Operation (continued)

Output Settings

Note: Any Output Setting changes require a UPS power cycle.

Output Voltage: Used to set the UPS’ output voltage rating. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT SETTING screen. Press ON to reach an OUTPUT VOLTAGE screen and ON again. You can now scroll DOWNi or UPh between 5 voltage values: 200/208/220/230/240V. Press ON to save your desired voltage. DEFAULT is set to 208V.

OUTPUT SETTING

 

 

ENT

DOWN UP

 

 

 

 

 

 

 

 

 

 

 

To ENTER

 

 

 

 

 

OUTPUT VOLTAGE

ENT DOWN UP

*230V*

ENT DOWN

220V

ENT DOWN

208V

ENT DOWN

200V

ENT DOWN

240V

ENT DOWN

UP

UP

UP

UP

UP

Frequency Converter: Used to set the Frequency Converter Mode. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT SETTING screen. Press ENTER for the OUTPUT VOLTAGE screen and DOWNi to access the FREQ CONVERTER screen. Here, press ON. Now you can scroll DOWNi or UPh between DISABLE, 50 and 60 Hz. Press ON to save your selection. When on DISABLE, the UPS will automatically detect input frequency and select 50 or 60 Hz accordingly. The DEFAULT selection is DISABLE.