Lochinvar 402 - 2072, 502 - 2072 service manual Maintenance

Page 24

Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual

2 Maintenance

￿WARNING

￿WARNING

￿WARNING

Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perform the service and maintenance could result in damage to the appliance or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.

The appliance should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the appliance designated in Table 2A and explained on the following pages must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure.

Electrical shock hazard – Turn off power to the appliance before any service operation on the appliance except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.

Address reported problems

1.Inspect any problems reported by the owner and correct before proceeding.

Inspect appliance area

1.Verify that appliance area is free of any combustible materials, gasoline and other flammable vapors and liquids.

Inspect appliance interior

1.Remove the outer access panels and inspect the interior of the appliance.

2.Vacuum any sediment from inside the appliance and components. Remove any obstructions.

Check all piping for leaks

Combustion air filter

This appliance has a standard air filter located at the combustion air inlet at the rear of the appliance. This filter helps ensure clean air is used for the combustion process. Check this filter every month and replace. The filter size on the 500,000 - 750,000 Btu/hr models is 12" x 12" x 1" and 16" x 16" x 1" on the 990,000 - 2,070,000 Btu/hr models. You can find these commercially available at any home center or HVAC supply store. Do not use pleated filters.

Check water system

1.

Verify all system components are correctly installed and

 

operational.

2.

Check the cold fill pressure for the system. Verify it is

 

correct (must be a minimum of 12 PSI).

￿WARNING

Eliminate all system or appliance leaks. Continual fresh makeup water will reduce appliance life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.

3.

Watch the system pressure as the boiler heats up (during

 

testing) to ensure pressure does not rise too high.

 

Excessive pressure rise indicates expansion tank sizing or

 

performance problem.

4.

Inspect automatic air vents and air separators. Remove

 

air vent caps and briefly press push valve to flush vent.

1.Inspect all water and gas piping and verify to be leak free.

2.Look for signs of leaking lines and correct any problems found.

3.Check gas line using the procedure found in the Gas Connections of the Installation and Operation Manual.

Flue vent system and air piping

1.Check for gastight seal at every connection, seam of air piping, and vent piping periodically inspected by a qualified service agency.

￿WARNING Venting system must be sealed gastight to prevent flue gas spillage and carbon

Replace caps. Make sure vents do not leak. Replace any

leaking vents.

Check expansion tank (if provided)

1.Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed, diaphragm or bladder type. See the Water Connections Section of the Installation and Operation Manual for suggested best location of expansion tanks and air eliminators.

24

monoxide emissions, which will result in severe personal injury or death.

Image 24
Contents Copper-fin II/IIE Boiler, Water Heater Pool Heater Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid What is in this manual? ServiceMaintenance TroubleshootingService Copper-fin displayControl inputs Control outputs General Operation How the appliance operatesHow the control module operates Sequence of operationSequence of operation OUT 123.8F129HTR Postpurge Display panel menu access Display panel parameter access Datalogging Functions Settingsdhw Resetoutdoor Parameter tableAnti-cycle Delay Yes Temperature settings boiler only Viewable and changeable control parametersData logging FunctionsDHW settings Outdoor air reset boiler only Anti-cycling Control modes Building Management System BMS CascadeService Notification Circulation pumpsMaintenance Maintenance and annual startup Service technicianOwner maintenance See the User’s Information Manual for instructionsMaintenance Check relief valve Inspect/replace hot surface igniter Inspect/replace hot surface ignitersCheck all wiring Check control settingsInspect and clean burner Perform start-up and checksAccess to the burner will require the following steps Checking combustion air pressureAdjusting combustion air pressure Checking manifold gas pressureValve Fitting Control Knob Inspect and clean the heat exchanger Review with ownerOiled bearing circulators Troubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No BurnerOperation Unit Does NotChecking temperature sensors Resistance TemperatureTemperature Resistance Noisy No PumpBoiler Pump System Pump DHW PumpFlow Switch Flame SequenceAnti-cycling Error No Flame IgnHSI Current Low Flame CKTAuto Reset No FlameRunning High LimitManual Reset Inlet LowSensor Open Sensor ShortedLouver Proving Tank OpenAPS Open APS ClosedTemp O/Shoot Rem Ctrl FltService Blk ParametersProgr Low VoltageWatch Dog Error No Error StoredWrite EEProm Program EEProm
Related manuals
Manual 44 pages 8.33 Kb Manual 44 pages 18.25 Kb Manual 80 pages 43.41 Kb

502 - 2072, 402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.