Operation (continued)
Start Settings
The UPS can start up through the battery without AC power. The DEFAULT is ENABLE. When the UPS switches to battery it can AUTO RESTART to work in an
From the SETUP MENU screen, scroll DOWNi to the START SETTING screen. From here, press the ON button for the BATTERY START screen. From this screen, pressing ON moves you to a ENABLE screen. Pressing ON will ENABLE, while scrolling DOWNi takes you to a DISABLE screen. From here, press ON to DISABLE this function.
From the BATTERY START screen, pressing DOWNi will take you to an AUTO RESTART screen. Pressing ON takes you to an ENABLE screen; press ON to ENABLE. Pressing DOWNi takes you to a DISABLE screen. Press ON to DISABLE this function.
START SETTING |
|
| | |
ENT | DOWN UP |
|
| |
|
|
| ||
|
|
|
|
|
| | To ENTER | ||
| | |||
|
|
|
|
BATTERY START
ENT DOWN UP
AUTO RESTART
ENT DOWN UP
|
| *ENABLE* |
| |
ENT | DOWN | UP | ||
| ||||
|
|
|
| |
|
| | | |
|
|
| ||
|
|
|
| |
|
| DISABLE |
| |
| ENT | DOWN | UP | |
|
|
|
| |
|
|
|
| |
|
| *ENABLE* |
| |
ENT | DOWN | UP | ||
| ||||
|
|
|
| |
|
| | | |
|
|
| ||
|
|
|
| |
|
| DISABLE |
| |
| ENT | DOWN | UP | |
|
|
|
|
Charger Settings
From the SETUP MENU screen, scroll DOWNi until you reach the CHARGER SETTING screen. From here, press ON to get to the CHARGER CURRENT screen. Press ON again. From here, you can scroll DOWNi or UPh to select current values between 0.7 and 4.0 A. Press ON to save your desired value. The DEFAULT selection is 0.7A.
CHARGER SETTING |
| | |
ENT | DOWN UP |
| |
|
| ||
|
|
|
|
To ENTER
CHARGER CURRENT
ENT DOWN UP
| |
|
CURRENT = 0.7A
ENT DOWN UP
| |
|
CURRENT = 1.5A
ENT DOWN UP
| |
|
CURRENT = 3.0A
ENT DOWN UP
| |
|
CURRENT = 4.0A*
ENT DOWN UP
Use the following table as a guide for charger settings based on the number of battery packs you are using.
UPS Charge Current Setting for 5/6kVA Models
Internal Battery Pack + External Battery Packs | 1 | 2 | 7 or more | |
|
|
|
|
|
Charge Current Setting | 0.7A | 1.5A | 3.0A | 4.0A |
|
|
|
|
|
UPS Charge Current Settings for the 12kVA Model
Use the same charger current settings as the 5/6kVA models for each power module of the SU12KRT4UHW. The number of connected external battery packs must be equal on each power module of the SU12KRT4UHW.