Operation (continued)

UPS Fault Shutdown Messages

CONDITION

LCD DISPLAY MESSAGES

 

 

+BUS >450V

+ DC BUS HIGH SHUTDOWN

 

 

Load <100%: +BUS < 320V; Load >100%: +BUS

+ DC BUS LOW SHUTDOWN

<290V

 

 

 

-BUS >450V

- DC BUS HIGH SHUTDOWN

 

 

Load <100%: -BUS <320V; Load >100%: -BUS <290V

- DC BUS LOW SHUTDOWN

 

 

BUS Voltage Over 500

BUS OVP FAIL SHUTDOWN

 

 

Output Short

OUTPUT SHORT SHUTDOWN

 

 

UPS Over Temperature

OVER TEMPERATURE SHUTDOWN

 

 

Ouput SCR Open Failure

OUTPUT SCR FAIL SHUTDOWN

 

 

Output Overload

OVERLOAD SHUTDOWN

 

 

Bypass SCR Short

BYPASS SCR FAIL SHUTDOWN

 

 

Input SCR Rectifier Failure

RECTIFIER FAIL SHUTDOWN

 

 

Inverter Output Voltage Failure

INVERTER SHUTDOWN

 

 

Input Fuse Open

I / P FUSE BROKEN SHUTDOWN

 

 

Output Fuse Open

O / P FUSE BROKEN SHUTDOWN

 

 

Parallel ID Lost

PARALLEL FAULT SHUTDOWN

 

 

On Battery Alarm

When in the On Battery Mode, the UPS power module will beep to inform you that it is using battery power to support connected equipment. If its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are below half capacity, it will beep twice a second. If its connected batteries are nearly depleted, the UPS power module will beep continuously.

To silence the On Battery Alarm, press the “ON/MUTE” button.

Overload Messages

When the UPS detects an output overload, its LCD will switch to the following display:

OVERLOAD!

LOAD = XXX% X.XXKW

The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to Bypass Mode to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:

Bypass Messages

 

Overload Condition

Countdown Duration

 

 

 

 

106% - 125%

1 minute

 

 

 

 

126% - 150%

30 seconds

 

 

 

 

>150%

Immediate

 

 

 

 

While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in Bypass Mode.

If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

 

BYPASS VOLTAGE

 

 

LCD DISPLAY

 

 

 

CONDITIONS

 

 

MESSAGES

 

 

 

>15% Higher

 

 

 

 

 

 

 

 

BYPS OUT OF VOLT

 

 

 

Than Nominal

 

 

XXXV / XX.X HZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

>20% Lower

 

 

 

 

 

 

 

 

BYPS OUT OF VOLT

 

 

 

Than Nominal

 

 

 

 

 

 

 

XXXV / XX.X HZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

201207113 933070.indb 26

9/17/2012 1:20:08 PM

Page 26
Image 26
Tripp Lite 5KVA-6KVA owner manual UPS Fault Shutdown Messages, On Battery Alarm, Overload Messages, Bypass Messages