DCA10SPX4/DCA10SPXU4 — SETUP

Battery

This unit is of negative ground DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level are not properly maintained. Add only distilled water when replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery.

The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F).If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Before charging the battery with an external electric source, be sure to disconnect the battery cables.

Battery Cable Installation

ALWAYS be sure the battery cables (Figure 19) are properly connected to the battery terminals as shown below.The Red Cable is connected to the positive terminal of the battery, and the Black Cable is connected to the negative terminal of the battery.

CAUTION - BATTERY SERVICING SAFETY

ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.

When connecting battery do the following:

1.NEVER connect the battery cables to the battery terminals when the ignition switch is in the ON position

2.Place a small amount of battery terminal treatment compound around both battery terminals.This will ensure a good connection and will help prevent corrosion around the battery terminals.

If the battery cable is connected

NOTE incorrectly, electrical damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.

CAUTION - BATTERY SERVICING SAFETY

Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.

Alternator

The polarity of the alternator is negative grounding type. When an inverted circuit connection takes place, the circuit will be in short circuit instantaneously resulting the alternator failure.

DO NOT put water directly on the alternator. Entry of water into the alternator can cause corrision and damage the alternator.

Wiring

Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.

Piping and Hose Connection

Inspect all piping, oil hose, and fuel hose connections for wear and tightness.Tighten all hose clamps and check hoses for leaks.

If any hose (fuel or oil) lines are defective replace them immediately.

Figure 19. Battery Connections

PAGE 28 — DCA10SPX4/DCA10SPXU4 — OPERATION AND PARTS MANUAL — REV. #0 (08/05/09)

Image 28
Contents Model DCA10SPX4 Model DCA10SPXU4 Diesel engine exhaust and some DCA10SPX4/DCA10SPXU4 Proposition 65 WarningDCA10SPX4/DCA10SPXU4 Note Component Drawings DCA10SPX4/DCA10SPXU4 Parts Ordering Procedures Ordering parts has never been easierDCA10SPX4/DCA10SPXU4 Specifications DCA10SPX4/DCA10SPXU4 Dimensions TOP, Side and Front Dimension ft. mmDCA10SPX4/DCA10SPXU4 Safety Message Alert Symbols Hazard SymbolsDCA10SPX4/DCA10SPXU4 Safety Message Alert Symbols DCA10SPX4/DCA10SPXU4 Rules for Safe Operation General SafetyOff Deadly carbon Monoxide gas DCA10SPX4/DCA10SPXU4 Rules for Safe Operation MalfunctionBattery Safety Death Towing and Transporting Safety Guidelines section in this manualPage DCA10SPX4/DCA10SPXU4 Installation DCA10SPX4/DCA10SPXU4 Installation Outdoor InstallationIndoor Installation MountingDCA10SPX4/DCA10SPXU4 General Information DCA10SPX4/DCA10SPXU4 Major Components Major ComponentsDCA10SPX4/DCA10SPXU4 Generator Control Panel DCA-10SPX4 /U4- Output Terminal Panel Familiarization Output Terminal FamiliarizationVAC Gfci Receptacle DCA-10SPX4 /U4 Output Terminal Panel FamiliarizationL5-30R Twist Lock 100 VAC Receptacle Option Connecting Loads Single Phase Load DCA10SPX4/DCA10SPXU4 Load APPLICATION/MAXIMUM AmpsGenerator Amperage Describes the generator’s current output capabilityCircuit Breakers Lubrication OilFuel Check Refilling the Fuel SystemEnce Figures 16 Refueling ProcedureRefueling Air Cleaner Fan Belt Tension Mm when depressed with the thumb as shown belowOperation Freezing Weather Vol % Freezing PointBattery Battery Cable InstallationWiring AlternatorDCA10SPX4/DCA10SPXU4 Generator START-UP Procedure Before StartingEngines exhaust contains harmful emissions Direct exhaust away from nearby personnelSet the Speed Control Switch to the RUN position Ammeter No LoadNormal Shutdown Procedure Emergency Shutdown ProcedureGeneral Inspection Air Cleaner Air Cleaner with Dust Indicator If EquippedService Daily Fuel AdditionDCA10SPX4/DCA10SPXU4 Maintenance DCA10SPX4/DCA10SPXU4 Trailer Maintenance Brake AdjustmentBrakes Check the wheel and drum for free rotationTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Lug Nut Torque Requirements Wheel Lug Nuts Tightening SequenceDCA10SPX4/DCA10SPXU4 Generator Wiring Diagram Generator Wiring DiagramDCA10SPX4/DCA10SPXU4 Engine Wiring Diagram Engine Wiring DiagramDCA10SPX4/DCA10SPXU4 Troubleshooting Engine Engine TroubleshootingDCA10SPX4/DCA10SPXU4 Troubleshooting Engine DCA10SPX4/DCA10SPXU4 Troubleshooting Generator Generator TroubleshootingDCA10SPX4/U4 Troubleshooting PRE-HEAT Lamp Codes Failure Diagnosis Lamp CodeDCA10SPX4/DCA10SPXU4 Note Sample Parts List DCA10SPX4/U4 Explanation of Code in Remarks ColumnDCA10SPX4/DCA10SPXU4 Suggested Spare Parts DCA10SPX4/DCA10SPXU4 Generator Assy 8321000102 06018213740601822630 8001070003DCA10SPX4/DCA10SPXU4 Control Panel Assy B0224005103 M02240000030601800455 Frequency METER, 45~65 Hz 0601805745 0601800281DCA10SPX4/DCA10SPXU4 Control Panel Assy 0601806640 0601830771B0214002903 M0214000003DCA10SPX4/DCA10SPXU4 Output Receptacle Assy 0601815109 06018125980601811035 0601811033DCA10SPX4/DCA10SPXU4 Engine and Radiator Assy B0924200174 16382970111641432433 B0304200403DCA10SPX4/DCA10SPXU4 Engine and Radiator Assy 0802081104 87020820040016906015 0199900450DCA10SPX4 Battery Assy 0165308026 B13452001140805002904 0037808000DCA10SPXU4 Battery Assy Y0602220193 M0484600004Y0602220920 M0344000003DCA10SPX4/DCA10SPXU4 Muffler Assy B0331100703 B03340005031526312371 0207008000DCA10SPX4/DCA10SPXU4 Fuel Tank Assy B0364000703 08101058000810105900 B0364300403DCA10SPX4/DCA10SPXU4 Enclosure Assy B0414002202 M0414000102D3414800104 M0414800004DCA10SPX4/DCA10SPXU4 Enclosure Assy B0464001002 M046400010225A B0494500104 25A M0494500604DCA10SPX4/DCA10SPXU4 Rubber Seals Assy 0229200650 02294006950221700900 0221700640DCA10SPX4/DCA10SPXU4 Nameplate Assy 0840614104 2635B9504501204 0800650804Effective October 1, 2002 Terms and Conditions of Sale Parts Page Heres HOW to GET Help

DCA10SPXU4, DCA10SPX4 specifications

The Multiquip DCA10SPX4 and DCA10SPXU4 are highly regarded portable diesel generators that cater to a wide range of applications, from construction sites to outdoor events. These models are part of Multiquip’s popular line of reliable power solutions, designed to deliver robust performance and versatility.

At the heart of both models lies a powerful and efficient Yanmar diesel engine. The DCA10SPX4 offers a rated output of 10 kVA, while the DCA10SPXU4 provides the same output, making both models suitable for powering tools, lights, and other equipment. The Yanmar engine is known for its efficiency, offering longer run times between refueling and lower operational costs, making these generators economical choices for users.

One of the standout features of the DCA10SPX4 and DCA10SPXU4 is their durability and rugged design. Constructed with a powder-coated steel frame, these generators can withstand harsh environments and heavy use. The enclosed design reduces noise levels, making them ideal for urban jobsites or residential areas where noise restrictions may apply. Additionally, the weather-resistant design enhances their usability in unfavorable weather conditions.

Both models come equipped with advanced monitoring features and controls that make operation straightforward. An easy-to-read digital display provides real-time information regarding output voltage, frequency, and engine performance. This allows operators to monitor their generator’s performance swiftly and efficiently, ensuring smooth operation throughout usage.

In terms of safety, the DCA10SPX4 and DCA10SPXU4 incorporate various protective mechanisms. They include an automatic shutdown feature that activates in the event of low oil pressure or overheating, protecting the engine from damage. Furthermore, the generators are equipped with overload protection to prevent equipment damage from excessive loads.

Another notable characteristic is the generator's portability. Both models feature a compact design, lightweight structure, and integrated lifting hooks, making them easy to transport and position on job sites. Their user-friendly design allows for quick setup and disassembly, ensuring minimal downtime for users.

Overall, the Multiquip DCA10SPX4 and DCA10SPXU4 generators combine efficiency, durability, and user convenience, making them an outstanding choice for professionals seeking dependable power solutions in various applications. Whether powering construction tools or supporting outdoor events, these generators deliver reliable performance tailored to meet diverse energy needs.