Page 18

Section 4 — Maintenance

Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators

4.5MAINTENANCE OWNER/ OPERATOR CAN PERFORM

‹4.5.1 CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels” in Section 4.4.

‹4.5.2 CHECK BATTERY

Check battery fluid level each week as outlined under “Check Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹4.5.3 EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. See Section 3.5, “Weekly Exercise Cycle”.

‹4.5.4 INSPECT COOLING SYSTEM

Inspect engine cooling system at least once each month.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹4.5.5 CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels” in Section 4.4.

‹4.5.6 PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

DANGER

DANGER: Do not attempt to adjust the gover-

!nor. Only qualified service facilities should adjust the governor. Excessively high operat- ing speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may short- en engine life. Correct rated frequency and voltage are supplied only at the proper gov- erned speed. Some connected electrical load devices may be damaged by incorrect fre- quency and/or voltage. Only qualified service technicians should adjust the governed speed.

‹4.5.10 CHANGING ENGINE OIL

Refer to maintenance performed by authorized serv- ice facilities for engine oil and filter change frequen- cies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 4.2) counterclockwise and remove. Dispose of old filter.

Figure 4.2 - Oil Filter

‹4.5.7 INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹4.5.8 CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 3/4 inch. Adjust belt tension as required.

‹4.5.9 INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

OIL FILTER

5.Apply light coating of new engine oil to seal of new oil filter. Install FILTER and tighten by hand only.

DO NOT OVERTIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

16 Generac® Power Systems, Inc.

Image 18
Contents Liquid-cooled, Prepackaged Standby Generators ‹ HOW to Obtain Service Authorized Service Dealer Location‹ Operation and Maintenance IntroductionIntroduction IFC Safety Rules General Hazards Electrical Hazards Automatic System Operation Transfer SwitchGenerator Generator AC Connection Systems‹ 1.7.3 LOW Coolant Level Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Engine Protective DevicesUnpacking Lifting the Generator‹ 1.10.1 Generator Specifications SpecificationsReconfiguring the Fuel System ‹ 1.10.2 Engine SpecificationsTorque Specifications Engine OIL RecommendationsCoolant Recommendations Basic Standby Electric System Generator LocationGenerator Mounting Support ‹ 2.1.1 Nfpa StandardsTotal Circuit Isolation Method Transfer Switch Start Signal ConnectionsEmergency Circuit Isolation Method Grounding the Generator‹ 2.10.1 Vented Batteries Battery InstallationPreparation Before START-UP ‹ 2.11.1 Prior to Initial START-UPUsing a Standard GTS Transfer Switch Control Console Components Manual Transfer START-UP Automatic OperationWeekly Exercise Cycle Once Every SIX Months Engine HeaterEvery Three Months Once AnnuallyCooling System Checking Fluid LevelsOverload Protection for Engine DC Electrical System ‹ 4.5.3 Exercise System ‹ 4.5.2 Check Battery‹ 4.5.1 Check Engine OIL Level ‹ 4.5.4 Inspect Cooling System‹ 4.6.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.13 Coolant Change‹ 4.6.3 Battery Maintenance ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionGuardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Installation Diagram Section Electrical Data Customer Connection 120/240V 1-PHASE Electrical Data Cover Connector Housing Housing Governor ConnectorConnector Interface Assembly ASM Motor StepperDampener Vibration Base Mounting 1.5L Stnrd & AcstcWasher Shakeproof EXT 5/16 STL Washer Flat 5/16 ZincWeld Stud Under Roof Panel for Access Cover Cable Assembly Cover Access Assembly BASE-DOOR Ground WireGRD Wire Assy 99HSB Cover Access GENWeld Stud Under Roof For Access Cover Cable Washer Self Locking Dome Roof Acstc & Stnd Cmprtmnt 1.5LDoor Weldment 1.5 EPS Baffle Cntrl PNL 1.5L AcousticTo a Hourmeter Wire AssemblySilksc Holder FuseWaterpump Hardware Ground Wire Starter Switch OIL PressureARM Adjust Alternator Clamp for Wiring Harness not Shown16 7 Venturi 1.5L Modine Tank Coolant RecoveryRadiator 1.5L Guard FAN 1.5L ModineVapor Weldment Mounting Base Cover AIR CleanerGasket AIR Cleaner Adapter Flange Fuel Inlet16 30 21 Assy Rotor 15KW Housing BlowerAssy Rotor 10KW Assy Rotor 20KWBRACKET, Battery Hold Down ASSY,WIRE#16 REDBOOT, Battery Cable Battery Post Cover RED+Saddle 2 Inch Manifold Exhaust 1.5LNipple TOE 1.5NPTX5.5 BLK Iron PIPE,EXHAUST 1.5L STNDRD&ACSTCYour Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

004721-0, 004722-0, 004723-0, 004724-0, 004725-0, 004725-1, 004725-2, 004725-3, 004726-0 specifications

Generac Power Systems is a leader in energy solutions, committed to providing reliable power products for homes, businesses, and industrial applications. Among their extensive range of products, the Generac Power Systems models 004721-0, 004722-0, 004723-0, 004724-0, 004725-0, 004725-1, 004725-2, 004725-3, and 004726-0 stand out due to their advanced features and innovative technologies.

One of the key features of these models is the robust engine performance. They are designed with Generac's signature engines, which ensure optimal power output and durability. This leads to better energy efficiency while maintaining a low operating cost. The models are engineered for seamless operation under various load conditions, ensuring that you stay powered in any situation.

These Generac models also incorporate state-of-the-art transfer switch technology, which enhances their reliability. The transfer switches ensure that power is instantly transferred from the grid to the generator during an outage, allowing for uninterrupted service. This is especially critical for homes and businesses where power reliability is essential.

Combining convenience with efficiency, the models feature user-friendly interfaces that simplify operation. With available mobile monitoring options, users can keep track of their power status and diagnostics remotely. This is a game changer for individuals who want to maintain oversight of their energy solutions without being physically present.

Safety is another critical aspect integrated into the Generac Power Systems. The models are equipped with advanced safety features such as overload protection, low oil shutdown, and high-temperature shutdown, ensuring an added layer of security for users.

Moreover, these models are built with rugged construction materials making them suitable for all environmental conditions. Whether it’s extreme cold or heat, they are crafted to withstand the elements while performing at peak efficiency.

Generac Power Systems emphasizes sustainability as well, with models designed for lower emissions and quieter operation. This is ideal for homeowners and businesses conscious of their environmental impact and seeking to reduce noise pollution.

Overall, the Generac Power Systems models 004721-0, 004722-0, 004723-0, 004724-0, 004725-0, 004725-1, 004725-2, 004725-3, and 004726-0 represent the evolution of power generation technology. With their robust features, efficient operation, and commitment to safety, these generators are an excellent investment for anyone seeking reliable power solutions.