Whirlpool W10032070 Burner Input Requirements, Gas Supply Pressure Testing

Page 7

Flexible metal appliance connector:

If local codes permit, a new CSA design-certified, 4-5 ft

(122-152.4 cm) long, ¹⁄₂" (1.3 cm) or ³⁄₄" (1.9 cm) I.D., flexible metal appliance connector may be used for connecting range to the gas supply line.

Burner Input Requirements

Input ratings shown on the model/serial rating plate are for elevations up to 2,000 ft (609.6 m).

For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4% for each 1,000 ft (304.8 m) above sea level.

A ¹⁄₂" (1.3 cm) male pipe thread is needed for connection to the female pipe threads of the inlet to the appliance gas pressure regulator.

Do not kink or damage the flexible metal tubing when moving the range.

Rigid pipe connection:

The rigid pipe connection requires a combination of pipe fittings to obtain an in-line connection to the range. The rigid pipe must be level with the range connection. All strains must be removed from the supply and fuel lines so range will be level and in line.

Gas Supply Pressure Testing

Line pressure testing above ¹⁄₂ psi gauge (14" WCP)

The range and its individual manual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures greater than ¹⁄₂ psi (3.5 kPa).

Line pressure testing at ¹⁄₂ psi gauge (14" WCP) or lower

The range must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of that system at test pressures equal to or less than

¹⁄₂ psi (3.5 kPa).

Must include a shutoff valve:

The supply line must be equipped with a manual shutoff valve. This valve should be located in the same room but external to the range. It should be in a location that allows ease of opening and closing. Do not block access to shutoff valve. The valve is for turning on or shutting off gas to the range.

A

C

B

A. Shutoff valve in “open” position

B. Gas supply line

C. To range

Gas Pressure Regulator

The gas pressure regulator supplied with this range must be used. The inlet pressure to the regulator should be as follows for proper operation:

Natural Gas:

Minimum pressure: 5" WCP

Maximum pressure: 14" WCP

LP Gas:

Minimum pressure: 11" WCP

Maximum pressure: 14" WCP

Contact local gas supplier if you are not sure about the inlet pressure.

†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.

7

Image 7
Contents W10032070 Installation Instructions 30 76.2 CM Freestanding GAS RangeTable of Contents Range SafetyWhat to do if YOU Smell GAS Tools and Parts Installation RequirementsLocation Requirements Width For tall Backguard Models Countertop Product Dimensions Installation ClearancesGas Supply Line Electrical RequirementsGas Supply Requirements Type of GasBurner Input Requirements Gas Supply Pressure TestingGas Pressure Regulator Install Anti-Tip Bracket Installation InstructionsUnpack Range Typical rigid pipe connection Verify Anti-Tip Bracket LocationLevel Range Make Gas ConnectionCheck Operation of Cooktop Burners If the low flame needs adjustingCheck Operation Electronic Ignition SystemIf range does not operate, check the following Complete InstallationIf the flame needs adjusting Check Operation of Oven/Broil BurnerTo Convert Surface Burners GAS ConversionsLP Gas Conversion To Convert Gas Pressure RegulatorTo Convert Oven Burner Complete ConversionNatural Gas Conversion Install natural gas orifice spuds Whirlpool Corporation All rights reserved 07/2006