Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. SeeTable 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA45ssk/ku3 60 hz Generator • operation and parts manual — rev. #0 (12/15/11) — page 23

Image 23
Contents Model dca45SSKU Model dca45SSKU3 Proposition 65 warning Administrator Reporting Safety DefectsDCA45SSKU/SSKU3 60 Hz Generator Table of ContentsChoose from three easy options SaFeTY messages Safety InformationGeneraTor saFeTY General saFeTYIf operating in speed ranges above the maximum allowable Engine saFeTYRestricted. If the air fl ow is From fuel vapors or if fuel is spilled on a hot engine Fuel saFeTYToWing saFeTY „ never use fuel as a cleaning agentPower Cord/Cable safety EleCTriCal saFeTYGrounding safety EnvironmenTal saFeTY BaTTerY saFeTYDCA-45SSKU/KU3 SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationGenerator Grounding Outdoor InstallationIndoor Installation MountingGeneral Information Item no Major ComponentsEngine Control Panel Will remain OFF. When the ignitionGenerator Control Panel Generator control PanelOutput Terminal Panel is provided with the following Output Terminal FamiliarizationTerminal legs O and Ground are considered bonded grounds VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsLoad Application Single Phase LoadThree Phase Load Generator Amperage Voltage Selector SwitchVoltage Selector Switch Locking Button Generator Output VoltagesAC Ammeter Gauge Reading How to Read the ac ammeter and ac voltage gaugesGenerator OUTPUTS/gauge reading AC Voltmeter Gauge Reading3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages Uvwo Terminal Output Voltages3Ø-240/139 Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesFuel Check Inspection/SETUPCircuit Breakers Lubrication OilRemove fuel cap and fill tank as shown in Figure Refueling ProcedureOperation in Freezing Weather Cleaning the RadiatorAir Cleaner Fan Belt Tension Coolant Antifreeze/Summer Coolant/ WaterAlternator BatteryBattery Cable Installation WiringEngine’s exhaust contains harmful emissions Before StartingStarting Place the engine speed control switch in the RUN position up Automatic Shut-down System Normal Shutdown ProcedureEmergency Shutdown Procedure Air Cleaner with Dust Indicator MaintenanceGeneral Inspection Air Cleaner Fuel Tank Inspection Cleaning Inside the Fuel TankFuel Addition Removing Water from the Fuel TankReplacing Oil Filter Radiator CleaningAir Removal Check Oil LevelBattery Charger and Jacket Water Heater option JacketWater Heater and Internal Battery OptionalCoupler Type of hitch used on the trailer for towing Trailer MaintenanceTrailer Maintenance Actuator Brake AdjustmentBrakes Hydraulic Surge BrakesSuspension Tires/Wheels/Lug NutsTire Wear/Inflation Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramGenerator Troubleshooting Troubleshooting GeneratorPage Explanation of Code in Remarks Column To 3 units Suggested Spare PartsGenerator Assy B3120100804 B31100013020601820083 06018Control box Assy Y0330000190 M1213002012Y0330000555 Y0330000255Control box Assy M1224100104 0027105010M9220100004 Y0080200007Engine and Radiator Assy 1C02032433 M19232001541G54197011 1663143562Engine and Radiator Assy 0605515170 5160137670 SWITCH, thermometer T106365660Y0199101000 0193601300Output Terminal Assy 0039310000 M1230700103M9220100204 M9220100104Battery Assy 0602220920 0602220199M9310500014 M9103000304Muffler Assy 0030410000 B3331102203B3334001403 1925812231Fuel Tank Assy 0605516090 M13630026020605505070 0605501072Enclosure Assy M1493110203 M1413004202M1413400004 M1423003102Enclosure Assy M1453006213 001910805536A 0042308000 36B 031108160Rubber Seals Assy REMArks Nameplate and Decals Assy M92000010 M9522000504M92200050 M9520000104Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help

DCA45SSKU, DCA45SSKU3 specifications

The Multiquip DCA45SSKU3 and DCA45SSKU are advanced diesel generators designed for a variety of applications, making them an ideal choice for contractors, event planners, and anyone needing reliable power solutions. With a robust design and cutting-edge technologies, these generators stand out in their class for performance and durability.

One of the main features of the DCA45SSKU3 and DCA45SSKU is their impressive power output. Offering a prime power capacity of 45 kVA, these generators are equipped with a powerful Yanmar engine that provides reliable and efficient performance. The engine operates at low speed, which not only enhances fuel efficiency but also reduces noise levels, making these generators suitable for use in noise-sensitive environments.

The generators come equipped with a fully integrated control panel, featuring an intuitive digital display that allows users to monitor operating parameters such as voltage, frequency, and runtime. This user-friendly interface simplifies operation, ensuring that even those unfamiliar with generator technology can easily manage the generator's functions.

In terms of fuel capacity, the DCA45SSKU and DCA45SSKU3 are designed for extended run times. The large fuel tank allows for continuous operation, meaning users can depend on these generators for prolonged periods without frequent refueling, enhancing their suitability for long-duration projects and events.

Another remarkable characteristic is the trailer-mounted design, providing excellent portability. This feature enables users to easily transport the generator to different job sites or locations, making it perfect for construction sites, outdoor events, or emergency backup power situations. The rugged construction also ensures that the generator can withstand the wear and tear of being moved frequently.

Safety features are integral to the design of the DCA45SSKU3 and DCA45SSKU. The generators are equipped with automatic shutdown mechanisms in case of low oil pressure or overheating, protecting the unit from damage and ensuring safe operation. Additionally, the sound-attenuated enclosure minimizes noise pollution, a crucial consideration for operations in populated areas.

In summary, the Multiquip DCA45SSKU3 and DCA45SSKU generators are powerful, portable, and feature-rich solutions for anyone in need of reliable diesel power. With their advanced technology, fuel efficiency, and safety features, these generators are an excellent choice for a wide range of applications, ensuring that users can access the power they need, when they need it.