hussman GSVM Model no Refrigerant Suction Pressure Head Pressure Type, Evaporator FAN Motors

Page 13

Be sure that all service valves are open to al- low all of the mixture to be discharged.

b.Connect a deep-drain vacuum pump to both the high and low side of the system. Pull a vacuum on the system to at least 1500 microns.

c.Break the vacuum by adding refrigerant into the system until the pressure is above 0 psig. Always charge the refrigerant line

into the system through a new drier in the charging manifold line. A 16 cubic inch drier is sufficient for this purpose.

d.Repeat steps 2 and 3 two more times, the third time evacuating the system to 500 microns.

The following pressures are optimum when the case in a 75º to 80ºF ambient and is running from 35º to 40ºF cabinet tempera- ture and are for reference only:

MODEL NO.

REFRIGERANT

SUCTION PRESSURE

HEAD PRESSURE

 

TYPE

(psig)

(psig)

 

 

 

 

GSVM4060

R-134a

12-15

130-150

 

 

 

 

 

 

 

 

GSVM4072

R-134a

12-15

130-150

 

 

 

 

 

 

 

 

GSVM5272

R-134a

14-18

130-150

 

 

 

 

GSVM5272

R-404A

40-50

310-320

 

 

 

 

Consult the serial plate for the correct refrigerant charge. This charge is critical and should be weighed in.

TEMPERATURE CONTROL

The temperature control is located in the electrical box. The sensing bulb is lo- cated on the left hand end of the lower back wall.

When replacing make sure the bulb is in the proper location and that the hole in the liner is properly sealed after the replace- ment has been made.

The control is adjustable from –30º to 50ºF (dial face marking). The actual cabinet tem- perature is approximately 6 to 9º warmer than the control setting so this must be taken into consideration.

The control also has an adjustable differen- tial that determines the difference between the cut-in and cut-out temperature. This is adjustable from 5 to 20º. The factory set- ting is from 8-10º to insure proper off time to keep the evaporator from icing.

EVAPORATOR FAN MOTORS

To replace an evaporator fan motor, the product must be removed from the cabinet and the bottom shelf also removed.

Next, remove the plate covering the fans by removing the 2 screws, and 4 bolts holding this in place. The fans are now ac-

13

Image 13
Contents OII Gsvm Table of Contents Table of Contents CON’T Inspection IntroductionSkid Leveling Access Panel RemovalSealing DrainsPower Switch Power RequirementsLoading Electrical BOXConnections Refrigerant RUN Fuse Power Type Amps Amps Cord Specifications DimensionsShelving Maximum Weight Capacity LBS ElectricalTemperature Control Shelves Condensing UnitThermometer Cleaning Interior Cleaning ExteriorLighting Refrigeration Cleaning Stainless Steel SurfacesEvacuation Evaporator FAN Motors Model no Refrigerant Suction Pressure Head Pressure TypeTrouble Probable Cause Solution Trouble Shooting ChartsProblem Solution Trouble Shooting Light ChartGsvm Accessories Ordering Parts Replacement Warranty and Parts InformationCompressor Replacement Procedure Warranty Parts Procedure115 115 115 60 Hz Gsvm 52072 R-404A

GSVM specifications

Hussman Global Multi-Strategy Fund (GSVM) is a prominent investment strategy that employs a multi-faceted approach to asset allocation, blending various investment styles to capitalize on diverse market opportunities. The fund operates under the aegis of Hussman Investment Trust, founded by renowned economist and investment strategist John Hussman. The primary objective of GSVM is to achieve long-term capital appreciation while managing risk through a disciplined investment process.

One of the main features of the Hussman GSVM is its dynamic asset allocation model. This model allows the fund to adjust its exposure to various asset classes based on quantitative assessments of market conditions. The flexibility to shift between equities, fixed income, and alternative investments positions GSVM as a versatile vehicle for navigating changing market landscapes. This adaptability is particularly crucial in volatile markets, where traditional strategies may falter.

The investment philosophy of GSVM is deeply rooted in research-driven methodologies. The fund employs a rigorous analysis of economic indicators, market trends, and valuation metrics to inform its investment decisions. This analytical framework allows for informed positioning within the market, aiming to exploit mispricings while also protecting against downside risks.

One of the defining characteristics of GSVM is its focus on risk management. The fund aims to preserve capital by employing various hedging strategies and maintaining a balanced portfolio. By dynamically hedging potential risks, Hussman GSVM seeks to mitigate losses during market downturns while participating in upswings. This emphasis on risk-adjusted returns distinguishes GSVM from more traditional funds, attracting investors who prioritize capital preservation alongside growth.

In terms of technology, GSVM leverages advanced quantitative models to enhance its decision-making process. By utilizing sophisticated algorithms and data analysis techniques, the fund can evaluate vast amounts of information quickly, identifying trends and potential investment opportunities. This tech-driven approach not only informs strategic asset allocation but also improves the overall efficiency of the investment process.

In summary, Hussman GSVM embodies a comprehensive investment strategy that marries flexibility with a rigorous analytical framework. Its dynamic asset allocation, strong emphasis on risk management, and utilization of advanced technologies contribute to an investment philosophy designed to deliver consistent returns while mitigating volatility. As a result, Hussman GSVM stands out as a compelling option for investors seeking a balanced approach to capital growth and risk control.