Precleaner Service

Use the following procedure to wash and oil the precleaner as indicated in the service schedule. Wash and oil the precleaner more often under extremely dusty or dirty conditions.

1.Press the OFF button on the generator set controller.

2.Disconnect the utility power to the generator set.

3.Disconnect the battery, negative (--) lead first.

4.Loosen the cover retaining knob and remove the cover. Remove the precleaner from the paper element. Wash the precleaner in warm water with detergent. Rinse the precleaner thoroughly until all traces of detergent are eliminated. Squeeze out excess water (do not wring). Allow the precleaner to air dry.

5.Saturate the precleaner with new engine oil. Squeeze out all of the excess oil.

6.Reinstall the precleaner over the paper element.

7.Reinstall the air cleaner cover. Secure the cover with the cover retaining knob.

8.Reconnect the power to the battery charger.

9.Reconnect the generator set engine starting battery, negative (--) lead last.

Paper Element Service

Use the following procedure to replace the paper element at the intervals specified in the service schedule. Replace the paper element more often under extremely dusty or dirty conditions.

1.Press the OFF button on the generator set controller.

2.Disconnect the utility power to the generator set.

3.Disconnect the generator set engine starting battery, negative (--) lead first.

4.Loosen the cover retaining knob and remove the cover.

5.Remove the element cover nut, element cover, and the paper element with precleaner.

6.Remove the precleaner from the paper element.

Note: Do not wash the paper element or clean it with pressurized air, as this will damage the element.

7.Replace the element if it is dirty, bent, or damaged.

8.Check the air cleaner base. Make sure it is secure and not bent or damaged. Also check the element cover for damage and fit. Replace all damaged air cleaner components. Remove any loose dirt or debris from the air cleaner base. Wipe the base carefully so that no dirt drops into the intake throat. Check the condition of the rubber seal on the air cleaner stud and replace the seal if necessary.

9.Reinstall the paper element, precleaner, element cover, element cover nut, and the air cleaner cover. Secure the cover with the cover retaining knob.

10.Reconnect the utility power to the generator set.

11.Reconnect the generator set engine starting battery, negative (--) lead last.

5.4.2Air Cleaner, 20RESA/RESAL Models

The engine is equipped with a replaceable, high density paper air cleaner element. See Figure 5-8.

 

 

 

1

 

 

 

2

 

 

 

3

 

 

 

4

 

 

 

tp6515

1.

Knobs (qty.2)

3.

Paper element

2.

Cover

4.

Base

Figure 5-8 Air Cleaner Components

Check the air cleaner daily or before starting the engine. Check for a buildup of dirt and debris around the air cleaner system. Keep this area clean. Also check for loose or damaged components. Replace all bent or damaged air cleaner components.

Note: Operating the engine with loose or damaged air cleaner components could allow unfiltered air into the engine causing premature wear and failure.

TP-6804 12/11

Section 5 Scheduled Maintenance 63

Image 63
Contents Models ControllersTP-6804 12/11 Engine Identification Product Identification InformationController Identification Generator Set Identification NumbersTable of Contents Networking Configuration Submenu OnCue Password Table of Contents TP-6804 12/11 Safety Precautions and Instructions BatteryAccidental Starting Exhaust System Engine Backfire/Flash FireHazardous Voltage/ Moving Parts Fuel System Hazardous NoiseHot Parts Heavy EquipmentList of Related Literature IntroductionEmission Information NameplateService Assistance Service Assistance TP-6804 12/11 Generator Set Enclosure Descriptions and Service ViewsTransfer Switch Introduction EngineRDC2 Controller Features DC2 Controller Features Accessories Removed to Show Detail Service ViewsDescriptions and Service Views TP-6804 12/11 Generator Set Operation Prestart ChecklistGenerator Set Operation Exercising the Generator SetAutomatic Operation with Model RDT or RSB Transfer Switches Automatic Operation with Model RXT Transfer SwitchSetting the Exerciser Unloaded Cycle Exercise with Complete System DiagnosticsExercise Faults Clearing a Fault on the RDC2 Controller Resetting the Controller after a Fault ShutdownCheck communication wiring between Controller Fault Messages Generator Set Operation TP-6804 12/11 RDC2 Generator Set/ Transfer Switch Controller Controls and IndicatorsRDC2 Controller Operation RUN OFF Auto Controller Keypad LED IndicatorsLCD Display Autopaging Displays, Automatic ModeController Power Battery ChargingChanging Settings Changing Settings Setting the Exerciser Setting the Exerciser at Controller Power--upChanging the Exercise Settings Procedure to Set the Exerciser on the RDC2 Controller Main Menu RDC2 Controller MenusEngine Metering Menu Overview Menu12 Generator Metering Menu Generator Metering MenuGenset Run Time Menu Generator Set Information Menu15 Genset System Menu Genset System Menu16 ATS Status Menu, with Calibration ATS Status Menu17 ATS Configuration Menu ATS Configuration MenuNetworking Information Menus Date and Time MenuDhcp Networking Status SubmenuReset OnCue Password? Yes Networking Configuration Submenu OnCue PasswordRbus Rbus Information23 Remote Devices Submenu Remote Devices Submenu24 Programmable Interface Module PIM Status Menu Programmable Interface Module PIM Status Menu25 Load Control Module LCM Status Menu Load Control Module LCM Menus26 Event Log Event LogDC2 Controller Operation DC2 Generator Set/ Transfer Switch ControllerDC2 Controller Pushbutton Operation Status Displays, Generator Running Exercise Modes Exerciser ResetOnCue Password Maintenance TimerDC2 Controller Operation TP-6804 12/11 Scheduled Maintenance Scheduled MaintenanceLubrication Service Schedule, 14RESA/RESAL ModelsService Schedule, 20RESA/RESAL Models Low Oil Pressure Shutdown Oil Change ProcedureLubrication System Engine Oil RecommendationOil Cooler 20RESA/RESAL Resetting the Maintenance TimerAir Cleaner Service Air Cleaner, 14RESA/RESAL ModelsSpark Plugs Air Cleaner, 20RESA/RESAL Models Cooling System EZ-273000-J Storage Procedure Introduction TroubleshootingFault Messages Controller Service AccessGeneral Troubleshooting Chart TroubleshootingAnsi Appendix a AbbreviationsLCB Page By Kohler Co. All rights reserved

14/20RESAL, 14/20RESA specifications

The Kohler 14/20RESA and 14/20RESAL are prominent generators recognized for their robust design, commitment to efficiency, and reliability in providing backup power for residential and light commercial applications. Kohler, a brand synonymous with quality, delivers these generators with advanced technologies and essential features that cater to the power needs of modern households and small businesses.

One of the major features of the Kohler 14/20RESA and 14/20RESAL models is their powerful engine, designed to deliver consistent and reliable performance. These generators are equipped with a high-performance, air-cooled, V-Twin engine that ensures smooth operation and longevity. The ability to run on either natural gas or propane provides versatility, making them suitable for various fuel preferences and availability.

Kohler’s innovative technology is reflected in the generator's Quiet Operation system, which minimizes noise levels, allowing homeowners to enjoy uninterrupted comfort during power outages. The noise-dampening qualities make the units ideal for residential settings, ensuring that they can operate without disturbing the peace of the neighborhood.

Another standout characteristic of the Kohler 14/20RESA and 14/20RESAL is the advanced digital control system. This system includes an intuitive LCD display that provides real-time data and diagnostics, allowing users to easily monitor the generator's performance. Features such as automatic voltage regulation and overload protection safeguard the generator and connected devices, preventing damage and ensuring stable power output.

The design of these generators emphasizes durability and ease of installation. The robust enclosure protects against environmental elements, making them suitable for outdoor placement. Additionally, the generators feature a compact footprint, which is advantageous in areas with confined spaces.

Residents will also appreciate the auto-start functionality, allowing the generator to turn on automatically during a power outage, ensuring that critical appliances continue to function without interruption. The remote monitoring capabilities also enhance user convenience, enabling owners to check on their generator's status from their smartphones or computers.

Maintenance is simplified with Kohler’s user-friendly design, which includes easy-access service points and a maintenance-free battery. This attention to serviceability enhances the overall user experience, ensuring that the generators operate efficiently for years.

In summary, the Kohler 14/20RESA and 14/20RESAL generators combine powerful performance with advanced technology, solid design, and user-friendly features. Their reliability makes them an excellent choice for anyone needing dependable backup power, whether for home, business, or specialized applications. With Kohler's reputation for quality backing these models, users can rest assured in their purchase decision.