Greenheck Fan 55, HRE-20 Frost Control Application/Operation, Frost Threshold Temperatures, Timer

Page 18

optional accessories

Frost Control Application/Operation

Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:

1)

Timed Exhaust frost control

 

 

Indoor RH @ 70º F

Frost Threshold Temp

2)

Electric preheat frost control

 

 

20%

2º F

3)

Modulating wheel frost control

 

 

25%

7º F

All of these options are provided with a thermostat (with

 

 

30%

14º F

probe) mounted in the outdoor air inlet compartment and

a pressure sensor to monitor pressure drop across the

Frost Threshold Temperatures

wheel.. The typical temperature setting corresponds to the

 

 

indoor air relative humidity as shown in the Frost Threshold Temperatures Table and represents when frost can occur.. An increase in pressure drop would indicate that frost is occurring.. Both the pressure sensor and the outdoor air temperature sensor must trigger in order to initiate frost control.. The two sensors together insure that frost control is only initiated during a real frost condition.. Field wiring of a light (or other alarm) between 6 & C in the control center will notify personnel when unit is in frost control mode (refer to Remote Panel Wiring schematics section for wiring details).. The following explains the three options in more detail..

Timed exhaust frost control includes a timer in addition to the thermostat and pressure sensor.. When timed exhaust frost control is initiated, the timer will turn the supply blower on and off to allow the warm exhaust air to defrost the energy recovery wheel.. Default factory settings are 5 minutes off and 30 minutes on.. Use the following test procedure for troubleshooting..

Testing (refer to diagram at right)

Jumper the pressure switch. Set the Timer Scale for T1 and T2 to

1 minute.. Set the Timer Settings for T1 and T2 to 1..0.. Set the dip switch to the down position..

Turn the temperature sensor up as high as possible. The supply blower should cycle on for one minute, then turn off for one minute..

After testing, set the Timer Scale as follows: T1 = 10 minutes, T2 =

1 hour

A1

B1

15

0.8

0.6

Dip

1.0

0.4

Switch

0

0.2

 

T2

1 MIN T2

 

Timer

Scale

1 MIN T1

0.8 0.6

1.0 0.4 0 0.2

T1

16 18 A2

Timer

Set the Timer Settings as follows: T1 = 0.5, T2 = 0.5. The timer is now set for 5 minutes off and 30 minutes on.. Remember to remove the jumper.

Electric preheat frost control includes an electric heater (outdoor air inlet) and an air pressure switch (outdoor air outlet) in addition to the thermostat and pressure sensor on wheel.. (Refer to Electric Heater Application/Operation for electric preheater location).. When electric preheat frost control is initiated, the electric preheater will turn on and warm the air entering the energy wheel to avoid frosting.. Use the following test procedure for troubleshooting..

Testing

Turn the thermostat as high as it will go and jumper the wheel pressure sensor. The heater should turn on..

If it doesn’t, either put the supply side doors on or temporarily jumper the air pressure switch to avoid nuisance tripping of the pressure switch.. Remember to remove the jumpers.

Modulating wheel frost control includes a variable frequency drive in addition to the thermostat and pressure sensor.. When modulating wheel frost control is initiated, the variable frequency drive will reduce the speed

of the wheel reducing the speed of the energy wheel reduces its effectiveness, which keeps the exhaust air condition from reaching saturation, thus, eliminating condensation and frosting.. If the outdoor air temperature is greater than the frost threshold temperature OR the pressure differential is less than the setpoint, the wheel will run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure differential is greater than the setpoint, the wheel will run at reduced speed until the pressure differential falls below the setpoint.. The temperature and pressure differential set points are set at the factory, but are field- adjustable (refer to VFD section for more information).. The variable frequency drive will be fully programmed at the factory..

18

Image 18
Contents Read and Save These INSTRUCTIONS461248 Indirect Evaporative CoolerDirect Evaporative Cooler TABLE OF Contents StorageBasic Operation Installation Safety WarningLifting Roof Curb Mounting Supply Weatherhood Rail MountingDuctwork Connections Exhaust WeatherhoodElectrical Information TYPICAL CONTROL CENTER COMPONENTS Exploded Detail Terminal StripService Clearances / access panel locations HRE-20 HRE-45HRE-55 HRE-90 Overall Exterior Dimensions Model Dimensional Data / Access Door DescriptionsModel Exterior Dimensions HRE-20 Dimensional dataEvaporative Cooling Modules Evap Module InstallationStandard Trap and Supply Line Configuration Evap Module START-UPWater Flow Adjustment DevicePump and Float Components HRE Water SUPPLY CONNECTION LocationTop View Water Control Options for Evaporative Cooling EvaporativeEvaporative FreezeTimer ProtectionTrap & Supply Line Configuration with Auto Drain and Fill Auto Drain and Fill with Freeze ProtectionDrain Trap Drain and Overflow Connection Locations Troubleshooting for evaporative module Symptom SolutionEvaporative Cooling Maintenance Electric Preheater Optional accessoriesElectric Heater Application/Operation Post-Heater Control PanelTesting Frost Threshold TemperaturesTimer Frost Control Application/OperationEconomizer Application/Operation Modulating the Wheel Enthalpy Sensor With OverrideVariable Frequency Drives for Blowers Yaskawa Yaskawa E7Variable Frequency Drives for Energy Recovery Wheel Factory Setpoints Modulating Control 0-10 VDC for FAN SpeedWiring Diagram TransformerRotation Sensor Dirty Filter SensorService Outlet CO2 SensorVapor Tight Lights Optional Accessories Remote Control Panel and Wiring SchematicsRemote Panel Wiring Schematics Indicator Lights powered by the ER UnitHeating/Cooling Switches and Night Setback Switch/Timer Temperature Sensors 1K Ohm RTD Sensors Mounted by FactoryStart-Up Checklist for unit Safety DangerSafety Caution Start-Up Checklist Start-Up Checklist for Evaporative CoolerSpecial Tools Required Economizer Application / Operation section Optional Accessories ChecklistOptional Accessories section Variable Frequency Drives sectionFan Performance Modifications Unit start-upFans Forward Curved Type Fan Belt DrivesVibration Direction of Fan Wheel RotationFan RPM Rotation DirectionDrive Belt Air SealsInside layout of HRE unit Routine maintenance DateFan Belts LubricationDampers Fan MotorsDoor Seal Maintenance External Filter MaintenanceInternal Filter Maintenance BearingsEnergy Recovery Wheel Maintenance Access to wheel through Outdoor air filter doorWheel segment removed Wheel Belt & Pulley Wheel BearingParts List Model HRESummer Operation Sequence of OperationBasic Unit Winter OperationDesign Airflow Pressure Drop Across Energy Recovery WheelTest and Balance Report Measured AirflowTroubleshooting Symptom Possible Cause Corrective ActionWarranty
Related manuals
Manual 24 pages 59.92 Kb

45, 55, 90, HRE-20 specifications

The Greenheck Fan HRE series, specifically the models HRE-20, HRE-90, HRE-55, and HRE-45, represents a blend of innovation and efficiency in the HVAC industry. Built for both commercial and industrial applications, these exhaust fans stand out due to their robust design and advanced operational features.

One of the main features of the HRE series is its energy-efficient motor design. These fans come equipped with a premium efficiency motor that reduces energy consumption while maintaining high performance. The motors are specifically designed to provide exceptional airflow while operating at lower sound levels, ensuring a quieter environment.

The HRE models also showcase advanced aerodynamic design, featuring optimized blade geometry that enhances airflow performance. This design ensures that the fans can deliver consistent and effective air movement even at varying operational conditions. This makes the HRE series suitable for use in a wide range of applications, from commercial kitchens to industrial processes.

Another significant characteristic of the HRE series is its durability. Constructed from high-quality materials, these fans are built to withstand harsh environmental conditions and prolonged usage. The robust casing and corrosion-resistant finishes ensure longevity, reducing the need for frequent repairs or replacements.

In terms of installation and maintenance, the HRE series offers significant advantages. The fans are designed for easy installation with clear mounting instructions. Additionally, maintenance procedures are simplified, allowing for hassle-free access to critical components, which reduces downtime and operating costs.

Technologically, the HRE models incorporate advanced controls and monitoring systems. These systems can offer real-time feedback on operational performance, allowing for proactive maintenance and energy management. Integrated controls can be customized to work with building management systems, providing users with seamless integration and control capabilities.

Overall, the Greenheck Fan HRE-20, HRE-90, HRE-55, and HRE-45 exemplify a commitment to quality and efficiency in commercial and industrial ventilation solutions. Their combination of energy efficiency, advanced design, durability, and user-friendly features make them a leading choice for those seeking reliable airflow solutions. These fans not only meet current industry standards but also set a benchmark for performance and innovation in the HVAC sector.