ELECTRICAL

All wiring must conform to the National Electric Code and any applicable local codes. The Chiller must be PERMANENTLY wired by means of electrical conduit to a properly fused disconnect of proper amperage or wired to a properly rated power cord and plugged into an outlet with the appropriate disconnect and amperage rating. The electrical junction box located on the upper rear of the Chiller, includes a four-terminal strip for power supply connections The DATA PLATE, located beside the junction box, indicates the actual phase, voltage and amperage for each Chiller.

After the electrical connections are made, power must be supplied to the Chiller for a period of 12 hours (with control switched off) to allow the compressor crankcase heater to warm the compressor lubricant.

CAUTION: On three phase applications, it is important that the rotation of the pump, when supplied, is correct. Running the pump in reverse for more than a few seconds will result in permanent pump damage. When the pump is running, shaft rotation must match the

direction indicated on the pump housing. If the rotation is incorrect, reverse two of the three incoming power supply leads. The Phase Protection/3–Phase Monitor Option will prevent the pump from operating backwards. See the option description.

Phase Protection / 3–Phase Option

The 3–Phase Monitor detects phase loss, low voltage, and phase reversal by continuously monitoring the 3–Phase power lines for abnormal conditions. When correct voltage and phase rotation are applied, the internal relay will energize. A fault condition will de–energize the relay. When the fault is corrected, the monitor will auto- matically reset. Both Trip and Norm condition indicators are provided on the relay to aid in adjustment and sys- tem trouble–shooting.

This control is located in the enclosure labeled “Monitor” on top of the electrical box.

Phase Protection / 3–Phase Option Adjustment

The following procedure will allow the 3–Phase Monitor to achieve a trip point just below the nominal phase-to- phase voltage, where the unit is applied.

Rotate the adjustment control fully clockwise, or until the red (Trip) indicator illuminated. Slowly rotate the ad- justment control in a counter-clockwise direction, just until the green (Norm) indicator illuminates. At this point, the 3–Phase Monitor is the most sensitive to irregular power line conditions. If nuisance tripping occurs, turn the control slightly further counter–clockwise.

PLUMBING

Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet connections are 3/4–inch or 1–inch FPT. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh strainer should be installed on the Chiller inlet to prevent foreign particles from entering the sys- tem and should be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient tempera- tures should be insulated to prevent condensation and/or significant liquid heat loss.

Water-Cooled Condensers

Water-cooled units must be connected to a source of tap water of chilled water and a drain. The connections for the water supply (3/4–inch FPT or 1–inch FPT) are located on the rear of the unit. These units are supplied with a WATER REGULATING VALVE that allows only the required amount of water to pass through the condenser for a given heat load. The water flow through the condenser can vary from 0 when the cooling system is in the “OFF” cycle to approximately 5.0–gpm at maximum rated loads for 1–1/2 ton units and approximately 20–gpm at maximum rated loads for 7–1/2 ton units. This valve is factory set to operate where the water supply temper- ature ranges from 50_F (10_C) to 80_F (27_C) with a supply pressure of 30 to 60–PSIG. For temperatures or pressure outside these ranges, contact our Technical Service Department for assistance in “field” adjustment of the valve. Once the system as been properly plumbed, it is important that the circulation system be filled with water.

3

91961OPR

Image 6
Contents Chiller Table of Contents Table of Contents cont’d Specification Notes General InformationIntroduction Installation LocationElectrical Phase Protection / 3-Phase OptionPhase Protection / 3-Phase Option Adjustment PlumbingChiller with Reservoir Auto Refill OptionChiller without Reservoir Chiller Plumbing Schematic with Pump and Tank Standard This page Left Blank Intentionally Thermostat Adjustment Start UPWater Flow START-UP Dual Point Adjustment Cooling Start-UpControl Panel 91961OPR Maintenance Fluid Recommendation Lab & Industrial Grade Ethylene GlycolCommercial/Automotive Antifreeze Troubleshooting Power Light OFFHigh Pressure Alarm Service Sample Data Plate for CH5002-AThis page Left Blank Intentionally High Pressure Control HPC Safety ControlsLOW Temperature Control LTC LOW Pressure Control LPCRefrigeration Piping Schematic with HOT GAS Bypass Parts List Index DescriptionPump and Tank Components Electrical BOX Components Warranty Page IMI Cornelius INC

CH1500-CH7500 specifications

The Cornelius CH1500-CH7500 series of beverage dispensers is an innovation in the world of commercial beverage service, combining high performance with user-friendly features. These dispensers are designed for establishments ranging from coffee shops to restaurants, ensuring a consistent and delightful beverage experience for customers.

One of the standout features of the CH1500-CH7500 series is its impressive capacity. With options available that can serve up to 7500 ounces, these dispensers can accommodate high-demand environments, allowing for efficient service during peak hours. This ample capacity minimizes the need for frequent refills, thereby enhancing operational efficiency.

The series is equipped with advanced technology that ensures optimal beverage quality. The integrated refrigeration system maintains precise temperature control, preserving the integrity and flavor of dispensed beverages. Whether serving iced coffee, flavored syrups, or other chilled drinks, the temperature consistency is a significant advantage in maintaining product quality.

User experience is at the forefront of the CH1500-CH7500 design. The interface features an intuitive, easy-to-use control panel that allows operators to select different beverage options with minimal effort. This design consideration aids in speeding up service times and reducing errors, ensuring customers receive their orders accurately and promptly.

Another important characteristic of the Cornelius series is its customizable options. Businesses can tailor their dispensers with various configurations to meet specific beverage types and combinations, allowing for a personalized approach to beverage service. This flexibility can be particularly beneficial for establishments looking to stand out in a competitive market.

Durability is also a significant factor in the construction of the CH1500-CH7500 series. Made from high-quality materials, these dispensers are built to withstand the rigors of daily use in busy commercial environments. This reliability reduces downtime and maintenance costs, allowing businesses to maximize productivity.

In terms of energy efficiency, the series stands out with its eco-friendly features that help to minimize energy consumption without compromising performance. This not only supports sustainability efforts but also contributes to cost savings in operational expenses.

Overall, the Cornelius CH1500-CH7500 series is an excellent choice for businesses prioritizing efficiency, quality, and user experience in their beverage dispensing needs. With its combination of advanced technology, customizable features, and durability, it is poised to meet the demands of a wide range of commercial settings.