Multiquip DCA-25SSIU2 operation manual Towing &Transporting Safety, Emergencies

Page 13

DCA-25SSIU2 (50 HZ)— RULES FOR SAFE OPERATION

Towing &Transporting Safety

To reduce the possibility of an accident while transporting the generator on public roads, always make sure the trailer that supports the generator and the towing vehicle are in good operating condition and both units are mechanically sound.

The following list of safety precautions should be followed when towing your generator:

CAUTION - FOLLOWTOWING REGULATIONS

Check with your local county or state safety towing regulations, in addition to meeting Department of Transportation (DOT) SafetyTowing Regulations, before towing your generator.

ALWAYS shutdown engine before transporting.

Tighten both fuel tank caps securely.

If generator is mounted on a trailer, make sure trailer complies with all local and state safety transportation laws. Follow the listed Towing & Transporting Safety guidelines for basic towing techniques.

Make sure the hitch and coupling of the towing vehicle are rated equal to, or greater than the trailer "gross vehicle weight rating.”

ALWAYS inspect the hitch and coupling for wear. NEVER tow a trailer with defective hitches, couplings, chains etc.

Check the tire air pressure on both towing vehicle and trailer. Trailer tires should be inflated to 50 psi cold. Also check the tire tread wear on both vehicles.

ALWAYS make sure the trailer is equipped with a "Safety Chain".

ALWAYS attach trailer’s safety chains to towing vehicle properly.

ALWAYS make sure the vehicle and trailer directional, backup, brake, and trailer lights are connected and working properly.

DOT Requirements include the following:

z Connect and test electric brake operation.

z Secure portable power cables in cable tray with tie wraps.

The maximum speed for highway towing is 55 MPH unless posted otherwise. Recommended off-road towing is not to exceed 15 MPH or less depending on type of terrain.

Place chock blocks underneath wheel to prevent rolling, while parked.

Use the trailer’s swivel jack to adjust the trailer height to a level position while parked.

Avoid sudden stops and starts. This can cause skidding, or jack-knifing. Smooth, gradual starts and stops will improve towing.

Avoid sharp turns.

Trailer should be adjusted to a level position at all times when towing.

Raise and lock trailer wheel stand in up position when transporting.

The maximum speed for highway towing is 55 MPH unless posted otherwise. Recommended off-road towing is not to exceed 15 MPH or less depending on type of terrain.

Place support blocks underneath the trailer’s bumper to prevent tipping, while parked.

Avoid sharp turns to prevent rolling.

DO NOT transport generator with fuel in tank.

Emergencies

ALWAYS know the location of the nearest fire extinguisher.

ALWAYS know the location of the nearest and first aid kit.

ALWAYS know the location of the nearest phone or keep a phone on the job site, in case of emergencies.

ALWAYS have easy access to the phone numbers of the nearest Ambulance, Doctor and Fire Department. This information will be invaluable in the case of an emergency.

DCA-25SSIU2 (50 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (03/11/05) — PAGE 13

Image 13
Contents Model DCA-25SSIU2 Parts List NO. M1870300804Page Heres HOW to GET Help Table of Contents When ordering parts Please supply the following information Parts Ordering ProceduresDCA-25SSIU2 50 HZ- Specifications DCA-25SSIU2 50 HZ- Dimensions TOP, Side and Front Hazard Symbols DCA-25SSIU2 50 HZ Safety Message Alert SymbolsDCA-25SSIU2 50 HZ Safety Message Alert Symbols DCA-25SSIU2 50 HZ- Rules for Safe Operation General SafetyGenerator Grounding Electrical SafetyBattery Safety Maintenance SafetyEmergencies Towing &Transporting SafetyGenerator Decals DCA-25SSIU2 50 HZ- Generator DecalsDCA-25SSIU2 50 HZ- Generator Decals DCA-25SSIU2 50 HZ- Installation Outdoor Installation DCA-25SSIU2 50 HZ- InstallationIndoor Installation MountingDCA-25SSIU2 50 HZ- General Information Generator Major Components DCA-25SSIU2 50 HZ- Major ComponentsDCA-25SSIU2 50 HZ- Generator Control Panel DCA-25SSIU2 50 HZ- Engine Operating Panel Output Terminal Familiarization DCA-25SSIU2 50 HZ- Output Terminal Panel FamiliarizationDCA-25SSIU2 50 HZ- Output Terminal Panel Familiarization Blower Fan Connecting LoadsThree Phase Load Single Phase LoadDCA-25SSIU2 50 HZ- Load Application DCA-25SSIU2 50 HZ- Generator Outputs Voltage Selector SwitchGenerator OutputVoltages Generator AmperageDCA-25SSIU2 50 HZ- Gauge Reading How to Read the OutputTerminal GaugesReading Amperage DCA-25SSIU2 50 HZ- Output Terminal Panel Connections Three-Phase PositionUvwo Terminal Output Voltages 3Ø-200/115 Output Terminal Lug Voltages1Ø 200V/100V Output Terminal Lug Voltages 3Ø 440/254 Output Terminal Lug VoltagesCircuit Breakers DCA-25SSIU2 50 HZ- PRE-SETUPLubrication Oil Fuel CheckRefueling Procedure DCA-25SSIU2 50 HZ- PRE-SETUPRefueling Air Cleaner Fan Belt Tension Cleaning the RadiatorOperation FreezingWeather Must be less than 50%Battery Cable Installation BatteryWhen connecting battery do the following WiringMain, Aux. and Gfci Circuit Breakers OFF Before StartingFrequency Meter Hz Main, AUX. and Gfci Circuit Breakers on DCA-25SSIU2 50 HZ- Generator START-UP ProcedureDCA-25SSIU2 50 HZ- Maintenance Air Removal Cleaning the Fuel StrainerCheck Oil Level Replacing Oil FilterTrailer Maintenance DCA-25SSIU2 50 HZ-TRAILER MaintenanceBrakes Brake AdjustmentHydraulic Surge Brakes Tire Wear/Inflation Tires/Wheels/Lug NutsSuspension Lug Nut Torque Requirements DCA-25SSIU2 50 HZ-TRAILER MaintenanceTrailer/Towing Vehicle Wiring Diagram DCA-25SSIU2 50 HZ-TRAILERWIRING DiagramGenerator Wiring Diagram DCA-25SSIU2 50 HZ- Generatorwiring DiagramEngine Wiring Diagram DCA-25SSIU2 50 HZ- Enginewiring DiagramGenerator Troubleshooting DCA-25SSIU2 50 HZ-TROUBLESHOOTING GeneratorDCA-25SSIU2 50 HZ-TROUBLESHOOTING Engine Engine Troubleshooting DCA-25SSIU2 50 HZ-TROUBLESHOOTING EnginePage Items Found In the Items Number Column Explanation of Code in Remarks ColumnDescription DCA-25SSIU2 50 HZ- Suggested Spare PartsDCA-25SSIU2 50 HZ- Generator Assy Part Name QTY Remarks DCA-25SSIU2 50 HZ- Control BOX Assy Part Name Control BOX ASSY.CONT CHANGE-OVER SWITCH, AMMETER, SL-2 AS DCA-25SSIU2 50 HZ- Engine Operating Panel Assy Engine Operating Panel Assy DCA-25SSIU2 50 HZ- Engine & Radiator Assy Part Name QTY. Remarks DCA-25SSIU2 50 HZ- Engine & Radiator ASSY. CONNECTOR, 10WFTX-S Output Terminal Assy DCA-25SSIU2 50 HZ- Outputterminal AssyPart Name QTY DCA-25SSIU2 50 HZ- Battery Assy Battery DCA-25SSIU2 50 HZ- Muffler Assy Muffler DCA-25SSIU2 50 HZ- Fuel Tank Assy Hose Band Includes Item W DCA-25SSIU2 50 HZ- Fueltank AssyEnclosure Assy DCA-25SSIU2 50 HZ- Enclosure AssyBase Enclosure ASSY.CONT DCA-25SSIU2 50 HZ- Enclosure ASSY.Enclosure #1 ASSY.CONT DCA-25SSIU2 50 HZ- Rubber Seals Assy Seal Rubber DCA-25SSIU2 50 HZ- Nameplate and Decals Stripe Whisperwatt Freightpolicy Terms and Conditions of Sale PartsPage Please have the Model and Serial Number ON-HANDWHEN Calling
Related manuals
Manual 82 pages 29.66 Kb

DCA-25SSIU2 specifications

The Multiquip DCA-25SSIU2 is a versatile and powerful diesel generator, designed to meet the needs of various industries while providing a reliable source of power. This model is particularly popular in construction, event management, and emergency backup supply applications. With its robust build and advanced features, the DCA-25SSIU2 stands out as a top choice for professionals seeking durability and efficiency.

One of the significant features of the DCA-25SSIU2 is its impressive power output. The generator delivers a continuous output of 25 kVA, making it suitable for powering heavy machinery, tools, and equipment. This model is equipped with a turbocharged, liquid-cooled YANMAR engine, known for its performance and fuel efficiency. The engine operates quietly, ensuring minimal noise pollution in sensitive environments.

Built to withstand harsh conditions, the DCA-25SSIU2 is housed in a sturdy steel frame enclosure. The design not only protects the generator from the elements but also reduces noise levels. The enclosure features a weather-resistant finish, making it ideal for both indoor and outdoor applications. Additionally, the unit's compact size allows for easy transportation and storage, which is an essential consideration for contractors on the go.

The DCA-25SSIU2 incorporates advanced technology to enhance performance and user experience. It features a digital control panel, offering intuitive monitoring of generator status, fuel consumption, and operational hours. Automatic voltage regulation ensures a stable output, protecting connected devices from voltage fluctuations.

Fuel efficiency is another highlight of this generator. The DCA-25SSIU2 operates on diesel, which is not only readily available but also provides a longer run time compared to gasoline generators. The large fuel tank capacity allows for extended periods of operation without frequent refueling.

Safety is a critical aspect of the DCA-25SSIU2. The generator is equipped with safety features such as low oil shut-off, overload protection, and a heavy-duty frame for stability. These elements ensure that the generator operates safely and reliably, even in demanding situations.

In conclusion, the Multiquip DCA-25SSIU2 diesel generator combines power, efficiency, and ruggedness. Its blend of advanced features, fuel efficiency, and safety make it an excellent choice for a wide range of applications. Whether for construction projects, outdoor events, or emergency power needs, the DCA-25SSIU2 stands as a testament to Multiquip's commitment to quality and innovation in the generator market.