nominal current is 10 ma. Switches with gold plated bifurcated contacts are recommended.

3.2Remove jumper wire between 12A and 12B before connecting auxil- iary safeties between these terminals.

3.3Pilot relays can control cooler and condenser pump and tower fan mo- tor contactor coil loads rated 10 amps at 115 vac up to 3 amps at 600 vac. Control wiring required for Carrier to start pumps and tower fan motors must be provided to assure machine protection. If primary pump and tower fan motor control is by other means, also provide a parallel means for control by Carrier. Do not use starter control transformer as the power source for pilot relay loads.

3.4Do not route control wiring carrying 30 v or less within a conduit which has wires carrying 50 v or higher or along side wires carrying 50 v or higher.

Fig. 34 Ð 23XL Typical Field Wiring with Optional Unit-Mounted Starter (Frame 1 and 2 Machines Shown)

33

Image 33
Contents Installation Instructions Contents Typical 23XL Installation Frame 1 and 2 Machines Typical 23XL Installation Frame 4 Machine Options English SizeMachine Rigging Guide Frame 4 Machines Width Height Size Heat Exchanger Length Overall Nozzle Pipe SizeWidth Height Heat Exchanger Length OverallUnit Compressor Size AssemblyComponent Frame 1 CompressorHeat Waterbox Heat Exchanger Waterbox PSI Frame DescriptionExchanger Description CoolerPage 23XL Drive End View Frame 1 and 2 Machines 23XL Top View Frame 1 and 2 Machines 23XL Top View Frame 4 Machines Motor Cooling Drain Section Frame 4 Machines Install Machine Supports Standard Isolation Connect Piping Typical Nozzle Piping Nominal Pipe Actual Pipe Frame Nozzle Arrangement CodesNominal Pipe Actual Pipe Frame Pass Piping Flow Data FrameTank Size Weight ASHRAE/ANSI SizeTrade QTY Location Size AnsiPage Page Pumpout Unit Page Page Page Manufacturer Cable no Carrier Comfort Network Communication Bus WiringInstall Field Insulation Typical COMM1 CCN Communication Wiring for Multiple Chillers 23XL Insulation Area for Frame 1 and 2 Machines General Copyright 1994 Carrier Corporation Installation START-UP Request Checklist Testing YES/NO Date to be Completed

23 XL specifications

The Carrier 23 XL series is an advanced line of air conditioning units designed for optimal cooling performance and energy efficiency. This unit stands out in the HVAC industry due to its integration of cutting-edge technologies and user-friendly features.

One of the main features of the Carrier 23 XL is its use of the Greenspeed Intelligence technology. This innovative system allows the unit to modulate its cooling output based on the actual needs of the environment, resulting in significant energy savings. By adjusting the compressor speed, the 23 XL can maintain a consistent temperature without the energy spikes common in traditional air conditioning systems.

Another notable characteristic of the Carrier 23 XL is its high SEER rating, which stands for Seasonal Energy Efficiency Ratio. The 23 XL boasts a SEER rating of up to 24, making it one of the most efficient units available on the market. This efficiency translates to lower utility bills and a reduced carbon footprint, which is a crucial consideration in today’s sustainability-focused world.

The Carrier 23 XL is also equipped with a variable-speed compressor, which enhances its overall performance. This component allows for quieter operation, providing comfortable indoor conditions without noise disturbances. Homeowners can enjoy peace and quiet while the system operates seamlessly in the background.

Moreover, the Carrier 23 XL features advanced air filtration capabilities. The unit is designed with high-efficiency filters that capture dust, pollen, and other airborne particles, improving indoor air quality. This feature is particularly beneficial for individuals with allergies or respiratory conditions, as it ensures a healthier living environment.

The sleek and compact design of the Carrier 23 XL makes it suitable for various installation configurations, maintaining aesthetic appeal without sacrificing performance. Additionally, it offers a range of smart features, such as compatibility with Wi-Fi-enabled thermostats, allowing users to control their home environment remotely via smartphone applications.

Finally, Carrier’s commitment to quality and reliability is evident in the 23 XL model. With robust construction and a warranty that provides peace of mind, homeowners can trust that their investment will deliver comfort and efficiency for years to come. Overall, the Carrier 23 XL is an exceptional choice for those seeking a blend of advanced technology, energy efficiency, and superior indoor comfort.