Greenheck Fan 55, 90 Evaporative Cooling Modules, Evap Module Installation, Evap Module START-UP

Page 10

EVAPORATIVE COOLING MODULES

Mount the heat recovery unit level to ensure proper operation and water drainage.. Piping should be of adequate size to provide sufficient supply of water to meet the maximum demand of the evaporative coolers..

EVAP MODULE INSTALLATION

1.After the energy recovery unit is set in place, run the overflow and drain lines to the exterior fittings on the evaporative cooler (drain & overflow connections at unit are 1-inch male pipe thread).. The supply line can be attached at the downstream side of the evaporative cooler.. A manual shut off valve should be mounted in the supply line near the unit for servicing purposes.. Also, a trap should be installed in the drain line to prevent air/sewer gas from being drawn into the unit (refer to Drain and Overflow Connection Locations and Drain Trap sections).. Run bleed line into overflow..

EVAP MODULE START-UP

1.The cooler will be prewired by the factory.. (pumps are 115VAC)..

2.Check to make sure that the pump filter is around the pump inlet..

Indirect Evaporative Cooler

(Exhaust/Scavenger Airstream)

Direct Evaporative Cooler

(Outdoor/Supply Airstream)

3.Turn the water on and allow the sump to fill.. Adjust the float valve to shut-off the water supply when the sump is filled to a 1-inch height..

4.Open the bleed-off valve completely and saturate the media without any airflow through the unit.. A jumper wire is required on the terminal strip to provide power to the evaporative cooler pump (see the wiring diagram for the proper location).. This saturation process will break-in the media and minimize the odors

 

 

 

associated with the media.. The media’s break-in period should

Side of HRE Unit

 

be no less than 20 minutes.. When the process is complete,

 

remove the jumper wires in the control center..

 

 

 

Note: Evaporative media may foam for a short period

Drain Line

Evaporative

following the initial start-up.. Leave the bleed-off

valve fully open until the foaming stops..

 

 

Overflow

 

Cooling

 

 

 

Media

5.. After the media break-in period, the

 

 

Trap

 

Sump

water flow rate over the media needs to be

 

checked.. The pumps should provide enough

 

Manual

 

 

 

 

water to saturate the media in 1-3

 

Shutoff

 

 

 

 

 

minutes.. If adequate flow rate is

Drain

Valve

Roof Curb

 

 

 

not achieved, adjust via water

Line

 

 

 

 

Roof Line

 

 

 

flow adjustment device found on

 

 

 

 

water supply line running to evap

Manual Shutoff Valve

header..

Supply Line

 

Standard Trap and Supply Line Configuration

6..The water bleed-off rate will now need to be adjusted.. This measurement is 3 to 6 percent of the media flow rate.. The recommended flow rate is 11/2 to 2 GPM

per square foot of media pad top area (see table at right).. Actual water to the unit will be based on the evaporation rate.. A water flow adjustment device is supplied and installed by Greenheck for ease of water flow adjustments.. After the unit has been installed and running for two weeks the unit should be checked for mineral deposits.. If there are deposits, the bleed-off rate needs to be increased.. Some areas of the country have water with greater amounts of dissolved minerals requiring a higher bleed-off rate..

 

 

Media Size

Media Pad

 

 

(w x h x d) (in.)

Top Area

 

 

 

 

HRE-20

Supply

18 x 36 x 12

1..5 ft2

Exhaust

18 x 36 x 12

1..5 ft2

 

 

 

 

 

HRE-45

Supply

30 x 48 x 12

2..5 ft2

Exhaust

24 x 48 x 12

2..0 ft2

 

 

 

 

 

HRE-55

Supply

36 x 56 x 12

3..0 ft2

Exhaust

30 x 56 x 12

2..5 ft2

 

 

 

 

 

HRE-90

Supply

48 x 69..5 x 12

4..0 ft2

Exhaust

40 x 69..5 x 12

3..3 ft2

 

 

 

 

 

10

Image 10
Contents Indirect Evaporative Cooler Read and Save These INSTRUCTIONS461248Direct Evaporative Cooler Storage TABLE OF ContentsBasic Operation Safety Warning InstallationLifting Roof Curb Mounting Supply Weatherhood Rail MountingDuctwork Connections Exhaust WeatherhoodElectrical Information TYPICAL CONTROL CENTER COMPONENTS Exploded Detail Terminal StripHRE-20 HRE-45 Service Clearances / access panel locationsHRE-55 HRE-90 Overall Exterior Dimensions Model Dimensional Data / Access Door DescriptionsModel Exterior Dimensions HRE-20 Dimensional dataEvaporative Cooling Modules Evap Module InstallationStandard Trap and Supply Line Configuration Evap Module START-UPHRE Water SUPPLY CONNECTION Location Water Flow Adjustment DevicePump and Float ComponentsTop View Water Control Options for Evaporative Cooling EvaporativeEvaporative FreezeTimer ProtectionTrap & Supply Line Configuration with Auto Drain and Fill Auto Drain and Fill with Freeze ProtectionDrain Trap Drain and Overflow Connection Locations Troubleshooting for evaporative module Symptom SolutionEvaporative Cooling Maintenance Electric Preheater Optional accessoriesElectric Heater Application/Operation Post-Heater Control PanelTesting Frost Threshold TemperaturesTimer Frost Control Application/OperationEconomizer Application/Operation Modulating the Wheel Enthalpy Sensor With OverrideVariable Frequency Drives for Blowers Yaskawa Yaskawa E7Variable Frequency Drives for Energy Recovery Wheel Factory Setpoints Modulating Control 0-10 VDC for FAN SpeedWiring Diagram TransformerRotation Sensor Dirty Filter SensorCO2 Sensor Service OutletVapor Tight Lights Optional Accessories Remote Control Panel and Wiring SchematicsRemote Panel Wiring Schematics Indicator Lights powered by the ER UnitHeating/Cooling Switches and Night Setback Switch/Timer Temperature Sensors 1K Ohm RTD Sensors Mounted by FactorySafety Danger Start-Up Checklist for unitSafety Caution Start-Up Checklist for Evaporative Cooler Start-Up ChecklistSpecial Tools Required Economizer Application / Operation section Optional Accessories ChecklistOptional Accessories section Variable Frequency Drives sectionFan Performance Modifications Unit start-upFans Forward Curved Type Fan Belt DrivesVibration Direction of Fan Wheel RotationFan RPM Rotation DirectionAir Seals Drive BeltInside layout of HRE unit Routine maintenance DateFan Belts LubricationDampers Fan MotorsDoor Seal Maintenance External Filter MaintenanceInternal Filter Maintenance BearingsAccess to wheel through Outdoor air filter door Energy Recovery Wheel MaintenanceWheel segment removed Wheel Belt & Pulley Wheel BearingParts List Model HRESummer Operation Sequence of OperationBasic Unit Winter OperationDesign Airflow Pressure Drop Across Energy Recovery WheelTest and Balance Report Measured AirflowTroubleshooting Symptom Possible Cause Corrective ActionWarranty
Related manuals
Manual 24 pages 59.92 Kb

45, 55, 90, HRE-20 specifications

The Greenheck Fan HRE series, specifically the models HRE-20, HRE-90, HRE-55, and HRE-45, represents a blend of innovation and efficiency in the HVAC industry. Built for both commercial and industrial applications, these exhaust fans stand out due to their robust design and advanced operational features.

One of the main features of the HRE series is its energy-efficient motor design. These fans come equipped with a premium efficiency motor that reduces energy consumption while maintaining high performance. The motors are specifically designed to provide exceptional airflow while operating at lower sound levels, ensuring a quieter environment.

The HRE models also showcase advanced aerodynamic design, featuring optimized blade geometry that enhances airflow performance. This design ensures that the fans can deliver consistent and effective air movement even at varying operational conditions. This makes the HRE series suitable for use in a wide range of applications, from commercial kitchens to industrial processes.

Another significant characteristic of the HRE series is its durability. Constructed from high-quality materials, these fans are built to withstand harsh environmental conditions and prolonged usage. The robust casing and corrosion-resistant finishes ensure longevity, reducing the need for frequent repairs or replacements.

In terms of installation and maintenance, the HRE series offers significant advantages. The fans are designed for easy installation with clear mounting instructions. Additionally, maintenance procedures are simplified, allowing for hassle-free access to critical components, which reduces downtime and operating costs.

Technologically, the HRE models incorporate advanced controls and monitoring systems. These systems can offer real-time feedback on operational performance, allowing for proactive maintenance and energy management. Integrated controls can be customized to work with building management systems, providing users with seamless integration and control capabilities.

Overall, the Greenheck Fan HRE-20, HRE-90, HRE-55, and HRE-45 exemplify a commitment to quality and efficiency in commercial and industrial ventilation solutions. Their combination of energy efficiency, advanced design, durability, and user-friendly features make them a leading choice for those seeking reliable airflow solutions. These fans not only meet current industry standards but also set a benchmark for performance and innovation in the HVAC sector.