Liebert 3000 installation manual Tables

Page 6

TABLES

Table 1 Unit net weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Table 2 Piping connection size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Table 3 Recommended free area ft2 (m2) for grilles or perforated panels at output velocities of 550

and 600 fpm (2.8 and 3.1 m/s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 4 Air cooled condenser statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Table 5 Recommended line sizes — OD copper (inches)* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Table 6 Equivalent lengths (feet) for various pipe fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Table 7 Indoor unit refrigerant charge lbs (kg) R22 or R407C (per unit serial tag). . . . . . . . . . . . . . . . . . 19 Table 8 Line charges - refrigerant per 100 ft (30 m) of Type "L" copper tube. . . . . . . . . . . . . . . . . . . . . . . 19 Table 9 Condenser refrigerant (per serial tag) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Table 10 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Table 11 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 12 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Table 13 Room dew point temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Table 14 Indoor unit glycol volume approximate gallons (liters) max. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Table 15 Volume in standard Type “L” copper piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Table 16 Ethylene glycol concentrations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Table 17 Mounting hole dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Table 18 Drycooler data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Table 19 Glycol pump data* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Table 20 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Table 21 Unit refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Table 22 Line charges - refrigerant per 100 ft (30 m) of Type "L" copper tube. . . . . . . . . . . . . . . . . . . . . . . 44 Table 23 Recommended refrigerant lines (R22 or R407C) sizes OD copper . . . . . . . . . . . . . . . . . . . . . . . . . 44 Table 24 Line coupling sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Table 25 Equivalent lengths (feet) for various pipe fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Table 26 Horizontal air discharge cabinet and floor planning dimensional data. . . . . . . . . . . . . . . . . . . . . 48 Table 27 Horizontal air discharge piping and electrical connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Table 28 Cabinet and floor planning dimensional data - prop fan condensing modules, top air

discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Table 29 Piping and electrical connections - top air discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Table 30 Indoor centrifugal condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Table 31 Airflow CFM (CMH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Table 32 Water and glycol cooled condensing unit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Table 33 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and

suction gas) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Table 34 R407C pressure/temperature chart for subcooling only (liquid measurements). . . . . . . . . . . . . . 66

iv

Image 6
Contents Liebert Challenger Page Table of Contents Chilled Water Models Split System ModelsR407C Refrigerant Figures Tables System Descriptions Location Considerations Room PreparationEquipment Inspection Equipment HandlingUnit net weight Removal of SkidModel Lbs kg Rear return configuration Front return configurationFloor Cutout Dimensions Piping Considerations Drain LinePiping connection size Hot GasRefrigerant Line Condensate Pump Line HumidifierWater SupplyLineSuction Refrigerant Line Condensate DrainHotWater Return Condenser SupplyLineCondenser Return Line HumidifierWater SupplyLine Hot Water SupplyPiping connections for chilled water self-contained units Installation Electrical Connections Electrical connectionsHz Units 550 600 Model Balancing the Air DistributionUnder-Floor Discharge Systems Ton Hz Units 550 600 ModelChecklist for Completed Installation Plenum InstallationDucted Applications Installation Low Voltage Condenser LocationLine Voltage Lee-Temp/Flood Back Head Pressure Control CondensersAir cooled condenser statistics Refrigerant Piping Recommended line sizes OD copper inchesEquivalent lengths feet for various pipe fittings Fan Speed Control SystemsMaterials Supplied Condenser refrigerant per serial tagDehydration/Leak Test Single Circuit Shown Charging Refrigerant control settings psi kPaLee-Temp/Flood Back Head Pressure Control Systems PipingMaterials Supplied Low Pressure Cut Out High Pressure Cut Out 360 Single Circuit Shown Condenser Water cooled general arrangement Adjustment Water Regulating ValveManual Flushing Testing Valve Function Adjusting collar nutDrycooler Installation Drycooler LocationPump and Drycooler Room dew point temperatures Glycol PipingDry Bulb Wet Bulb Relative Dew Point Humidity Expansion Tanks, Fluid Relief Valves and Other Devices Volume in standard Type L copper pipingFilling Instructions Preparing the System for FillingGlycol Solutions Ethylene glycol concentrations@ 50F 10C Filling the System See Note 30-1/4 For expansion tank dimensions, see on43-3/16 43-9/16 110 5mm 1095mm 483mm 1097mmGlycol pump data Mounting hole dimensional dataDrycooler data Pump Pump Suction Pump Discharge ConnectionFactory Glycool general arrangement Glycol Regulating Valve Chilled Water Models WAY Valve Air Cooled Condensing Units Water/Glycol Cooled Condensing UnitsRefrigerant Loop Unit refrigerant charge Recommended refrigerant lines R22 or R407C sizes OD copperLine coupling sizes Refrigerant piping diagram Quick Connect Fittings Unit Dimensions See Table Outdoor Air Cooled Condensing UnitsPFCZ42A-L PFCZ41A-L Outdoor air cooled condensing unit-top air discharge models See TablePiping and electrical connections top air discharge 36-1/4 38-1/2152 SL-11081 PG 8A Discharge ModelsCentrifugal Air Cooled Condensing Units Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lbs kg Indoor centrifugal condensing unitDetail of ceiling hanging bracket Ducting Airflow CFM CMHTon Dimensional Data Piping Connections DPN000207Rev0 Ton centrifugal air cooled condensing unitTon centrifugal air cooled condensing unit dimensional data DPN000226Rev0 Water Cooled Condenser Water Requirements Water and Glycol Cooled Condensing UnitsPiping Considerations Regulating ValvePiping Connections DPN000209Rev0 Ton water/glycol cooled condensing unit dimensional data DPN000228Rev0 Temperature Gauge Pressure Psig KPa R407C RefrigerantTemperature Pressure Gauge Psig KPa Calculating SubcoolingExample R407C Refrigerant R407C Refrigerant Page Tin NetIti That
Related manuals
Manual 76 pages 7.19 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.