
Table 5ÐWet Coil Pressure Drop
UNIT SIZE | AIRFLOW | PRESSURE DROP | |
50ZH | (CFM) | (IN. WG) | |
| 600 | 0.02 | |
|
|
| |
024 | 700 | 0.05 | |
|
| ||
800 | 0.06 | ||
| |||
|
|
| |
| 900 | 0.07 | |
|
|
| |
| 900 | 0.06 | |
030 |
|
| |
1000 | 0.06 | ||
| 1200 | 0.08 | |
|
|
| |
| 1000 | 0.07 | |
|
|
| |
036 | 1200 | 0.09 | |
1400 | 0.11 | ||
| |||
| 1600 | 0.12 | |
| 1000 | 0.04 | |
042 | 1200 | 0.06 | |
1400 | 0.08 | ||
| |||
| 1600 | 0.09 | |
| 1400 | 0.07 | |
048 | 1600 | 0.08 | |
| 1800 | 0.09 | |
| 1700 | 0.07 | |
060 | 1800 | 0.08 | |
2100 | 0.09 | ||
| |||
| 2300 | 0.10 |
Table 6ÐFilter Pressure Drop (in. wg)
UNIT | FILTER |
|
|
|
|
|
|
|
|
|
|
| CFM |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
SIZE | SIZE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
50ZH | (IN.) | 500 | 600 |
| 700 | 800 |
| 900 | 1000 | 1100 | 1200 | 1300 | 1400 | |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 24 x 24 | 0.06 | 0.07 |
| 0.08 | 0.08 |
| 0.09 | 0.09 | 0.09 | 0.10 | 0.11 |
| 0.12 | ||||||||||||||||||
048, 060 |
| 24 x 30 | - |
| - |
|
| - | - |
| - |
| - |
| - |
| - | 0.08 |
| 0.09 | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
UNIT |
| FILTER |
|
|
|
|
|
|
|
|
|
|
|
| CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
SIZE |
| SIZE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
50ZH |
| (IN.) |
| 1500 | 1600 |
| 1700 |
| 1800 |
| 1900 | 2000 | 2100 | 2200 |
| 2300 |
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 24 x 24 |
| 0.14 | 0.15 |
| - |
| - |
|
| - |
| - |
| - |
| - |
|
| - |
|
|
|
| ||||||||
048,060 |
| 24 x 30 |
| 0.10 | 0.11 |
| 0.12 |
| 0.13 |
| 0.14 | 0.15 | 0.16 | 0.17 | 0.18 |
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
Table 7ÐAccessory Electric Heat Pressure Drop |
|
|
|
|
|
| ||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
| (in. wg) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
HEATER KW |
|
|
|
|
|
|
|
|
|
|
|
|
| CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
600 | 800 |
| 1000 | 1200 |
| 1400 | 1600 |
| 1800 |
| 2000 |
| 2200 |
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
0.06 | 0.08 |
| 0.10 | 0.13 |
| 0.15 | 0.18 |
| 0.20 |
| 0.23 |
| 0.25 |
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
Step 6ÐElectrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag.
Remove the top panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate from tubing and sheet metal edges.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in
18
3.125 in.
C00021
Fig. 21ÐOutdoor-Fan Adjustment (024±048 Size)
0.708in.
C02017
Fig. 22ÐOutdoor-Fan Adjustment (060 Size)
operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumenta- tion. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the Sequence of Operation section, as an aid in determining proper control operation.
Step 7ÐRefrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrig- erant leak.
If oil is detected or if low cooling performance is suspected,
If no refrigerant leaks are found and low cooling performance is suspected, refer to Refrigerant Charge. (See Table of Contents for page number.)
Step 8ÐIndoor Airflow
The cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and
Step 9ÐMetering Devices
Refrigerant metering devices are fixed orifices and are located in the inlet header to the indoor and outdoor coils.
Check valves are also located in the liquid lines near the strainers. The check valves are the smaller of the two components.
Step 10ÐLubrication
COMPRESSORÐThe compressor is charged with the correct amount of oil at the factory.
FAN MOTOR BEARINGSÐFan motor bearings are perma- nently lubricated. No further lubrication of outdoor or indoor fan motors is required.
Step 11ÐLiquid Line Strainer
The liquid line strainer (to protect metering device) is made of wire mesh and is located in the liquid line on the inlet side of the metering device.