Lenox XC14, Elite Series installation instructions New or Replacement Line Set

Models: Elite Series XC14

1 30
Download 30 pages 31.71 Kb
Page 10
Image 10
New or Replacement Line Set

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 12.

Manual background IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 7 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.

Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil on page 15).

Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance.

To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XC14) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

Manual background IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol Ester oil.

Table 2. Refrigerant Line Set

Model Number

Field Connections

 

Recommended Line Set

 

 

 

 

 

 

Liquid Line

Suction Line

Liquid Line

Suction Line

L15 Line Set

 

 

 

 

 

 

XC14−018−230

 

 

 

 

 

 

 

 

 

 

 

XC14−024−230

3/8" (10 mm)

3/4" (19 mm)

3/8" (10 mm)

3/4" (19 mm)

L15−41

 

 

 

 

 

 

XC14−030−230

 

 

 

 

 

 

 

 

 

 

 

XC14−036−230

 

 

 

 

 

 

 

 

 

 

 

XC14−041−230

 

 

 

 

 

 

 

 

 

 

 

XC14−042−230

3/8" (10 mm)

7/8" (22 mm)

3/8" (10 mm)

7/8" (22 mm)

L15−65

 

 

 

 

 

 

XC14−047−230

 

 

 

 

 

 

 

 

 

 

 

XC14−048−230

 

 

 

 

 

 

 

 

 

 

 

XC14−060−230

3/8" (10 mm)

1−1/8" (29 mm)

3/8" (10 mm)

1−1/8" (29 mm)

Field Fabricated

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

Page 10

506636−01

Page 10
Image 10
Lenox XC14, Elite Series installation instructions New or Replacement Line Set