![](/images/new-backgrounds/1007505/750513x1.webp)
Unit removes condensate through a 1
19.17″ | 3.92″ | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C00007
Fig. 7ÐArea Not to Be Drilled More Than 3/4-in.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground- level installations. Install a
If the installation requires draining the condensate water away from the unit, install a
Failure to follow these precautions could result in damage to the unit being installed:
1.Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connec- tions must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2.Use only copper conductor for connections between
3.Be sure that
4.Insulate
5.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On
HIGH-VOLTAGE CONNECTIONS
INDOOR
THERMOSTAT
RETURN
AIR
1 in. lower than the unit
Step 7ÐInstall Electrical Connections
TOP COVER
Power Wiring
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND
ENTRY
COMPOSITE
BASEPAN
CONDENSATE
DRAIN
CONNECTION
*Separate disconnect per NEC (National Electrical Code) required for electric heater when single- point conection is not used.
FROM
POWER
SOURCE
DISCONNECT PER NEC* (UNIT AND ELECTRIC HEATER)
C00008
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI (American National Standards Institute)/NFPA (latest edition) (in Canada, Canadian Elec- trical Code CSA C22.1) and local electrical codes. Failure to adhere to this warning could result in serious injury or death.
C00008
Table 2ÐMinimum Airflow for Safe Electric Heater
Operation (CFM)
SIZE
024 | 030 | 036 | 042 | 048 | 060 |
600 | 750 | 900 | 1050 | 1200 | 1500 |
Fig. 8ÐTypical installation
1” (25mm) MIN.
TRAP
OUTLET
2” (50mm) MIN.
C99013
Fig. 9ÐCondensate Trap (Using Tubing)
The unit must have a separate electrical service with a field- supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 3 for electrical data.
7