Operation (continued)

Normal Operation

During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online Mode, Economy Mode, Frequency Conversion Mode, Battery Mode, Bypass Mode or Parallel Mode (12kVA model only).

Online Mode: The UPS provides AC power while utility power is available and switches to On Battery Mode instantly (zero transfer time) if AC power is interrupted.

Economy Mode: The UPS provides AC power at high efficiency while utility power is within +/- 10% rated AC input voltage and switches to On Battery Mode (8ms transfer time) if AC power is interrupted.

Frequency Conversion Mode: Used to convert your UPS’s input frequency to a different output frequency (i.e. Input 60 Hz to Output 50

Hz. Note: Output will be turned off in Frequency Conversion Mode if the unit is put into Bypass).

Battery Mode: The UPS provides AC power from battery backup so long as battery power lasts. It switches back to Online or Economy Mode if utility power is available and shuts down if it runs out of battery power.

Bypass Mode: The UPS provides AC power while utility power is available. The UPS shuts down if AC power is interrupted.

Parallel Mode (SU12KRT4UHW model only): The UPS can provide redundancy up to 6kVA or power up to 12kVA. Refer to the manual provided with the Parallel PDU Kit for more information.

The second line of the LCD Display shows basic power conditions. In each operating mode you can push the SCROLL buttons to browse through these basic power conditions in the sequences shown below:

Display Information Online Mode:

ONLINE MODE

00.00KW / 000%

STANDALONE

00.00KVA / 000%

 

INPUT VOLTAGE 000V / 00.0Hz

 

BYPASS VOLTAGE

000V / 00.0Hz

 

OUTPUT VOLTAGE

000V / 00.0Hz

 

BATTERY CAPACITY

000V / 000%

 

REMAINING TIME

0000 MINUTES

 

ON-LINE 5/6KVA

V00 CV01

Display Information Economy Mode:

ECONOMY MODE 00.00KW / 000%

STANDALONE

00.00KVA / 000%

 

INPUT VOLTAGE 000V / 00.0Hz

 

BYPASS VOLTAGE

000V / 00.0Hz

 

OUTPUT VOLTAGE

000V / 00.0Hz

 

BATTERY CAPACITY

000V / 000%

 

REMAINING TIME

0000 MINUTES

 

ON-LINE 5/6KVA

V00 CV01

Display Information

Frequency

Conversion Mode:

FREQ CONV MODE 00.00KW / 000%

STANDALONE

00.00KVA / 000%

 

INPUT VOLTAGE 000V / 00.0Hz

 

BYPASS VOLTAGE

000V / 00.0Hz

 

OUTPUT VOLTAGE

000V / 00.0Hz

 

BATTERY CAPACITY

000V / 000%

 

REMAINING TIME

0000 MINUTES

 

ON-LINE 5/6KVA

V00 CV01

Display Information Battery Mode:

BATTERY MODE 00.00KW / 000%

STANDALONE

00.00KVA / 000%

 

INPUT VOLTAGE 000V / 00.0Hz

 

BYPASS VOLTAGE

000V / 00.0Hz

 

OUTPUT VOLTAGE

000V / 00.0Hz

 

BATTERY CAPACITY

000V / 000%

 

REMAINING TIME

0000 MINUTES

 

ON-LINE 5/6KVA

V00 CV01

Display Information Bypass Mode:

BYPASS MODE

00.00KW / 000%

STANDALONE

00.00KVA / 000%

 

INPUT VOLTAGE 000V / 00.0Hz

 

BYPASS VOLTAGE

000V / 00.0Hz

 

OUTPUT VOLTAGE

000V / 00.0Hz

 

BATTERY CAPACITY

000V / 000%

 

REMAINING TIME

0000 MINUTES

 

ON-LINE 5/6KVA

V00 CV01

17

201207113 933070.indb 17

9/17/2012 1:20:08 PM

Page 17
Image 17
Tripp Lite 5KVA-6KVA owner manual Normal Operation, Display Information Economy Mode