START-UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No .............................................................................................................................................................
Serial No ..............................................................................................................................................................
Date ......................................................................................................................................................................
Technician ...........................................................................................................................................................
Customer Information(Name/Address) ...........................................................................................................................................................
II.PRE-START-UP
____ Verify that all packing materials have been removed from unit
____ Verify that condensate connection is installed per installation instructions
____ Check all electrical connections and terminals for tightness
____ Check wire proximity to refrigerant tubes and sheet metal edges
____ Check that indoor (indoor) air filter is clean and in place
____ Verify that unit installation is level
____ Check fan wheel propeller for location in housing and setscrew tightness
III. START-UP
Supply Voltage:
Compressor Amps: L1(C) __________ L2(S) __________ L3(R) __________
Indoor Fan Amps: __________ Outdoor Fan Amps: __________
TEMPERATURE-Cooling Mode
Outdoor Air Temperature: __________ DB ____________WB
Cooling Supply Air: __________DB___________WB
PRESSURES-Cooling Mode
Refrigerant Suction __________ psig
Suction Line Temp* ___________
Refrigerant Discharge __________ psig
Discharge Temp²__________
TEMPERATURE-Heating Mode
Outdoor Air Temperature: __________ DB ____________WB
Cooling Supply Air: __________DB___________WB
PRESSURES-Heating Mode
Refrigerant Suction __________ psig
Suction Line Temp* ___________
Refrigerant Discharge __________ psig
Discharge Temp²__________
____ Verify Refrigerant charge using charging tables
____ Verify that
*Measured at suction inlet to compressor ²Measured at liquid line leaving outdoor coil
23