Operation (continued)
Output Settings
ECO Mode: Used to set the UPS’s ability to work in the energy saving Economy Mode. When input voltage is in a + or - range of 10% of the overall voltage rating, the UPS will transfer into an Economy Mode to improve the efficiency of the UPS. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT SETTING screen. From here, press ON for the OUTPUT VOLTAGE screen, and DOWNi through the FREQ CONVERTER screen until you reach the ECO MODE screen. From here, press ON and now you can scroll DOWNi or UPh between DISABLE and ENABLE. Press ON to save your selection. The DEFAULT setting is DISABLE.
OUTPUT SETTING |
|
| | |
ENT | DOWN UP |
|
| |
|
|
| ||
|
|
|
|
|
| | To ENTER | ||
| | |||
|
|
|
|
OUTPUT VOLTAGE
ENT DOWN UP
| |
|
FREQ. CONVERTER
ENT DOWN UP
| |
|
ECO MODE
ENT DOWN UP
| |
|
|
| *DISABLE* |
| |
ENT | DOWN | UP | ||
| ||||
|
|
|
| |
|
| | | |
|
|
| ||
|
|
|
| |
|
| ENABLE |
| |
| ENT | DOWN | UP | |
|
|
|
|
Industrial: Used to set the UPS’s voltage protection. If enabled, and receiving AC power with input voltage and frequency within a normal range the UPS will work in an
DISABLE.
OUTPUT SETTING |
|
| | |
ENT | DOWN UP |
|
| |
|
|
| ||
|
|
|
|
|
| | To ENTER | ||
| | |||
|
|
|
|
OUTPUT VOLTAGE
ENT DOWN UP
| |
|
FREQ. CONVERTER
ENT DOWN UP
ECO MODE
ENT DOWN UP
| |
|
INDUSTRIAL
ENT DOWN UP
| |
|
REDUNDANCY
ENT DOWN UP
| |
|
|
| *ENABLE* |
| |
ENT | DOWN | UP | ||
| ||||
|
|
|
| |
|
| | | |
|
|
| ||
|
|
|
| |
|
| DISABLE |
| |
| ENT | DOWN | UP | |
|
|
|
| |
|
|
|
| |
|
| *ENABLE* |
| |
ENT | DOWN | UP | ||
| ||||
|
|
|
| |
|
| | | |
|
|
| ||
|
|
|
| |
|
| DISABLE |
| |
| ENT | DOWN | UP | |
|
|
|
|