Lochinvar 502 - 2072, 402 - 2072 service manual No Flame, Running, Auto Reset, High Limit

Page 37

Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual

3 Troubleshooting (continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

 

The unit was running and lost the flame signal.

• Inspect igniter and associated wiring for damage and

 

 

connection. Reference page 25 of this manual for

 

 

removal and cleaning procedure. Replace if

 

 

necessary.

 

 

 

 

 

 

 

• Check for proper electrical grounding of unit.

 

 

 

 

• Check incoming supply gas pressure. Refer to the

No Flame

 

Gas Connections Section of the Installation and

 

Operation Manual for detailed information concerning

Running

 

the gas supply.

 

 

 

 

(Will require a manual

 

• Verify that

the

tube from

the gas valve

to

the

reset once the condition

 

 

combustion

air

chamber is

connected and

is

not

has been corrected. Press

 

 

damaged.

 

 

 

 

 

the RESET button on the

 

 

 

 

 

 

 

 

 

 

 

 

 

SMART SYSTEM display

 

• Verify that the vent/air intake pipes are installed

to reset.)

 

correctly and there are no obstructions.

 

 

 

 

• Refer to the Checking Manifold Gas Pressure and

 

 

Combustion Analysis Procedure on pages 27 and 28

 

 

of this manual for the proper settings.

 

 

 

 

• Inspect the burners. Reference pages 26 and 27

 

 

of this manual for removal and cleaning procedures.

 

 

Replace if necessary.

 

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

The outlet water temperature has exceeded the

• Verify that the system is full of water and that all air

 

setting of the automatic reset high limit.

has been properly purged from the system.

 

 

 

 

• Verify that the appliance is piped properly into the

 

 

heating system. Refer to the Water Connections

 

 

Section of the Installation and Operation Manual for

 

 

the proper piping methods for the Copper-fin.

 

 

 

 

• Check 120 VAC to boiler pump motor on a call for

 

 

heat. If voltage is not present, check wiring back

 

 

to the main control board. Replace the main

 

 

control board if necessary.

 

 

 

Auto Reset

 

• If 120 VAC is present on a call for heat and the

High Limit

 

pump is not operating, replace the pump.

 

 

 

 

• If the system pump is a variable speed pump,

 

 

ensure that the system flow is not less than the

 

 

boiler flow.

 

 

 

 

 

 

 

• Check temperature setting of the main control

 

 

board.

 

 

 

 

 

 

 

• Check resistance of water sensors and compare to

 

 

Table 3B on page 33 of this manual. Replace

 

 

sensor if necessary.

 

 

 

 

 

• Replace outlet sensor.

 

 

 

 

 

 

 

 

 

 

 

37

Image 37 Contents
Copper-fin II/IIE Boiler, Water Heater Pool Heater Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid Service What is in this manual?Maintenance TroubleshootingCopper-fin display ServiceControl inputs Control outputs How the appliance operates General OperationHow the control module operates Sequence of operationOUT 123.8F129 Sequence of operationHTR Postpurge Display panel menu access Display panel parameter access Parameter table Datalogging Functions Settingsdhw ResetoutdoorAnti-cycle Delay Yes Viewable and changeable control parameters Temperature settings boiler onlyFunctions Data loggingDHW settings Outdoor air reset boiler only Anti-cycling Control modes Cascade Building Management System BMSCirculation pumps Service NotificationService technician Maintenance Maintenance and annual startupOwner maintenance See the User’s Information Manual for instructionsMaintenance Inspect/replace hot surface igniters Check relief valve Inspect/replace hot surface igniterCheck control settings Check all wiringInspect and clean burner Perform start-up and checksChecking combustion air pressure Access to the burner will require the following stepsChecking manifold gas pressure Adjusting combustion air pressureValve Fitting Control Knob Review with owner Inspect and clean the heat exchangerOiled bearing circulators Before troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does Not Resistance Temperature Checking temperature sensors Temperature Resistance No Pump NoisyBoiler Pump System Pump DHW PumpFlame Sequence Flow SwitchAnti-cycling No Flame Ign ErrorHSI Current Low Flame CKTNo Flame Auto ResetRunning High LimitInlet Low Manual ResetSensor Open Sensor ShortedTank Open Louver ProvingAPS Open APS ClosedRem Ctrl Flt Temp O/ShootParameters Service BlkProgr Low VoltageNo Error Stored Watch Dog ErrorWrite EEProm Program EEProm