Standby Generator Sets
Specifications
SPECIFICATIONS
GENERATOR
Type | Synchronous |
Rotor Insulation | Class F or H |
Stator Insulation | Class H |
Total Harmonic Distortion | < 3.5% |
Telephone Interference Factor (TIF) | < 50 |
Alternator Output Leads | |
Bearings | Sealed Ball |
Coupling | Flexible Disc |
Load Capacity (Standby Rating) | 30kW* |
*NOTE: Generator rating and performance in accordance with
Excitation System |
| Direct | ||
Generator Output Voltage/kW - 60 Hz | kW | Amp | CB Size | |
120/240V, | 30 | 125 | 150 | |
120/208V, | 30 | 104 | 125 | |
277/480V, | 30 | 45 | 50 | |
Generator Locked Rotor KVA Available @ Voltage Dip of 35% |
| |||
| 60 | KVA | ||
480V, |
| 70 | KVA |
ENGINE
Make | Generac |
Model | |
Cylinders and Arrangement | 6 |
Displacement | 3.0 Liter |
Bore | 3.55 in. |
Stroke | 3.1 in. |
Compression Ratio | |
Air Intake System | Naturally Aspirated |
Valve Seats | Hardened |
Lifter Type | Hydraulic |
Engine Parameters |
|
Rated Synchronous RPM | 60 Hz, 1800 |
HP at rated kW | 60 Hz, 48 |
Exhaust System |
|
Exhaust Flow at Rated Output 60 Hz | 200 cfm |
Exhaust Temperature at Rated Output | 890° F |
Engine Lubrication System |
|
Type of Oil Pump | Gear |
Oil Filter | Full Flow, Cartridge |
Crankcase Oil Capacity | 4 U.S. qts. |
COOLING SYSTEM
Type | Closed |
Water Pump | Belt Driven |
Fan Speed | 2150 |
Fan Diameter | 18 inches |
Fan Mode | Pusher |
Air Flow (inlet air including alternator and |
|
combustion air) | 2460 ft3/min. |
Coolant Capacity | (2.5 U.S. gal.) |
Heat Rejection to Coolant | 115,000 Btu/h |
Maximum Operating Air Temp. on Radiator | 60° C (150° F) |
Maximum Ambient Temperature | 50° C (140° F) |
FUEL SYSTEM
Type of Fuel | ......................................... | Natural Gas, Propane Vapor | ||
Carburetor |
|
| Down Draft | |
Secondary Fuel Regulator |
| Standard | ||
Fuel |
| Standard | ||
Operating Fuel Pressure | 5 in. - 14 in. Water Column | |||
Fuel Consumption - ft3/hr (Natural Gas/LPV) | ||||
Exercise | 25% | 50% | 75% | 100% |
Cycle | Load | Load | Load | Load |
70/28.3 | 111/45 | 214/86.1 | 298/120 | 412/166 |
ELECTRICAL SYSTEM
Battery Charge Alternator | ............................................12V, 30 Amp |
Static Battery Charger | 2 Amp |
Recommended Battery | 24F 525CCA |
System Voltage | 12 Volts |
Voltage Regulator |
|
Type | Electronic |
Sensing | |
Regulation | ± 1% |
Features | V/F Adjustable, Adjustable |
| Voltage and Gain LED Indicators |
Power Adjustment for Ambient Conditions
Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz | ................................................... 92 cfm |
Governor |
|
Type | Electronic |
Frequency Regulation | Isochronous |
Steady State Regulation | ± 1/2% |
Adjustments: |
|
Speed | Selectable |
Temperature Deration |
|
3% for every 10° C above °C | 25 |
1.65% for every 10° above °F | 77 |
Altitude Deration |
|
1% for every 100 m above m | 183 |
3% for every 1000 ft. above ft | 600 |
Controller |