REQUIRED CLEARANCE TO COMBUSTIBLE MATL. |
|
| INCHES [mm] |
TOP OF UNIT | 0 |
DUCT SIDE OF UNIT | 0 |
SIDE OPPOSITE DUCTS | 0 |
BOTTOM OF UNIT | 0 |
NEC. REQUIRED CLEARANCES. |
|
| INCHES [mm] |
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 [1066.8] |
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] | |
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 [1066.8] |
REQUIRED CLEARANCE FOR OPERATION AND SERVICING | |
| INCHES [mm] |
CONDENSER. COIL ACCESS SIDE | 30.00 [762.0] |
POWER ENTRY SIDE | 30.00 [762.0] |
(EXCEPT FOR NEC REQUIREMENTS) |
|
UNIT TOP | 48.00 [1219.2] |
SIDE OPPOSITE DUCTS | 30.00 [762.0] |
LEGEND |
|
NEC – National Electrical Code |
|
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| C00156 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT | ELECTRICAL CHARACTERISTICS | UNIT WEIGHT | CENTER OF GRAVITY IN. (MM) | |||||||||||||
lb | kg | X |
|
|
|
|
|
| Y |
| Z | |||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50ZH024 | 232 | 106 | 14.0 (356) | 19.0 (483) |
| 12.0 (305) | ||||||||||
50ZH030 | 254 | 116 | 14.0 (356) | 19.0 (483) |
| 12.0 (305) | ||||||||||
208/230±3±60 |
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 2ÐUnit Base Dimensions, 50ZH024-030
3