supply connects to the terminal block at the rear of the refrigerator (See Figure 9 on page 8). The 12 volt DC should enter the refrigerator’s enclosure near the refrigerator’s terminal block. The 12 volt DC connects at (2) one quarter inch quick connects. The positive DC input lead connects to terminal marked (+), and the DC ground input lead connects to terminal marked
CAUTION: Correct polarity must be ob- served when connecting the DC supply. Do not use the chassis of the refrigerator or the vehicle frame as one of the conduc- tors. Connect DC supply wires at the bat- tery and route to the refrigerator.
The distance the current travels from the battery to the refrigerator dictates the wire size. Undersized wire can result in a voltage drop, which will affect the wattage output of the DC heater and result in re- duced refrigerator performance. Norcold recommends the installation of a fuse in the supply wiring between the battery and the refrigerator. For optimum protec- tion, install the fuse as close to the battery as possi- ble.
WARNING: A circuit overload can result in an electrical fire when undersized wires or improperly sized fuses are used. To pre- vent a possible electrical fire, follow R.V.I.A. A119.2 Standards, Norcold’s wire size and fuse specifications, or applicable state and local codes.
TABLE 3
12 VOLT SUPPLY WIRING AND FUSE SIZE
| 482, 462 | 483, 463 | 453, 443 | |||
| 452, 442 |
|
|
|
| |
| min. | max. | min. | max. | Min. | max. |
| wire | fuse | wire | fuse | wire | fuse |
| size | size | size | size | size | size |
|
|
|
|
|
|
|
0 - 20’ | 18 | 6 Amp | 10 | 30 | 12 | 20 |
| AWG |
| AWG | Amp | AWG | Amp |
|
|
|
|
|
|
|
over | 18 | 6 Amp | 8 | 40 | 10 | 30 |
20’ | AWG |
| AWG | Amp | AWG | Amp |
|
|
|
|
|
|
|
If a wire size is installed which is larger than the minimum size indicated the table above, it must be fused in accordance with the R.V.I.A. A119.2 stand- ard or local governing codes.
Chassis Bonding Connection
A No. 8 AWG copper conductor is commonly used to meet the chassis bonding requirements of the Na-
tional Electric Code (ANSI/NFPA No. 70, Art. 551). When this conductor is used to bond the
Figure 10
Hypot Test
A Dielectric Strength test (hypot) has been con- ducted at the factory; this refrigerator does not re- quire an additional test. If hypot tests are conducted on the vehicle’s 12 volt circuit, the 12 volts must be disconnected from the refrigerator to protect the flame ignition circuit.
Testing the Vehicle’s Gas Supply Piping
When installation of the refrigerator is complete, the propane gas supply piping must be inspected and tested for leaks from the refrigerator to the main gas supply tank. Use a leak detection solution. Do not test for leaks with an open flame.
If compressed air is used for leak testing, the gauge pressure must not exceed 1/2 pound per square inch (14 inches water column).
The appliance and its individual
The appliance must be isolated from the gas supply system by closing its individual manual
Check the gas pressure to the refrigerator without other gas appliances operating. The pressure should not exceed 11 inches water column. With other appli- ances operating the pressure should not be less than 10.5 inches water column.
10