Lochinvar 502 - 2072, 402 - 2072 Check relief valve Inspect/replace hot surface igniter

Page 25

Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual

2 Maintenance (continued)

 

Check relief valve

Inspect/replace hot surface igniter

1.Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read the Water Connections Section of the Installation and Operation Manual before proceeding further.

This unit uses a proven hot surface ignition module and a hot surface igniter. The hot surface ignition module is not repairable. Any modification or repairs will invalidate the warranty.

￿ WARNING Do not attempt to repair a faulty hot

￿WARNING

Safety relief valves should be re-inspected

AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency

not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.

surface igniter or ignition module. Any

modification or repairs may create hazardous conditions that result in property damage, personal injury, fire, explosion and/or toxic gases.

A faulty hot surface igniter or ignition module must be replaced with an identical part. A specification igniter and ignition module for this specific unit is available from your local distributor. Do not use general purpose field replacement ignition modules or igniters.

Inspect/replace hot surface igniters

1.

Turn off main electrical power to the appliance.

2.

Turn off main manual gas shutoff to the appliance.

3.

Remove lower front door to gain access to the hot surface

 

igniter.

4.

Locate the hot surface igniter. Disconnect the two power

 

leads to the hot surface igniter.

5.

Loosen and remove the two screws used to attach the

 

igniter.

￿WARNING

Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the appliance until a new relief valve has been installed.

6.

Remove the igniter from the combustion chamber door.

 

Use care, do not hit or break the silicon carbide igniter. Do

 

not contaminate the igniter by handling with oily or dirty

 

hands.

7.

Check the replacement igniter for cracks or damage before

 

installing.

8.

Ensure that the fiber gasket used to seal the base of the

 

igniter to the combustion chamber door is reinstalled to seal

 

the base of the replacement igniter.

9.

Carefully insert the igniter into the opening of the

 

combustion chamber door and re-attach the two screws

 

removed in Step 5. Over-tightening may break the ceramic

 

mounting flange.

10.

Ensure that the igniter gasket is properly installed and seals

 

the point of contact between the igniter and the combustion

2.After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.

 

chamber door.

11.

Reconnect the power leads to the igniter.

12.

Replace the lower front door.

13.

Turn on main gas supply and main power.

14.

Test fire the appliance to ensure proper operation.

25

Image 25
Contents Copper-fin II/IIE Boiler, Water Heater Pool Heater Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid Service What is in this manual?Maintenance TroubleshootingCopper-fin display ServiceControl inputs Control outputs How the appliance operates General OperationHow the control module operates Sequence of operationOUT 123.8F129 Sequence of operationHTR Postpurge Display panel menu access Display panel parameter access Parameter table Datalogging Functions Settingsdhw ResetoutdoorAnti-cycle Delay Yes Viewable and changeable control parameters Temperature settings boiler onlyFunctions Data loggingDHW settings Outdoor air reset boiler only Anti-cycling Control modes Cascade Building Management System BMSCirculation pumps Service NotificationService technician Maintenance Maintenance and annual startupOwner maintenance See the User’s Information Manual for instructionsMaintenance Inspect/replace hot surface igniters Check relief valve Inspect/replace hot surface igniterCheck control settings Check all wiringInspect and clean burner Perform start-up and checksChecking combustion air pressure Access to the burner will require the following stepsChecking manifold gas pressure Adjusting combustion air pressureValve Fitting Control Knob Review with owner Inspect and clean the heat exchangerOiled bearing circulators Before troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does NotResistance Temperature Checking temperature sensorsTemperature Resistance No Pump NoisyBoiler Pump System Pump DHW PumpFlame Sequence Flow SwitchAnti-cycling No Flame Ign ErrorHSI Current Low Flame CKTNo Flame Auto ResetRunning High LimitInlet Low Manual ResetSensor Open Sensor ShortedTank Open Louver ProvingAPS Open APS ClosedRem Ctrl Flt Temp O/ShootParameters Service BlkProgr Low VoltageNo Error Stored Watch Dog ErrorWrite EEProm Program EEProm
Related manuals
Manual 44 pages 8.33 Kb Manual 44 pages 18.25 Kb Manual 80 pages 43.41 Kb

502 - 2072, 402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.