DCA-25SSIU2 (50 HZ)— LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

If wattage is not given on the equipment's name plate,

NOTE approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type Of Load

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

Single-phase induction motors

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

1.0

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

1.0

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 100

At 200

 

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

 

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

 

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

 

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

2400

 

250

ft.

 

150

ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

 

150

ft.

 

100

ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

 

125

ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

If 3Ø load (kVA) is not given on the equipment nameplate,

NOTEapproximate 3Ø load output maybedeterminedbymultiplying voltage by amperage by 1.732.

Motors and motor-driven

NOTEequipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA-25SSIU2 (50 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (03/11/05) — PAGE 25

Image 25
Contents Model DCA-25SSIU2 Parts List NO. M1870300804Page Heres HOW to GET Help Table of Contents When ordering parts Please supply the following information Parts Ordering ProceduresDCA-25SSIU2 50 HZ- Specifications DCA-25SSIU2 50 HZ- Dimensions TOP, Side and Front Hazard Symbols DCA-25SSIU2 50 HZ Safety Message Alert SymbolsDCA-25SSIU2 50 HZ Safety Message Alert Symbols DCA-25SSIU2 50 HZ- Rules for Safe Operation General SafetyGenerator Grounding Electrical SafetyBattery Safety Maintenance SafetyEmergencies Towing &Transporting SafetyGenerator Decals DCA-25SSIU2 50 HZ- Generator DecalsDCA-25SSIU2 50 HZ- Generator Decals DCA-25SSIU2 50 HZ- Installation Outdoor Installation DCA-25SSIU2 50 HZ- InstallationIndoor Installation MountingDCA-25SSIU2 50 HZ- General Information Generator Major Components DCA-25SSIU2 50 HZ- Major ComponentsDCA-25SSIU2 50 HZ- Generator Control Panel DCA-25SSIU2 50 HZ- Engine Operating Panel Output Terminal Familiarization DCA-25SSIU2 50 HZ- Output Terminal Panel FamiliarizationDCA-25SSIU2 50 HZ- Output Terminal Panel Familiarization Blower Fan Connecting LoadsThree Phase Load Single Phase LoadDCA-25SSIU2 50 HZ- Load Application DCA-25SSIU2 50 HZ- Generator Outputs Voltage Selector SwitchGenerator OutputVoltages Generator AmperageDCA-25SSIU2 50 HZ- Gauge Reading How to Read the OutputTerminal GaugesReading Amperage DCA-25SSIU2 50 HZ- Output Terminal Panel Connections Three-Phase PositionUvwo Terminal Output Voltages 3Ø-200/115 Output Terminal Lug Voltages1Ø 200V/100V Output Terminal Lug Voltages 3Ø 440/254 Output Terminal Lug VoltagesCircuit Breakers DCA-25SSIU2 50 HZ- PRE-SETUPLubrication Oil Fuel CheckRefueling Procedure DCA-25SSIU2 50 HZ- PRE-SETUPRefueling Air Cleaner Fan Belt Tension Cleaning the RadiatorOperation FreezingWeather Must be less than 50%Battery Cable Installation BatteryWhen connecting battery do the following WiringMain, Aux. and Gfci Circuit Breakers OFF Before StartingFrequency Meter Hz Main, AUX. and Gfci Circuit Breakers on DCA-25SSIU2 50 HZ- Generator START-UP ProcedureDCA-25SSIU2 50 HZ- Maintenance Air Removal Cleaning the Fuel StrainerCheck Oil Level Replacing Oil FilterTrailer Maintenance DCA-25SSIU2 50 HZ-TRAILER MaintenanceBrakes Brake AdjustmentHydraulic Surge Brakes Tire Wear/Inflation Tires/Wheels/Lug NutsSuspension Lug Nut Torque Requirements DCA-25SSIU2 50 HZ-TRAILER MaintenanceTrailer/Towing Vehicle Wiring Diagram DCA-25SSIU2 50 HZ-TRAILERWIRING DiagramGenerator Wiring Diagram DCA-25SSIU2 50 HZ- Generatorwiring DiagramEngine Wiring Diagram DCA-25SSIU2 50 HZ- Enginewiring DiagramGenerator Troubleshooting DCA-25SSIU2 50 HZ-TROUBLESHOOTING GeneratorDCA-25SSIU2 50 HZ-TROUBLESHOOTING Engine Engine Troubleshooting DCA-25SSIU2 50 HZ-TROUBLESHOOTING EnginePage Items Found In the Items Number Column Explanation of Code in Remarks ColumnDescription DCA-25SSIU2 50 HZ- Suggested Spare PartsDCA-25SSIU2 50 HZ- Generator Assy Part Name QTY Remarks DCA-25SSIU2 50 HZ- Control BOX Assy Part Name Control BOX ASSY.CONT CHANGE-OVER SWITCH, AMMETER, SL-2 AS DCA-25SSIU2 50 HZ- Engine Operating Panel Assy Engine Operating Panel Assy DCA-25SSIU2 50 HZ- Engine & Radiator Assy Part Name QTY. Remarks DCA-25SSIU2 50 HZ- Engine & Radiator ASSY. CONNECTOR, 10WFTX-S Output Terminal Assy DCA-25SSIU2 50 HZ- Outputterminal AssyPart Name QTY DCA-25SSIU2 50 HZ- Battery Assy Battery DCA-25SSIU2 50 HZ- Muffler Assy Muffler DCA-25SSIU2 50 HZ- Fuel Tank Assy Hose Band Includes Item W DCA-25SSIU2 50 HZ- Fueltank AssyEnclosure Assy DCA-25SSIU2 50 HZ- Enclosure AssyBase Enclosure ASSY.CONT DCA-25SSIU2 50 HZ- Enclosure ASSY.Enclosure #1 ASSY.CONT DCA-25SSIU2 50 HZ- Rubber Seals Assy Seal Rubber DCA-25SSIU2 50 HZ- Nameplate and Decals Stripe Whisperwatt Freightpolicy Terms and Conditions of Sale PartsPage Please have the Model and Serial Number ON-HANDWHEN Calling
Related manuals
Manual 82 pages 29.66 Kb

DCA-25SSIU2 specifications

The Multiquip DCA-25SSIU2 is a versatile and powerful diesel generator, designed to meet the needs of various industries while providing a reliable source of power. This model is particularly popular in construction, event management, and emergency backup supply applications. With its robust build and advanced features, the DCA-25SSIU2 stands out as a top choice for professionals seeking durability and efficiency.

One of the significant features of the DCA-25SSIU2 is its impressive power output. The generator delivers a continuous output of 25 kVA, making it suitable for powering heavy machinery, tools, and equipment. This model is equipped with a turbocharged, liquid-cooled YANMAR engine, known for its performance and fuel efficiency. The engine operates quietly, ensuring minimal noise pollution in sensitive environments.

Built to withstand harsh conditions, the DCA-25SSIU2 is housed in a sturdy steel frame enclosure. The design not only protects the generator from the elements but also reduces noise levels. The enclosure features a weather-resistant finish, making it ideal for both indoor and outdoor applications. Additionally, the unit's compact size allows for easy transportation and storage, which is an essential consideration for contractors on the go.

The DCA-25SSIU2 incorporates advanced technology to enhance performance and user experience. It features a digital control panel, offering intuitive monitoring of generator status, fuel consumption, and operational hours. Automatic voltage regulation ensures a stable output, protecting connected devices from voltage fluctuations.

Fuel efficiency is another highlight of this generator. The DCA-25SSIU2 operates on diesel, which is not only readily available but also provides a longer run time compared to gasoline generators. The large fuel tank capacity allows for extended periods of operation without frequent refueling.

Safety is a critical aspect of the DCA-25SSIU2. The generator is equipped with safety features such as low oil shut-off, overload protection, and a heavy-duty frame for stability. These elements ensure that the generator operates safely and reliably, even in demanding situations.

In conclusion, the Multiquip DCA-25SSIU2 diesel generator combines power, efficiency, and ruggedness. Its blend of advanced features, fuel efficiency, and safety make it an excellent choice for a wide range of applications. Whether for construction projects, outdoor events, or emergency power needs, the DCA-25SSIU2 stands as a testament to Multiquip's commitment to quality and innovation in the generator market.