Internal Battery Replacement

Under normal conditions, the original batteries in your UPS will last many years. See Safety section before replacing batteries. The batteries are designed for hot-swap replacement (i.e. leaving the UPS ON), but some qualified service personnel may wish to completely turn the UPS OFF and disconnect equipment before proceeding. It is suggested that you remove the batteries before the installation process.

1Remove the screws A which secure the front bezel.

2Separate the front bezel B from the front panel.

3Remove the battery connector snap covers. Save these covers for reuse.

4Disconnect the battery connectors C and remove the screws D that secure the battery retention bracket in place.

5Remove the battery retention bracket E and remove/ recycle the middle battery pack F .

6Remove/recycle the side battery packs G .

7Replace the battery packs F and G .

8Re-attach the battery retention bracket E .

9Replace the screws D to secure the battery retention bracket in place.

10Connect the battery connectors C . Attach connectors black-to-black, red-to-red, white-to-white and green- to-green.

11Reinstall the battery connector snap covers.

12Replace the front bezel B .

13Replace the screws A to secure the front bezel in place.

 

A

1

13

 

B

2

12

 

D

 

 

C

D

 

 

4

 

9-10

 

F

 

E

5

7-8

 

G

 

G

6

7

28

201207113 933070.indb 28

9/17/2012 1:20:10 PM

Page 28
Image 28
Tripp Lite 5KVA-6KVA owner manual Internal Battery Replacement