Liebert 3000 installation manual Piping connections for chilled water self-contained units

Page 16

Installation

Figure 7 Piping connections for chilled water self-contained units

UPFLOW (BU) MODELS

Piping outlet locations through

the plenum are the same as the unit. See below for descriptions and connectoin sizes

Humidifier Water Supply

Line 1/4" OD CU

Condenser Re turn Line 7/8" OD CU on Models

BU046WG/BU045WG 1 1/8" OD CU on Models

BU071WG/BU070WG

Condensate Pump Line 1/2" OD CU

Used only if optional condensate pump is ordered

Hot Water Return Line 5/8" OD CU (optional)

Condenser Supply Line 7/8" OD CU on Models BU046WG/BU045WG

1 1/8" OD CU on Models BU071WG/BU070WG

Hot Water Supply 5/8" OD CU (optional)

Monitoring Panel

Condensate Drain 3/4" FPT

Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without a condensate pump have a factory-supplied trap in the unit, so a field trap should not be added. Units with a condensate pump will require a field-supplied trap downstream from the pump. The drain line must comply with all applicable codes. (If condensate pump is ordered piping is out top of unit).

PIPING OUTLET LOCA TIONS

(See Cabinet and Floor Planning

Dimensional Data for Piping

Opening Sizes.)

SL-11898 PG 9

10

Image 16
Contents Liebert Challenger Page Table of Contents Split System Models Chilled Water ModelsR407C Refrigerant Figures Tables System Descriptions Room Preparation Equipment InspectionLocation Considerations Equipment HandlingRemoval of Skid Unit net weightModel Lbs kg Rear return configuration Front return configurationFloor Cutout Dimensions Drain Line Piping ConsiderationsPiping connection size Hot GasRefrigerant Line HumidifierWater SupplyLine Suction Refrigerant LineCondensate Pump Line Condensate DrainCondenser SupplyLine Condenser Return LineHotWater Return HumidifierWater SupplyLine Hot Water SupplyPiping connections for chilled water self-contained units Installation Electrical Connections Electrical connectionsBalancing the Air Distribution Under-Floor Discharge SystemsHz Units 550 600 Model Ton Hz Units 550 600 ModelPlenum Installation Checklist for Completed InstallationDucted Applications Installation Condenser Location Line VoltageLow Voltage Lee-Temp/Flood Back Head Pressure Control CondensersAir cooled condenser statistics Refrigerant Piping Recommended line sizes OD copper inchesFan Speed Control Systems Materials SuppliedEquivalent lengths feet for various pipe fittings Condenser refrigerant per serial tagDehydration/Leak Test Single Circuit Shown Refrigerant control settings psi kPa Lee-Temp/Flood Back Head Pressure Control SystemsCharging PipingMaterials Supplied Low Pressure Cut Out High Pressure Cut Out 360 Single Circuit Shown Condenser Water cooled general arrangement Water Regulating Valve AdjustmentManual Flushing Testing Valve Function Adjusting collar nutDrycooler Location Drycooler InstallationPump and Drycooler Glycol Piping Room dew point temperaturesDry Bulb Wet Bulb Relative Dew Point Humidity Volume in standard Type L copper piping Filling InstructionsExpansion Tanks, Fluid Relief Valves and Other Devices Preparing the System for FillingEthylene glycol concentrations Glycol Solutions@ 50F 10C Filling the System For expansion tank dimensions, see on 43-3/16 43-9/16 110 5mmSee Note 30-1/4 1095mm 483mm 1097mmMounting hole dimensional data Drycooler dataGlycol pump data Pump Pump Suction Pump Discharge ConnectionFactory Glycool general arrangement Glycol Regulating Valve Chilled Water Models WAY Valve Air Cooled Condensing Units Water/Glycol Cooled Condensing UnitsRefrigerant Loop Recommended refrigerant lines R22 or R407C sizes OD copper Unit refrigerant chargeLine coupling sizes Refrigerant piping diagram Quick Connect Fittings Unit Dimensions See Table Outdoor Air Cooled Condensing UnitsPFCZ42A-L PFCZ41A-L Outdoor air cooled condensing unit-top air discharge models See Table36-1/4 38-1/2 Piping and electrical connections top air discharge152 SL-11081 PG 8A Discharge ModelsInstalling the Indoor Condensing Unit Model Net Weight 60 Hz 50 Hz Lbs kgCentrifugal Air Cooled Condensing Units Indoor centrifugal condensing unitDetail of ceiling hanging bracket Airflow CFM CMH DuctingTon Dimensional Data Piping Connections DPN000207Rev0 Ton centrifugal air cooled condensing unitTon centrifugal air cooled condensing unit dimensional data DPN000226Rev0 Water Cooled Water and Glycol Cooled Condensing Units Piping ConsiderationsCondenser Water Requirements Regulating ValvePiping Connections DPN000209Rev0 Ton water/glycol cooled condensing unit dimensional data DPN000228Rev0 Temperature Gauge Pressure Psig KPa R407C RefrigerantCalculating Subcooling Temperature Pressure Gauge Psig KPaExample R407C Refrigerant R407C Refrigerant Page Net ItiTin That
Related manuals
Manual 76 pages 7.19 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.