HOW TO CHANGE THE SETPOINT
HOW TO CHANGE a parameter value
LIST OF PARAMETERS
Here is a list of the parameters the value of which can be changed in the programming mode, as well as their ranges.
Display | Parameter |
| ||
Symbol | Range | BMG/TMG Setting | ||
| ||||
SP | Temperature Set Point | SPL…SPH | 35°F | |
HYS | Temperature Differential | 1 to 255°F | 5° | |
SPL | Minimum Temperature limit setpoint | 27°F | ||
SPH | Maximum Temperature limit setpoint | SPH…120° | 50°F | |
AHA | High Temperature Alarm | 65°F | ||
ALA | Low Temperature Alarm | 50…120° | 0°F | |
ATD | Temperature Alarm Delay | 0…120min | 30min | |
DFR | Number of Defrost Cycle per 24hr | 0…24 | Off Cycle | |
DLI | Defrost Termination Temperature | - | ||
DTO | Maximum Defrost Duration | 1…120min | 30min |
ELECTRICAL CONNECTIONS
The controller is provided with a screw terminal block to connect cables with a cross section up to 2,5 mm2. Before connecting cables make sure the power supply complies with the control’s requirements. Separate the probe cables from the power supply cables, the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay or contactor’s.
PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damage due to casual liquid infiltration. It is recommended to place the thermostat probe at the warmest loacation of return air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.