Liebert 3000 installation manual Ducting, Airflow CFM CMH, Ton

Page 60

Split System Models

7.5.2Ducting

The total external static pressure for the inlet and outlet ducts, including grille, must not exceed 0.5 inches of H2O. Hood intake dimensions should be the same as the condensing unit duct dimen- sions.

If the condensing unit is located close to the outside of the building, rain hoods must be installed. In addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of insects, birds, water, or debris entering the unit.

Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control vibration transmission to the building. Attach the ductwork to the unit using the flanges provided. Locate the unit and ductwork so that the return air does not short circuit to the supply air inlet.

Avoid directing the hot exhaust air toward adjacent doors or windows.

Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work areas. Ductwork that runs through a conditioned space or is exposed to areas where condensation may occur must be insulated. Whenever possible, ductwork should be suspended using flexible hang- ers. Ductwork should not be fastened directly to the building structure. In applications where the ceil- ing plenum is used as the heat rejection domain, the discharge air must be directed away from the condensing unit air inlet and a screen must be added to the end of the discharge duct to protect ser- vice personnel.

For multiple unit installations, space the units so that the hot condensing unit exhaust air is not directed toward the air inlet of an adjacent unit.

Table 31 Airflow CFM (CMH)

 

3 Ton

5 Ton

 

 

 

60 Hz

2000 (3398)

3500 (5947)

 

 

 

50 Hz

1650 (2800)

3500 (5947)

 

 

 

54

Image 60
Contents Liebert Challenger Page Table of Contents Chilled Water Models Split System ModelsR407C Refrigerant Figures Tables System Descriptions Room Preparation Equipment InspectionLocation Considerations Equipment HandlingUnit net weight Removal of SkidModel Lbs kg Rear return configuration Front return configurationFloor Cutout Dimensions Piping Considerations Drain LinePiping connection size Hot GasRefrigerant Line HumidifierWater SupplyLine Suction Refrigerant LineCondensate Pump Line Condensate DrainCondenser SupplyLine Condenser Return LineHotWater Return HumidifierWater SupplyLine Hot Water SupplyPiping connections for chilled water self-contained units Installation Electrical Connections Electrical connectionsBalancing the Air Distribution Under-Floor Discharge SystemsHz Units 550 600 Model Ton Hz Units 550 600 ModelChecklist for Completed Installation Plenum InstallationDucted Applications Installation Condenser Location Line VoltageLow Voltage Lee-Temp/Flood Back Head Pressure Control CondensersAir cooled condenser statistics Refrigerant Piping Recommended line sizes OD copper inchesFan Speed Control Systems Materials SuppliedEquivalent lengths feet for various pipe fittings Condenser refrigerant per serial tagDehydration/Leak Test Single Circuit Shown Refrigerant control settings psi kPa Lee-Temp/Flood Back Head Pressure Control SystemsCharging PipingMaterials Supplied Low Pressure Cut Out High Pressure Cut Out 360 Single Circuit Shown Condenser Water cooled general arrangement Adjustment Water Regulating ValveManual Flushing Testing Valve Function Adjusting collar nutDrycooler Installation Drycooler LocationPump and Drycooler Room dew point temperatures Glycol PipingDry Bulb Wet Bulb Relative Dew Point Humidity Volume in standard Type L copper piping Filling InstructionsExpansion Tanks, Fluid Relief Valves and Other Devices Preparing the System for FillingGlycol Solutions Ethylene glycol concentrations@ 50F 10C Filling the System For expansion tank dimensions, see on 43-3/16 43-9/16 110 5mmSee Note 30-1/4 1095mm 483mm 1097mmMounting hole dimensional data Drycooler dataGlycol pump data Pump Pump Suction Pump Discharge ConnectionFactory Glycool general arrangement Glycol Regulating Valve Chilled Water Models WAY Valve Air Cooled Condensing Units Water/Glycol Cooled Condensing UnitsRefrigerant Loop Unit refrigerant charge Recommended refrigerant lines R22 or R407C sizes OD copperLine coupling sizes Refrigerant piping diagram Quick Connect Fittings Unit Dimensions See Table Outdoor Air Cooled Condensing UnitsPFCZ42A-L PFCZ41A-L Outdoor air cooled condensing unit-top air discharge models See TablePiping and electrical connections top air discharge 36-1/4 38-1/2152 SL-11081 PG 8A Discharge ModelsInstalling the Indoor Condensing Unit Model Net Weight 60 Hz 50 Hz Lbs kgCentrifugal Air Cooled Condensing Units Indoor centrifugal condensing unitDetail of ceiling hanging bracket Ducting Airflow CFM CMHTon Dimensional Data Piping Connections DPN000207Rev0 Ton centrifugal air cooled condensing unitTon centrifugal air cooled condensing unit dimensional data DPN000226Rev0 Water Cooled Water and Glycol Cooled Condensing Units Piping ConsiderationsCondenser Water Requirements Regulating ValvePiping Connections DPN000209Rev0 Ton water/glycol cooled condensing unit dimensional data DPN000228Rev0 Temperature Gauge Pressure Psig KPa R407C RefrigerantTemperature Pressure Gauge Psig KPa Calculating SubcoolingExample R407C Refrigerant R407C Refrigerant Page Net ItiTin That
Related manuals
Manual 76 pages 7.19 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.