Table 5ÐWet Coil Pressure Drop

UNIT SIZE

AIRFLOW

PRESSURE DROP

50ZH

(CFM)

(IN. WG)

 

600

0.02

 

 

 

024

700

0.05

 

 

800

0.06

 

 

 

 

 

900

0.07

 

 

 

 

900

0.06

030

 

 

1000

0.06

 

1200

0.08

 

 

 

 

1000

0.07

 

 

 

036

1200

0.09

1400

0.11

 

 

1600

0.12

 

1000

0.04

042

1200

0.06

1400

0.08

 

 

1600

0.09

 

1400

0.07

048

1600

0.08

 

1800

0.09

 

1700

0.07

060

1800

0.08

2100

0.09

 

 

2300

0.10

Table 6ÐFilter Pressure Drop (in. wg)

UNIT

FILTER

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50ZH

(IN.)

500

600

 

700

800

 

900

1000

1100

1200

1300

1400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024-042

 

24 x 24

0.06

0.07

 

0.08

0.08

 

0.09

0.09

0.09

0.10

0.11

 

0.12

048, 060

 

24 x 30

-

 

-

 

 

-

-

 

-

 

-

 

-

 

-

0.08

 

0.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

FILTER

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

 

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50ZH

 

(IN.)

 

1500

1600

 

1700

 

1800

 

1900

2000

2100

2200

 

2300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024-042

 

24 x 24

 

0.14

0.15

 

-

 

-

 

 

-

 

-

 

-

 

-

 

 

-

 

 

 

 

048,060

 

24 x 30

 

0.10

0.11

 

0.12

 

0.13

 

0.14

0.15

0.16

0.17

0.18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 7ÐAccessory Electric Heat Pressure Drop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATER KW

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

800

 

1000

1200

 

1400

1600

 

1800

 

2000

 

2200

 

5-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.06

0.08

 

0.10

0.13

 

0.15

0.18

 

0.20

 

0.23

 

0.25

 

 

 

 

 

 

 

 

 

 

Step 6ÐElectrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag.

Remove the top panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.

Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate from tubing and sheet metal edges.

After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in

18

3.125 in.

C00021

Fig. 21ÐOutdoor-Fan Adjustment (024±048 Size)

0.708in.

C02017

Fig. 22ÐOutdoor-Fan Adjustment (060 Size)

operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumenta- tion. Refer to the unit wiring label when making these checkouts.

NOTE: Refer to the Sequence of Operation section, as an aid in determining proper control operation.

Step 7ÐRefrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrig- erant leak.

If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leak-detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section. (See Table of Contents for page number.)

If no refrigerant leaks are found and low cooling performance is suspected, refer to Refrigerant Charge. (See Table of Contents for page number.)

Step 8ÐIndoor Airflow

The cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to Indoor Airflow and Airflow Adjustments section to check the system airflow.

Step 9ÐMetering Devices

Refrigerant metering devices are fixed orifices and are located in the inlet header to the indoor and outdoor coils.

Check valves are also located in the liquid lines near the strainers. The check valves are the smaller of the two components.

Step 10ÐLubrication

COMPRESSORÐThe compressor is charged with the correct amount of oil at the factory.

FAN MOTOR BEARINGSÐFan motor bearings are perma- nently lubricated. No further lubrication of outdoor or indoor fan motors is required.

Step 11ÐLiquid Line Strainer

The liquid line strainer (to protect metering device) is made of wire mesh and is located in the liquid line on the inlet side of the metering device.

Page 18
Image 18
Carrier 50ZH024-060 ÐWet Coil Pressure Drop, ÐFilter Pressure Drop in. wg, ÐAccessory Electric Heat Pressure Drop In. wg