Heatcraft Refrigeration Products H-IM-82B Standard Installation Procedure, Drain Line, PTT Models

Page 6

uctionsOperating 1.Owner's

The Outdoor comes standard with the following additional components:

Crankcase Heater

Drain Line Heater

Weather Hood

Fan Cycling

(Pressure on 1 fan models, Pressure and Ambient on 2 fan models).

Standard Installation Procedure

PTT Models

For outdoor use

1.Provide a 25" X 25" (medium cabinet) or 25" X 38.5" (large cabinet) opening in the roof of walk-in cooler or as specified by the panel manufacturer.

2.Apply silicone caulk around the perimeter of roof opening. Place the curb on roof of cooler. It is recommended that the curb be fastened to

the roof panels using non-conductive bolts or insulating the bolt heads. Bolt heads should be countersunk or low profile to prevent contact with the system. (See Figure 1, page 7) Check the top of the curb with a level. units require

a surface that is within 1° of level or better and no more than a 5/8" drop per 3 feet

(17mm drop per meter).

3.Install the membrane onto the roof of the box and over the curb. Fasten to roof per panel manufacturer's instructions. The membrane material should be slit over the evaporator grill opening the flaps allowed to drape into the hole 2" - 4". (See Figure 2, page 7) Care should be taken during the membrane installation to prevent bunching or folding which could affect the gasket- to-curb sealing or trap rainwater adjacent to the curb.

4.Remove the weather hood from the system. The compressor compartment cover(s) should be left in place during lifting/rigging.

5.Place system onto curbing and center over opening in roof box. (See Figure 3, page 7)

6.It is recommended that the system be secured to the curb with wood screws. Seal the screw heads as necessary to prevent moisture from entering beneath the membrane. Additional caulk may be applied around the perimeter of the evaporator box gasket. The compressor compartment should not be caulked.

7.Install trim pieces (if used) around the ceiling opening in cooler.

Condensate Drain

Outlet Location

8.Remove compressor compartment cover for access to electrical box.

9.Connect power wiring in accordance with all applicable building and electrical codes.

10.Reinstall condensing unit cover(s).

11.Reinstall the protective weather hood. (See Figure 4, page 7)

12.Apply power and check for proper operation.

Drain Line

A condensate drain outlet is located on the side of the compressor compartment. Field piping may be connected to the outlet provided it is adequately sloped and heated for freezing weather conditions. There is a drain line "P" trap located in the PTT unit.

General Safety information:

Do NOT lift the by the weather hood.

This product is not designed to be transported while installed or operating.

Image 6
Contents Refrigeration System Performance / Electrical Data Coolers Air Defrost Systems SpecificationsUctionsOperating 1.Owners Freezers Electric Defrost SystemsDimensional Diagrams Owners Operating InstructionsModels PTT 021, 031, 044, 047, 063 Models PTT 052, 069, 099 Top View Two Systems Recommended Unit Placement For PTT ModelsTop View One System MinOperating Instructions Standard Installation Procedure Drain LinePTT Models Owners Operating Instructions Freezers HOW to Start a Manual Defrost HOW to see the SetpointHOW to Change the Setpoint HOW to Enter the Hidden MenuAlarm Signals Message Cause OutputsCooler Defrost Control Room Thermostat SettingsSystem Standard Maintenance Guidelines Air Defrost Sequence of Operation for CoolersSystem Troubleshooting Chart Problem Possible Causes Possible Corrective StepsReplacement Parts by Right source. Right parts. Right nowDependable. Versatile. Courteous Diagram 1. PTT072H2B Cooler Air Air Defrost 208-230/1/60 B ModelsPTT047H2B, PTT063H2B Defrost 208-230/1/60 Wiring InformationFreezer Electric Defrost VoltagesInformationWirig Models PTT099H2C and PTT128H2C 208-230V/3PH/60HZWiriInformation.5g 230/3/60 Freezer- Electric Defrost Systems Three PhaseOnly PTT069L6CWarranty Statement Optional Three-Year Extended Compressor Warranty