REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
| INCHES [mm] | |
TOP OF UNIT | 0 |
|
DUCT SIDE OF UNIT | 0 |
|
SIDE OPPOSITE DUCTS | 0 |
|
BOTTOM OF UNIT | 0 |
|
NEC. REQUIRED CLEARANCES. | INCHES [mm] | |
| ||
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 | [1066.8] |
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 | [914.0] | |
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
|
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 | [1066.8] |
REQUIRED CLEARANCE FOR OPERATION AND SERVICING |
| |
| INCHES [mm] | |
CONDENSER. COIL ACCESS SIDE | 30.00 [762.0] | |
POWER ENTRY SIDE | 30.00 | [762.0] |
(EXCEPT FOR NEC REQUIREMENTS) |
|
|
UNIT TOP | 48.00 | [1219.2] |
SIDE OPPOSITE DUCTS | 30.00 | [762.0] |
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
|
|
|
|
|
|
|
|
|
|
|
|
|
| C00158 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT | ELECTRICAL CHARACTERISTICS | UNIT WEIGHT | CENTER OF GRAVITY IN. (MM) | |||||||||||
lb | kg | X |
|
|
|
|
|
| Y | Z | ||||
|
|
|
|
|
|
|
| |||||||
50ZH060 | 368 | 167 | 14.0 (356) | 20.0 (508) |
| 16.0 (406) |
Fig. 4ÐUnit Base Dimensions, 50ZH060
5