Generac Power Systems 0043733, 0046264, 0046263 Battery Installation, Preparation Before START-UP

Page 12

Section 2 — Installation

Guardian Liquid-cooled 40 kW Generator

NOTE:

When using a GTS switch, it is necessary to connect a 240V AC supply to N1 and N2 terminals of the generator to provide for battery charging. Wires T1, T2, 23 and 194 should not be connected.

2.7BATTERY INSTALLATION

DANGER

Standby generators installed with automatic trans- ! fer switches will crank and start automatically

when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per- sonnel, do not connect battery cables until the normal source voltage at the transfer switch is cor- rect and the system is ready to be placed into operation.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat- tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caustic ! sulfuric acid solution that can cause severe burns.

Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not dispose of the battery in a fire. The battery is capable of exploding.

Do not open or mutilate the battery. Released ! electrolyte can be toxic and harmful to the skin

and eyes.

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

10 Generac® Power Systems, Inc.

‹2.7.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is

!harmful to the skin and eyes. It is electrically con- ductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing,

Where electrolyte contacts the skin, wash it off immediately with water,

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical atten- tion, and

Spilled electrolyte is to be washed down with an acid- neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead acid batteries present a risk of fire because they generate hydrogen gas. The following proce- dures are to be followed:

DO NOT SMOKE when near batteries,

DO NOT cause flame or spark in battery area, and

Discharge static electricity from body before touching batteries by first touching a grounded metal surface.

Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

For recommended batteries, see Section 4.5, “Battery Maintenance”. All batteries must be at 100 percent state- of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not neces- sary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals spec- ified in Section 4, “Maintenance.” A negative ground sys- tem is used. Battery connections are shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

NOTE:

Damage will result if the battery connections are reversed.

2.8PREPARATION BEFORE START-UP

The instructions in this section assume that the standby generator has been properly installed, serviced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on Pages 2 and 3, as well as all other safe- ty information in this manual, before attempting to oper- ate this (and related) equipment.

Image 12
Contents 0046262, 0046263 Introduction Authorized Dealer LocationIntroduction Inside Front Cover General Hazards Electrical Hazards Prepackaged Transfer Switch UNPACKING/INSPECTIONGenerator Generator AC Connection SystemsSpecifications Main Circuit BreakerEngine Protective Devices Fuel Requirements Recommendations ‹ 1.8.2 Generator and Load Compatibility‹ 1.9.1 Conversion to LP GAS Vapor Emissions Control System Coolant‹ 1.12.1 AIR Fuel Ratio Controller Standby Generator Installation Basic Standby Electric SystemNfpa Standards Other Published StandardsTransfer Switch Start Signal Connections ‹ 2.6.1 PRE-PACKAGED Type SwitchMethod Grounding the GeneratorBattery Installation Preparation Before START-UP‹ 2.7.1 Vented Batteries ‹ 2.8.2 Transfer Switch ‹ 2.8.1 Prior to Initial START-UP‹ 2.8.3 Fuel System ‹ 2.8.4 Generator SET LubricationUsing the AUTO/OFF/MANUAL Switch Sequence of Automatic Operation Engine Heater‹ 3.2.3 Manual Position Weekly Exercise Cycle Checking the Engine OIL LevelChanging the Engine AIR Cleaner ‹ 4.2.2 OIL and Filter Change ProcedureChanging the Engine OIL and Filter ‹ 4.2.1 Engine OIL RecommendationsBattery Maintenance ‹ 4.5.1 Battery ReplacementSpark Plugs Miscellaneous Maintenance Cooling SystemOverload Protection for DC FuseOUT of Service Procedure ‹ 4.11.1 Removal from Service‹ 4.11.2 Return to Service Service Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionElectrical Data TS1 Generator D4992-A Guardian Liquid- Panel 4.3L Drawing No Section Wiring Diagram Control Panel Model No KW Generators No D6975 EC1 ACT Drain Pan Oil QTY Description Base Frame Assembly M6 Hinge Panel Face Panel BTM & Back Control Exploded Views and Parts Lists Cover Plate AVR ALT Leads Sensing Wire QTY To Engine Flywheel Washer Lock M12 Exploded Views and Parts Lists Engine 4.3L GM Exploded Views and Parts Lists MOUNT, Engine R & L KIT Radiator Copper Brass DIA. Clamp Assembly 2 Compartment To Engine Front NUT Wing 1/4-20 Nylk To Stepper Motor Support Solenoid NAT GAS Attach to REGULATOR, N/G R600S Exploded Views and Parts Lists Muffler Catalyst 4.3L Assembly Motor Stepper To Thermostat Housing Guardian Liquid-cooled 40 kW Generators Guardian Liquid-cooled 40 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following

0043735, 0043734, 0046262, 0046263, 0046264 specifications

Generac Power Systems has established itself as a leader in the power generation industry, best known for its wide range of products designed for various power needs. Among its offerings are model numbers 0043733, 0046264, 0046263, 0046262, and 0043734. Each unit reflects Generac's commitment to innovation, reliability, and efficiency in providing backup power solutions.

The Generac model 0043733 is a powerful portable generator known for its robust performance and user-friendly design. It typically features a high starting wattage, capable of powering essential appliances during outages. With a compact design and ergonomic handle, it ensures easy transportability, making it an excellent choice for outdoor activities or emergency backup. This model often incorporates advanced technology such as digital watt meters for real-time monitoring and fuel level indicators to enhance user convenience.

Moving on to model 0046264, this unit is engineered for reliability in home standby applications. Its automatic transfer switch allows for seamless switching from grid power to generator power in the event of an outage. This ensures a continuous power supply without any manual intervention. Generac's Quiet-Test technology makes this model exceptionally quiet, operating at a lower decibel level compared to traditional generators, enhancing its suitability for residential areas.

The 0046263 model is similar to the 0046264 but is designed for slightly different power requirements and configurations. It offers a range of customizable options, allowing users to tailor the system to their specific needs. Advanced monitoring capabilities often come standard, enabling users to track performance and receive alerts via smartphone or other devices.

Model 0046262 is also tailored for homeowners, focusing on versatility and efficiency. It usually features a highly efficient engine, capable of providing substantial power while optimizing fuel consumption. Its sturdy build ensures durability, making it suitable for various weather conditions.

Lastly, the 0043734 model is designed for commercial use, capable of handling larger power needs. It typically comes equipped with technologies such as remote monitoring and diagnostics, making it easier to maintain and service. With a heavy-duty construction, this model is built to withstand demanding environments while providing reliable, uninterrupted power.

In summary, Generac Power Systems offers a diverse range of backup power solutions through models such as 0043733, 0046264, 0046263, 0046262, and 0043734. With features focusing on portability, reliability, efficiency, and advanced technology, these models cater to various power requirements, ensuring customers can find the ideal generator for their needs.