Operation (continued)

Start Settings

The UPS can start up through the battery without AC power. The DEFAULT is ENABLE. When the UPS switches to battery it can AUTO RESTART to work in an On-Line Mode when AC power is restored. DEFAULT is ENABLE.

From the SETUP MENU screen, scroll DOWNi to the START SETTING screen. From here, press the ON button for the BATTERY START screen. From this screen, pressing ON moves you to a ENABLE screen. Pressing ON will ENABLE, while scrolling DOWNi takes you to a DISABLE screen. From here, press ON to DISABLE this function.

From the BATTERY START screen, pressing DOWNi will take you to an AUTO RESTART screen. Pressing ON takes you to an ENABLE screen; press ON to ENABLE. Pressing DOWNi takes you to a DISABLE screen. Press ON to DISABLE this function.

START SETTING

 

 

ENT

DOWN UP

 

 

 

 

 

 

 

 

 

 

 

To ENTER

 

 

 

 

 

BATTERY START

ENT DOWN UP

AUTO RESTART

ENT DOWN UP

 

*ENABLE*

 

ENT

DOWN

UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISABLE

 

 

ENT

DOWN

UP

 

 

 

 

 

 

 

 

 

*ENABLE*

 

ENT

DOWN

UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISABLE

 

 

ENT

DOWN

UP

 

 

 

 

Charger Settings

From the SETUP MENU screen, scroll DOWNi until you reach the CHARGER SETTING screen. From here, press ON to get to the CHARGER CURRENT screen. Press ON again. From here, you can scroll DOWNi or UPh to select current values between 0.7 and 4.0 A. Press ON to save your desired value. The DEFAULT selection is 0.7A.

CHARGER SETTING

 

ENT

DOWN UP

 

 

 

 

 

 

 

To ENTER

CHARGER CURRENT

ENT DOWN UP

 

CURRENT = 0.7A

ENT DOWN UP

 

CURRENT = 1.5A

ENT DOWN UP

 

CURRENT = 3.0A

ENT DOWN UP

 

CURRENT = 4.0A*

ENT DOWN UP

Use the following table as a guide for charger settings based on the number of battery packs you are using.

UPS Charge Current Setting for 5/6kVA Models

Internal Battery Pack + External Battery Packs

1

2

3-6

7 or more

 

 

 

 

 

Charge Current Setting

0.7A

1.5A

3.0A

4.0A

 

 

 

 

 

UPS Charge Current Settings for the 12kVA Model

Use the same charger current settings as the 5/6kVA models for each power module of the SU12KRT4UHW. The number of connected external battery packs must be equal on each power module of the SU12KRT4UHW.

20

201207113 933070.indb 20

9/17/2012 1:20:08 PM

Page 20
Image 20
Tripp Lite 5KVA-6KVA owner manual Start Settings, Charger Settings