IX. TROUBLESHOOTING GUIDE
PROBLEM |
| POSSIBLE CAUSE/REMEDY |
1. Condensing unit fails to start - no hum. | 1. | Line Disconnected - Reconnect |
| 2. | Fuse - Replace Fuse |
| 3. | Overload Protection - Determine Reason & Correct, |
|
| Replace If Necessary |
2. Condensing unit fails to start - hums but | 1. | Improperly Wired - Check Wiring Against Diagram |
trips on overload protector. | 2. | Low Voltage - Determine Reason & Correct |
| 3. | Starting Capacitor Defective - Determine Reason & Replace |
| 4. | Relay Not Closing - Determine Reason & Correct, |
|
| Replace If Necessary |
| 5. | Compressor Motor Has Winding Open Or Shorted - Replace |
|
| Compressor |
| 6. | Internal Mechanical Trouble In Compressor - Replace |
|
| Compressor |
3. Condensing unit starts, but fails to switch | 1. | Improperly Wired - Check Wiring Against Diagram |
off of “start” winding. | 2. | Low Voltage - Determine Reason & Correct |
| 3. | Relay Failing To Open - Determine Reason & Correct, |
|
| Replace If Necessary |
| 4. | Run Capacitor Defective - Determine Reason & Replace |
| 5. | Excessively High Discharge Pressure - Check Disharge |
|
| |
| 6. | Compressor Motor Has Winding Open Or Shorted - Replace |
|
| Compressor |
| 7. | Internal Mechanical Trouble In Compressor - Replace |
|
| Compressor |
4. Condensing unit starts and runs, but short | 1. | Additional Current Passing Through Overload Protector - |
cycles on overload protector. |
| Check Wiring Diagram. Check For Added Fan Motors, |
|
| Pumps, etc., Connected To Wrong Side Of Protector |
2.Low Voltage To Unit (or unbalanced if three phase) - Determine Reason & Correct
3.Overload Protector Defective - Check Current - Replace Protector
4.Run Capacitor Defective - Determine Reason & Replace
5.Excessive Discharge Pressure - Check Ventilation, Restrictions In Cooling Medium, Restrictions in Refrigeration System
6.Suction Pressure Too High - Check For Possibility Of Misapplication. Use Stronger Unit
7.Compressor Too Hot (return gas) - Check Refrigerant Charge (fix leak) Add If Necessary
8.Compressor Motor Has Winding Shorted - Replace Compressor
5.Condensing unit runs but short cycles on... 1. Overload Protector - See #4 Above
2.Thermostat - Differential Set Too Close, Widen
3.High Pressure
a)Insufficient Air or Water Supply - Check Air or Water Supply To Condenser, Correct
b)Overcharge - Reduce Refrigerant Charge
c)Air In System - Purge
4.Low Pressure
a)Liquid Line Solenoid Leaking - Replac e
b)Compressor Valve Leak - Replace
c)Undercharge - Fix Leak, Add Refrigerant
d)Restriction In Expansion Device - Replace Device