Section 2 – Installation

QUIETPACT™ 75D Recreational Vehicle Generator

Because diesel fuels are less volatile than gasoline or gaseous fuels, they are considered safer from the standpoint of storage and handling. As a result, installers may tend to be careless in their installation practices, which can result in poor engine perfor- mance. For example, a poorly tightened fuel line may not show any signs of leakage; however, air can be drawn into the loose connection and cause problems. Air that is trapped in the diesel fuel system results in hard starting and rough engine operation.

Dirt that enters the fuel system also may cause prob- lems. Lines and piping must be properly installed and tightened to prevent dirt from entering. Diesel fuel must be kept clean.

Factory-installed generator fuel system components include (a) a fuel filter, (b) a 12-volt DC electric pump,

(c)an injection pump, and (d) interconnecting lines and fittings. Connect a fuel supply line to the supply fitting and a return line from the fuel return fitting back to the tank.

NOTE:

Fuel supply and return fittings located on the gen- erator are 1/8” NPT.

Use a length of approved flexible fuel hose between the fuel connection fittings and rigid fuel lines (see Sections 2.4.2 and 2.4.3).

2.4.1 FUEL TANK

Either the generator must share the vehicle’s engine fuel tank, or a separate fuel tank for the generator set must be installed. All fuel tanks installed on the vehi- cle must be constructed, installed, and restrained so they comply with applicable codes, standards, and regulations.

If the generator is to share the vehicle’s engine tank, separate fuel pickup tubes are required for the engine and the generator. Generac recommends that the fuel pickup tube be two to three inches (51 to 76 mm) shorter than the vehicle’s engine pickup tube. This prevents the generator from depleting the entire fuel supply during prolonged generator operating peri- ods.

Do NOT tee the generator fuel supply line into

!the vehicle engine fuel supply line. If this is done, the generator will be starved of fuel when both engines are operating at the same time. Also, while the vehicle engine is not run- ning, generator operation may drain the vehi- cle engine supply line, making it difficult to start the vehicle engine.

2.4.2 GENERATOR FUEL SUPPLY LINES

2.4.2.1 Rigid Fuel Lines

Those lines used to supply fuel from a tank to the generator must comply with applicable codes, stan- dards, and regulations. The following general rules apply to rigid fuel lines:

Rigid lines should be of annealed, seamless, drawn aluminum, or steel.

Lines and fittings must comply with SAE J512F, “Standard Automotive Fittings,” or with ANSI B126.26 (latest edition).

Route the fuel line so that at least 2 inches (51 mm) of clearance is maintained between the line and any exhaust system parts.

Do not attach electrical wiring to fuel lines. Route the wiring so it cannot come into contact with any fuel line.

Route fuel lines so that, if they leak, fuel does not drip onto any electrical or exhaust system parts.

Use nonferrous metal straps without sharp edges to secure fuel lines.

Fuel system components must be accessible, but protected from abrasion, chafing, road damage, and kinking.

2.4.2.2 Flexible Fuel Line

Use a length of approved flexible fuel hose between the generator fuel supply fitting and rigid fuel lines. This prevents breaking of the line caused by vibra- tion, shifting, settling, or movement. The following rules apply:

The flexible hose must comply with SAE J30B, “Standard for Fuel and Oil Hose.” It must be approved for use with diesel fuel.

The hose should be at least 6 inches (152 mm) longer than is needed, to prevent the hose from rupturing if the generator shifts or settles.

2.4.3 GENERATOR FUEL RETURN LINES

The same general rules that apply to fuel supply lines also apply to fuel return lines.

NOTE:

Locate the diesel fuel return line at least 12 inch- es from the tank fuel pickup tubes to prevent air bubbles from entering the fuel supply lines.

28 Generac® Power Systems, Inc.

Image 30
Contents Liquid-cooled Recreational Vehicle Generator Authorized Service Dealer Location IntroductionPart II Installation Instructions Table of ContentsGeneral Hazards Electrical Hazards Generator Identification ModelQuietpact 75D Generator Applicability SafetySpecifications Generator AC Connection SystemCoolant Fuel Consumption GAL/HREngine OIL Requirements EngineGenerator Control Panel Optional Remote START/STOPBefore Starting the Engine Starting the Generator Stopping the Generator Protection SystemsOvervoltage Protection Additional InformationOverspeed Shutdown 1 25-HOUR BREAK-IN PeriodOperation in High Grass or Brush Checking the Engine OIL LevelChanging the Engine OIL AND/OR OIL Filter Effects of Moisture and DirtServicing the Engine AIR Filter Spark Arrestor MufflerCleaning the Generator Battery MaintenanceDrive Belt Cooling SystemEngine Coolant Exercising the GeneratorOUT-OF-SERVICE Procedure Removal from ServiceReturn to Service Service Schedule Part General Hazards Fire Hazards Equipment Description Purpose and Scope ManualStandards Booklets Generator Engine Operating SpeedMajor Features and Dimensions Generator Support Location and SupportGenerator Location Suspended MountingGenerator Compartments Generator RestraintCompartment Construction Sound Insulating Materials AcousticsTypical Noise Abatement 2.2.4 Compartment Floor Cutouts Cooling and Ventilating AIR Cooling AIR Inlet OpeningsGenerator Airflow Testing the Installation Diesel Fuel SystemCompensating for Restrictions Fuel Tank Generator Fuel Supply LinesGenerator Fuel Return Lines Exhaust System Safety Exhaust SystemMuffler and Spark Arrestor Electrical Junction BOX WiringElectrical Connections Generator AC ConnectionsGenerator Coversion to Volts Only Dual CircuitsPower Supply Cord Isolating Different Power SourcesConduit Battery Cables Battery InstallationRecommended Battery Battery Cable ConnectionsOptional Accessories Battery CompartmentRemote START/STOP Connections Before Initial Startup Post Installation TestsTesting Under Load Initial StartInstallation Checklist Troubleshooting Guide Problem Cause CorrectionAppendix 2 Notes Appendix 2 Notes Appendix 3 Electrical Data Appendix 3 Electrical Data Appendix 3 Electrical Data Wiring Diagram 120 VAC- Drawing No. 0D2793-B Part Part NO. QTY Description 677mm Item Part NO. QTY. Description 0C4554 Shaft, Fan 0C4845 Gasket, Electrical Enclosure Divider Exhaust Gasket 0C6946A Fuel Pump Assembly 023484F Snap Bushing 052219 2118 11 29 32 33 Camshaft Assembly Complete Cylinder Block Cylinder Head Assembly Crankshaft Assembly Idler Gear Assembly Rocker ARM Assemblyincludes ALL Components Shown below Injector Pump Assembly Fuel Filter Support HOUSING, Timing Gear OIL PAN Water Pump Assembly Appendix 5 Notes Manufacturers Warranty Coverage Federal and California Emissions Control Warranty StatementYour Warranty Rights and Obligations Parts CoveredObtaining Warranty Service Obligations and Rights of the Manufacturer and OwnerLimitations Warranty Schedule CONSUMER/PERSONAL Applications

004270-2 specifications

Guardian Technologies has made significant strides in air purification technology with its model 004270-2, which stands out for its advanced features and impressive performance. Designed to enhance indoor air quality, this air purifier combines efficiency and innovation to create a healthier living environment.

One of the most notable features of the Guardian Technologies 004270-2 is its multi-layer filtration system. This system includes a true HEPA filter that captures 99.97% of airborne particles as small as 0.3 microns. This means that allergens such as dust mites, pet dander, and pollen are effectively removed from the air. In addition to the HEPA filter, the unit also incorporates a charcoal filter that eliminates unpleasant odors, making it perfect for homes with pets or cooking frequently.

The Guardian Technologies 004270-2 employs UV-C light technology to further enhance its air purification capabilities. This innovative feature works by using ultraviolet light to kill bacteria and viruses, promoting a healthier atmosphere. The combination of HEPA filtration and UV-C technology sets this model apart from standard air purifiers, providing an extra layer of protection against harmful microorganisms.

Another characteristic that contributes to the efficiency of the Guardian Technologies 004270-2 is its quiet operation. This model is engineered to minimize noise levels, making it suitable for use in bedrooms, living spaces, or offices without disrupting daily activities. Users can enjoy clean air without the annoyance of constant fan noise.

The design of the 004270-2 is also worth mentioning. Its sleek, modern appearance allows it to fit seamlessly into any room decor while being compact enough for easy placement. Additionally, the unit features a filter change indicator, ensuring that users are aware when it’s time to replace the filters for optimal performance.

Energy efficiency is another advantage of this air purifier, as it is designed to consume less power while providing powerful air purification. This not only helps in reducing electricity bills but also promotes eco-friendly practices.

In summary, the Guardian Technologies 004270-2 is an exemplary air purifier that boasts a robust filtration system, innovative UV-C technology, quiet operation, and energy efficiency. It effectively addresses common indoor air quality concerns, making it an ideal choice for households seeking a healthier atmosphere.