REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

 

INCHES [mm]

TOP OF UNIT

0

 

DUCT SIDE OF UNIT

0

 

SIDE OPPOSITE DUCTS

0

 

BOTTOM OF UNIT

0

 

NEC. REQUIRED CLEARANCES.

INCHES [mm]

 

BETWEEN UNITS, POWER ENTRY SIDE

42.00

[1066.8]

UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00

[914.0]

UNIT AND BLOCK OR CONCRETE WALLS AND OTHER

 

 

GROUNDED SURFACES, POWER ENTRY SIDE

42.00

[1066.8]

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

 

 

INCHES [mm]

CONDENSER. COIL ACCESS SIDE

30.00 [762.0]

POWER ENTRY SIDE

30.00

[762.0]

(EXCEPT FOR NEC REQUIREMENTS)

 

 

UNIT TOP

48.00

[1219.2]

SIDE OPPOSITE DUCTS

30.00

[762.0]

LEGEND

NEC – National Electrical Code

NOTES:

1. Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.

2. Dimensions are in inches. Dimensions in [ ] are in millimeters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C00158

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

CENTER OF GRAVITY IN. (MM)

lb

kg

X

 

 

 

 

 

 

Y

Z

 

 

 

 

 

 

 

 

50ZH060

208/230-1-60, 208/230-3-60, 460-3-60

368

167

14.0 (356)

20.0 (508)

 

16.0 (406)

Fig. 4ÐUnit Base Dimensions, 50ZH060

5

Page 5
Image 5
Carrier 50ZH024-060 instruction manual ÐUnit Base Dimensions, 50ZH060