Kohler 14/20RESAL manual Generator Set Operation, Prestart Checklist, Exercising the Generator Set

Page 21

Section 2 Generator Set Operation

2.1 Prestart Checklist

To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.

Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.

Air Inlets. Check for clean and unobstructed air inlets.

Battery. Check for tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and maintenance.

Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.

DInspect the exhaust system components for cracks, leaks, and corrosion. Check for tight exhaust system connections.

DCheck for corroded or broken metal parts and replace them as needed.

DCheck that the exhaust outlet is unobstructed.

Oil Level. Check the oil level before starting the generator set and at the intervals given in Section 5, Scheduled Maintenance. Maintain the oil level at or near, not over, the full mark on the dipstick.

Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.

2.2 Exercising the Generator Set

Operate the generator set without load once each week for 20 minutes. See Section 2.4 for information about loaded and unloaded exercise modes. For instructions to set the exerciser, see:

DSection 3.6 for the RDC2 controller

DSection 4.5 for the DC2 controller

2.3 Generator Set Operation

2.3.1Local Starting and Stopping

Start: Press the RUN button to immediately start the generator set.

Stop: Press the OFF button. The engine stops.

Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.

2.3.2Automatic Starting and Stopping

An automatic transfer switch monitors the utility power and signals the generator set to start when utility power is lost. The ATS then transfers the load to the generator set.

When utility power is restored, the transfer switch transfers the load back to utility, runs the generator set with no load to cool down the engine, and then stops the generator set.

2.3.3Remote Starting and Stopping

A remote switch connected to terminals 3 and 4 can be used to start and stop the generator set. Close the switch to start and run the generator set. Open the switch to stop the generator set.

Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.

2.3.4Engine Start Crank Cycle

The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off). If the generator set does not start in three attempts, the system shuts down on an overcrank fault. See Section 2.5.

Cranking 1, 2, and 3 are displayed during the crank cycle. Pressing the OFF button during the crank cycle stops the cranking. No other buttons are acknowledged during the crank cycle.

2.3.5Engine Cooldown

The engine cooldown time delay allows the engine to run after the loads have been removed.

The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if the temperature drops below the cooled-down

TP-6804 12/11

Section 2 Generator Set Operation 21

Image 21
Contents Models ControllersTP-6804 12/11 Controller Identification Product Identification InformationGenerator Set Identification Numbers Engine IdentificationTable of Contents Networking Configuration Submenu OnCue Password Table of Contents TP-6804 12/11 Safety Precautions and Instructions BatteryAccidental Starting Exhaust System Engine Backfire/Flash FireHazardous Voltage/ Moving Parts Fuel System Hazardous NoiseHot Parts Heavy EquipmentList of Related Literature IntroductionEmission Information NameplateService Assistance Service Assistance TP-6804 12/11 Transfer Switch Descriptions and Service ViewsIntroduction Engine Generator Set EnclosureRDC2 Controller Features DC2 Controller Features Accessories Removed to Show Detail Service ViewsDescriptions and Service Views TP-6804 12/11 Generator Set Operation Prestart ChecklistExercising the Generator Set Generator Set OperationAutomatic Operation with Model RDT or RSB Transfer Switches Automatic Operation with Model RXT Transfer SwitchSetting the Exerciser Unloaded Cycle Exercise with Complete System DiagnosticsExercise Faults Clearing a Fault on the RDC2 Controller Resetting the Controller after a Fault ShutdownCheck communication wiring between Controller Fault Messages Generator Set Operation TP-6804 12/11 RDC2 Generator Set/ Transfer Switch Controller Controls and IndicatorsRDC2 Controller Operation RUN OFF Auto Controller Keypad LED IndicatorsLCD Display Autopaging Displays, Automatic ModeController Power Battery ChargingChanging Settings Changing Settings Setting the Exerciser Setting the Exerciser at Controller Power--upChanging the Exercise Settings Procedure to Set the Exerciser on the RDC2 Controller Main Menu RDC2 Controller MenusEngine Metering Menu Overview Menu12 Generator Metering Menu Generator Metering MenuGenset Run Time Menu Generator Set Information Menu15 Genset System Menu Genset System Menu16 ATS Status Menu, with Calibration ATS Status Menu17 ATS Configuration Menu ATS Configuration MenuNetworking Information Menus Date and Time MenuDhcp Networking Status SubmenuReset OnCue Password? Yes Networking Configuration Submenu OnCue PasswordRbus Rbus Information23 Remote Devices Submenu Remote Devices Submenu24 Programmable Interface Module PIM Status Menu Programmable Interface Module PIM Status Menu25 Load Control Module LCM Status Menu Load Control Module LCM Menus26 Event Log Event LogDC2 Controller Operation DC2 Generator Set/ Transfer Switch ControllerDC2 Controller Pushbutton Operation Status Displays, Generator Running Exercise Modes Exerciser ResetOnCue Password Maintenance TimerDC2 Controller Operation TP-6804 12/11 Scheduled Maintenance Scheduled MaintenanceLubrication Service Schedule, 14RESA/RESAL ModelsService Schedule, 20RESA/RESAL Models Lubrication System Oil Change ProcedureEngine Oil Recommendation Low Oil Pressure ShutdownOil Cooler 20RESA/RESAL Resetting the Maintenance TimerAir Cleaner Service Air Cleaner, 14RESA/RESAL ModelsSpark Plugs Air Cleaner, 20RESA/RESAL Models Cooling System EZ-273000-J Storage Procedure Fault Messages TroubleshootingController Service Access IntroductionGeneral Troubleshooting Chart TroubleshootingAnsi Appendix a AbbreviationsLCB Page By Kohler Co. All rights reserved

14/20RESAL, 14/20RESA specifications

The Kohler 14/20RESA and 14/20RESAL are prominent generators recognized for their robust design, commitment to efficiency, and reliability in providing backup power for residential and light commercial applications. Kohler, a brand synonymous with quality, delivers these generators with advanced technologies and essential features that cater to the power needs of modern households and small businesses.

One of the major features of the Kohler 14/20RESA and 14/20RESAL models is their powerful engine, designed to deliver consistent and reliable performance. These generators are equipped with a high-performance, air-cooled, V-Twin engine that ensures smooth operation and longevity. The ability to run on either natural gas or propane provides versatility, making them suitable for various fuel preferences and availability.

Kohler’s innovative technology is reflected in the generator's Quiet Operation system, which minimizes noise levels, allowing homeowners to enjoy uninterrupted comfort during power outages. The noise-dampening qualities make the units ideal for residential settings, ensuring that they can operate without disturbing the peace of the neighborhood.

Another standout characteristic of the Kohler 14/20RESA and 14/20RESAL is the advanced digital control system. This system includes an intuitive LCD display that provides real-time data and diagnostics, allowing users to easily monitor the generator's performance. Features such as automatic voltage regulation and overload protection safeguard the generator and connected devices, preventing damage and ensuring stable power output.

The design of these generators emphasizes durability and ease of installation. The robust enclosure protects against environmental elements, making them suitable for outdoor placement. Additionally, the generators feature a compact footprint, which is advantageous in areas with confined spaces.

Residents will also appreciate the auto-start functionality, allowing the generator to turn on automatically during a power outage, ensuring that critical appliances continue to function without interruption. The remote monitoring capabilities also enhance user convenience, enabling owners to check on their generator's status from their smartphones or computers.

Maintenance is simplified with Kohler’s user-friendly design, which includes easy-access service points and a maintenance-free battery. This attention to serviceability enhances the overall user experience, ensuring that the generators operate efficiently for years.

In summary, the Kohler 14/20RESA and 14/20RESAL generators combine powerful performance with advanced technology, solid design, and user-friendly features. Their reliability makes them an excellent choice for anyone needing dependable backup power, whether for home, business, or specialized applications. With Kohler's reputation for quality backing these models, users can rest assured in their purchase decision.