Murphy Keystart 9700 Control Outputs, Fault protection and Alarm System, Charge Fail Warning

Page 2

Control Outputs

The following are provided:-

Rear Facia Settings & Electrical Connection

Switched +ve RUN relay and START outputs, used for controlling the engine fuel and starter motor circuits.

A –ve DC (open collector transistor), common ALARM output, used for remotely signalling a fault condition.

Fault protection and Alarm System

After the operator has started the engine and the fault override timer has expired, the Keystart monitors for engine and plant faults through remotely connected switch sensors.

Dedicated inputs are provided for Low Oil Pressure and High Engine Temperature switch sensors. 1 or 2 additional inputs may be used for general purpose ‘plant fail’ contacts. Switches at the rear allow the inputs to be configured for use with remote contacts which either open or close during fault, with wiring polarity to either +ve or –ve DC.

The Keystart may optionally be fitted with an engine overspeed trip, available in alternator sensing (generator AC, 50/60Hz) or magnetic pickup sensing variants.

+ve –ve

VR1

VR2

VR3

Tachometer/calibration output:–

0 – 1mA into 75 meter

VR1: Nominal speed calibration:–

With engine running at normal speed, adjust VR1 until calibration meter reads 0.75mA.

VR2: Overspeed trip level:–

100 - 130% of nominal calibrated speed, clockwise to increase

VR3: Fault override timer:–

<10 to > 30 seconds clockwise to increase

Switch Settings (N.B.

 

= up

 

= down)

S1

Fault Inputs:–

S2

S3

S4

Not

 

 

Supply:–

Used

closed –ve

 

 

12 V DC

 

closed +ve

 

 

24 V DC

 

open –ve

 

 

 

 

open +ve

 

 

 

If any of the above faults occur, Keystart will:-

turn off its RUN output (stopping the engine)

indicate the fault on the appropriate front facia LED

activate its Alarm output (to remotely signal that a fault has occurred).

The automatic fault shutdowns operate on a first-up and latching basis - subsequent faults are not indicated and the displayed fault can only be cleared by switching the Keystart to STOP.

Charge Fail Warning

A charge failure warning LED is provided for use with an

1– ve DC power supply

2Charge fail input

3 +ve DC power supply

4Aux. input ('A' option)

5Mag. pickup input (KEY9701 only)

6Alarm output: –ve DC, < 250mA

7- No connection -

8- No connection -

9- No connection -

10- No connection -

11- No connection -

12- No connection -

13- No connection -

14- No connection -

15Aux./preheat output: +ve DC ('A' option only)

16

Input 1: Low Oil Pressure

17

Input 2: High Engine Temp.

18

Input 3: Plant Fail (9700 only)

19

Input 4: Plant Fail

20- No connection -

22Fuel output: + ve DC, 16A max.

23Start output: + ve DC, 15A max.

24- No connection -

25- No connection -

26- No connection -

27- No connection -

28- No connection -

29L Generator AC: 90 - 300 VAC

30N (KEY9702 only)

engine driven charge alternator. The charge alternator’s WL terminal is connected to the Keystart, which will in turn monitor the WL voltage and provide the alternator with excitation current at engine start up.

Note:–

Pin 5 is not used on models 9700 and 9702.

Pin 18 is not used on overspeed models 9701 and 9702. Pins 29 and 30 are not used on models 9700 and 9701.

Installation

The Keystart uses a DIN standard 96 x 96 mm casing, designed for mounting in a control panel cut-out (92 x 92mm DIN). Electrical connection is through a pair of ‘two-part’ type terminal blocks at the rear of the unit, with 2 separate ¼” blade terminals on overspeed versions for the tachometer or calibration meter.

Also at the rear is are 4 switches for the setting of the supply voltage and alarm input configurations, and up to 3 potentiometers: one to set the fault ‘override’ time (all units), and 2 more to set the speed calibration and overspeed trip level, where fitted.

When ordering, please specify:–

a) Base unit type:-

Keystart 9700: no overspeed

Keystart 9701: magnetic pickup sensing overspeed

Keystart 9702: AC alternator (50/60Hz) overspeed

b) Options:-

‘A’: auxiliary control/preheat option

N.B: stock units are supplied with switch settings for 24VDC power supply, inputs closing to –ve DC during fault.

Typical Connection Circuit

+ VE DC

 

Emergency

 

 

 

 

 

 

Stop

 

 

 

RAL

alarm

 

Generator AC

 

 

 

 

 

 

 

(KEY9702 only)

29

3

6

 

 

 

L

(’A’ option only)

 

 

N

30

 

 

15

 

 

 

Aux

 

 

+

 

Start

15

Remote

 

 

Start

 

WL

Stop

 

2

 

 

 

 

 

 

Run

 

Run

 

 

 

 

 

Magnetic pickup

 

 

 

4

 

 

 

(KEY9701 only)

 

 

 

 

Start

 

 

5

 

RUN

22

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

LOP

17

 

 

23

RFL

fuel

 

 

 

 

 

 

 

 

 

 

 

 

19

 

 

 

 

 

 

 

 

 

 

 

 

 

HET

+

1

 

RST

starter

 

 

 

 

 

 

 

 

Fail

 

 

 

 

RPH

preheat

 

 

 

 

 

(’A’ option

 

Plant

 

 

 

 

 

RPM/Calib.

 

 

only)

 

 

 

 

 

Meter

 

 

 

 

– VE DC

Since 1939

Frank W. Murphy Manufacturer

PO Box 470248, Tulsa, Oklahoma 74147, USA Tel: + 1 918 627 3550 Fax: + 1 918 664 6146 email: sales@fwmurphy.com

web: http://www.fwmurphy.com

Frank W. Murphy Ltd.

Frank W. Murphy Ltd. en France

Frank W. Murphy Southern Division

Murphek Pty. Ltd.

Incorporating Modex Automation

Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89

PO Box 1819, Rosenberg, Texas 77471, USA

1620 Hume Highway, Campbellfield, Vic. 3061 Australia

Church Road, Laverstock, Salisbury U.K.

Direct usine Tel: + 44 1722 410697

Tel: + 1 281 342 0297 Fax: + 1 281 341 6006

Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558

Tel: + 44 1722 410055 Fax + 44 1722 410088

email: sales@fwmurphy.co.uk

email: sales@fwmurphy.com

email: murphy@macquarrie.com.au

Pour service en Français, tél: + 44 1722 410697

Frank W. Murphy Pte, Ltd.

Murphy Switch of California

 

 

Murphy de Mexico S.A. de C.V.

 

email: sales@fwmurphy.co.uk

No. 2 Tuas South Street 2, Sprintecs Building

PO Box 900788, Palmdale, California 93590, USA

Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje

 

web: http://www.fwmurphy.co.uk

 

02-01/02, Singapore 637895

Tel: + 1 805 272 4700 Fax: + 1 805 947 7570

San Luis Potosí, S.L.P. México 78384

 

 

Tel: + 65 863 1398 Fax: + 65 863 0208

email: sales@murphyswitch.com

Tel: + 52 48 206264 Fax: + 52 48 206336

 

 

email: fwmsales@fwmurphy.com.sg

web: http://www.murphyswitch.com

email: murmexsl@sanluis.podernet.com.mx

 

Image 2
Contents Inputs Power supplyAdjustable settings OutputsWhen ordering, please specify Fault protection and Alarm SystemInstallation Control Outputs

Keystart 9700 specifications

The Murphy Keystart 9700 is a robust and versatile control system that has been designed to meet the needs of various applications, primarily in the industrial sector. With its advanced capabilities, the Keystart 9700 is particularly well-suited for engine monitoring and control, making it an essential tool for many operators and engineers.

One of the main features of the Murphy Keystart 9700 is its intuitive user interface. The system is equipped with a large display that offers clear visibility of key operational parameters. This includes engine temperature, oil pressure, fuel levels, and more, allowing users to monitor the performance of their engines in real-time. The interface is user-friendly, ensuring that operators can easily navigate through the menu and adjust settings as needed.

Another significant characteristic of the Keystart 9700 is its advanced diagnostic capabilities. The system is designed to provide comprehensive fault detection and troubleshooting information, which helps in identifying issues quickly, minimizing downtime, and increasing overall efficiency. This feature is particularly beneficial in critical applications where engine reliability is paramount.

The Murphy Keystart 9700 also incorporates cutting-edge communication technologies. It supports various communication protocols, enabling seamless integration with other systems and devices. This flexibility makes it a perfect fit for diverse applications, from marine and agricultural to power generation and construction sites.

In terms of environmental resilience, the Keystart 9700 is built to withstand harsh conditions. Its rugged construction and IP67-rated enclosure ensure reliable operation even in extreme temperatures and challenging environments. This durability is essential for applications where equipment is exposed to moisture, dust, or vibration.

Safety is another critical feature of the Murphy Keystart 9700. The system includes built-in safety alarms and shutdown features, which help to protect both the engine and surrounding equipment from potential damage. By providing early warnings, it allows operators to take necessary precautions before more significant issues arise.

Overall, the Murphy Keystart 9700 stands out as a leading solution in engine management technology. Its combination of user-friendly design, advanced diagnostics, robust communication capabilities, and durability makes it an excellent choice for those seeking a reliable and efficient control system for their engines in demanding environments.