maintenance
3.On the GFCI module (Figure 36), verify that the green POWER LED is ON.
P | F |
O | A |
W | U |
E | L |
R | T |
GREEN |
|
POWER |
|
LED |
|
MANUAL RESET |
Figure 36. GFCI Module (Green LED ON)
4.Also verify that the AC voltmeter is registering a voltage reading as indicated by Figure 41.
5.Next, press the TEST button on the GFCI module and verify that the green POWER LED turns OFF and the red FAULT LED turns ON.
PRESS
P F
O A
W U
E L
R T
RED
FAULT
LED
MANUAL RESET
Figure 37. GFCI Module (Red/Fault LED ON)
6.Also verify that the main circuit breaker switch trips to the OFF position.
ON
OFF
Figure 38. Circuit Breaker OFF (GFCI Test)
7.Verify that the AC voltmeter (Figure 39) on the generator reads zero volts.
240
V 120
Figure 39. AC Voltmeter (Zero Volts)
8.To restore power, press the RESET button (Figure 40) on the GFCI module and verify that the red FAULT LED turns OFF and the green POWER LED should turn ON
P | F |
O | A |
W | U |
E | L |
R | T |
GREEN |
|
POWER |
|
LED | PRESS |
MANUAL RESET |
Figure 40. GFCI Module (Green LED ON Reset)
9.Verify that the AC voltmeter is registering a voltage reading as indicated by Figure 41.
240
V 120
Figure 41. AC Voltmeter (120/240V)
NOTICE
It is recommended that the GFCI unit be tested when the generator is initially taken out of the box. Then, the generator should be tested daily at startup.
CAUTION
The GFCI module is designed to interrupt power when a ground fault exists to prevent injuries and shock hazards. DO NOT operate the generator if this test fails. Consult a qualified electrician for repair or replacement of the GFCI module.
page 30 — GA6HB/GA6HEB 60 hz gENERATOR• operation and parts manual — rev. #0 (03/13/14)