3 Troubleshooting (continued)
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION |
|
| |||
|
|
| |||||
| The unit was running and lost the flame signal. | • Inspect igniter and associated wiring for damage and | |||||
|
| connection. Reference page 25 of this manual for | |||||
|
| removal and cleaning procedure. Replace if | |||||
|
| necessary. |
|
|
|
|
|
|
| • Check for proper electrical grounding of unit. |
|
| |||
|
| • Check incoming supply gas pressure. Refer to the | |||||
No Flame |
| Gas Connections Section of the Installation and | |||||
| Operation Manual for detailed information concerning | ||||||
Running |
| the gas supply. |
|
|
|
| |
(Will require a manual |
| • Verify that | the | tube from | the gas valve | to | the |
reset once the condition |
| ||||||
| combustion | air | chamber is | connected and | is | not | |
has been corrected. Press |
| ||||||
| damaged. |
|
|
|
|
| |
the RESET button on the |
|
|
|
|
|
| |
|
|
|
|
|
|
| |
SMART SYSTEM display |
| • Verify that the vent/air intake pipes are installed | |||||
to reset.) |
| correctly and there are no obstructions. |
|
| |||
|
| • Refer to the Checking Manifold Gas Pressure and | |||||
|
| Combustion Analysis Procedure on pages 27 and 28 | |||||
|
| of this manual for the proper settings. |
|
| |||
|
| • Inspect the burners. Reference pages 26 and 27 | |||||
|
| of this manual for removal and cleaning procedures. | |||||
|
| Replace if necessary. |
|
|
| ||
|
| • Replace the main control board. |
|
| |||
|
|
| |||||
| The outlet water temperature has exceeded the | • Verify that the system is full of water and that all air | |||||
| setting of the automatic reset high limit. | has been properly purged from the system. |
|
| |||
|
| • Verify that the appliance is piped properly into the | |||||
|
| heating system. Refer to the Water Connections | |||||
|
| Section of the Installation and Operation Manual for | |||||
|
| the proper piping methods for the |
|
| |||
|
| • Check 120 VAC to boiler pump motor on a call for | |||||
|
| heat. If voltage is not present, check wiring back | |||||
|
| to the main control board. Replace the main | |||||
|
| control board if necessary. |
|
|
| ||
Auto Reset |
| • If 120 VAC is present on a call for heat and the | |||||
High Limit |
| pump is not operating, replace the pump. |
|
| |||
|
| • If the system pump is a variable speed pump, | |||||
|
| ensure that the system flow is not less than the | |||||
|
| boiler flow. |
|
|
|
|
|
|
| • Check temperature setting of the main control | |||||
|
| board. |
|
|
|
|
|
|
| • Check resistance of water sensors and compare to | |||||
|
| Table 3B on page 33 of this manual. Replace | |||||
|
| sensor if necessary. |
|
|
| ||
|
| • Replace outlet sensor. |
|
|
| ||
|
|
|
|
|
|
|
|