Generac Power Systems 65, 55, 75 Test 28- Check Fuel Supply, Test Bracket, Remove Starter Motor

Page 56

Section 7

DIAGNOSTIC TESTS

Figure 7-24. – Tachometer

TEST BRACKET:

A starter motor test bracket may be made as shown in Figure 7-25.

Figure 7-25. – Test Bracket

REMOVE STARTER MOTOR:

It is recommended that the Starter Motor be removed from the engine when testing Starter Motor perfor- mance. Assemble starter to test bracket and clamp test bracket in vise (Figure 7-26).

TESTING STARTER MOTOR:

1.A fully charged 12 volt battery is required.

2.Connect jumper cables and clamp-on ammeter as shown in Figure 7-26.

3.With the Starter Motor activated (jump the terminal on the Starter Contactor to battery voltage), note the reading on the clamp-on ammeter and on the tachometer (rpm).

Note: Take the reading after the ammeter and tachometer are stabilized, approximately 2-4 seconds.

4.A starter motor in good condition will be within the following specifications:

Minimum rpm

4500

Maximum Amps

50

Note: Nominal amp draw of starter in generator is 60 amps.

Figure 7-26. – Testing Starter Motor Performance

TEST 28- CHECK FUEL SUPPLY

DISCUSSION (GASOLINE MODELS):

If the engine cranks but won't start, don't overlook the obvious. The fuel supply may be low. Many RV gen- erator installations “share” the fuel tank with the vehi- cle engine. When such is the case, the Installer may have used a generator fuel pickup tube that is shorter than the vehicle engine's pickup tube. Thus, the gen- erator will run out of gas before the vehicle engine.

PROCEDURE:

Check fuel level in the supply tank. Attach a fresh fuel supply if necessary and restart. Fuel may be stale, causing a hard start.

RESULTS:

1.If necessary, replenish fuel supply.

2.If fuel is good, go to Test 29 (for Problem 7, Section 6). Go to Test 32 for Problem 8 (Section 6).

Page 54

Image 56
Contents Diagnostic Repair Manual Safety Replacement PartsTable of Contents Section Specifications & Charts Section Exploded Views / Part NumbersElectromagnetic Induction MagnetismElectromagnetic Fields Simple AC Generator More Sophisticated AC GeneratorGenerator Operating Diagram Line Breakers 120 Volts only Field BoostGenerator AC Connection System Connection for 120 Volts Only Reconnection for Dual Voltage OutputRotor Assembly Stator AssemblyBattery Charge Components Brush HolderExcitation Circuit Components GeneralAdjustment Procedure Crankcase BreatherVoltage Regulator DescriptionInstall Breather Install oil vapor collector and retainerControl Panel Component Identification Check BreatherCleaning the Generator Effects of Dirt and MoistureInsulation Resistance Testers Drying the GeneratorBrushing and Vacuum Cleaning Stator Insulation ResistanceCloth or Compressed AIR Stator SHORT-TO-GROUND TestsTesting Rotor Insulation Testing Stator InsulationTesting Rotor Insulation MegohmmeterMeters VOMMeasuring AC Voltage Measuring DC VoltageMeasuring Resistance Measuring AC FrequencyMeasuring Current Electrical Units Ohms LAWAmpere VoltCircuit CONDITION- Rest IntroductionOperational Analysis Circuit CONDITION- Priming Circuit CONDITION- Cranking Circuit CONDITION-RUNNING Choke Heater CHCircuit CONDITION- Shutdown Circuit CONDITION- Fault Shutdown Sure Switch LOPBattery Recommended BatteryBattery Cables Engine Controller Circuit BoardAMP Fuse Fuel Primer SwitchSTART-STOP Switch Starter Contactor Relay Starter Motor Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Troubleshooting Flowcharts Procedure Test 1- Check NO-LOAD Voltage FrequencyTest 2- Check Engine Governor DiscussionGovernor Adjustment Test 3- Test Excitation Circuit BreakerTest 4- Fixed Excitation TEST/ROTOR AMP Draw If continuity was indicated, go to TestTest 5- Wire Continuity Re-connect Wire 11 and Wire 22 to the Voltage RegulatorSet the VOM to measure AC voltage Set a VOM to its Rx1 scaleIf field boost checks good, replace the Voltage Regulator Test 6- Check Field BoostTest 7 Test Stator DPE Winding Test 8- Check Sensing Leads / Power Windings Across Wires Ohms11S 22S Model OhmsTest 9- Check Brush Leads Test 10 Check Brushes & Slip RingsTest 11- Check Rotor Assembly Tance Tests ProcedureTest 12 Check Main Circuit Breaker Replace the Rotor if it fails the testTest 15 Check Battery Charge Output Test 16 Check Battery Charge RectifierBattery Charge Rectifier BCR is a full wave rectifier Test 13- Check Load Voltage Frequency10. Battery Charge Rectifier Short to GroundTest 19- Test Primer Switch Set a VOM to read battery voltage 12 VDCAlso see Fuel Primer Switch, Test 18 TRY Cranking the EngineTest 20- Check Fuel Pump 13. The LPG Fuel Solenoid FSTest 21- Check 7.5 AMP Fuse Test 22- Check Battery & CablesTest 23- Check Power Supply to Circuit Board Test 24 Check START-STOP Switch 17. Start-Stop SwitchTest 26- Check Starter Contactor Relay Set a VOM to measure DC voltage 12 VDCConditions Affecting Starter Motor Performance Test 26A Check Starter ContactorTest 27 Check Starter Motor Checking the Pinion Tools for Starter Performance TestMeasuring Current TachometerTesting Starter Motor Test 28- Check Fuel SupplyTest Bracket Remove Starter Motor28 LP Gas Carburetion Diagram Discussion LPG ModelsTest 29 Check Wire 14 Power Supply Test 30 Check WireBattery voltage is not measured, proceed to Step Crank the engine. The meter should indicate battery voltageTest 31 Check Fuel Solenoid Gasoline Models Test 32 Check Ignition SparkCylinder Balance Test Conclusion No cylinder is weakest of the two cylindersTest 34 Check and Adjust Ignition Magnetos Test 33 Check Spark Plugs37. Setting Ignition Magneto Armature Air Gap Test 35 Check Valve Adjustment Adjusting Valve ClearanceChecking Flywheel Magnet Flywheel KEYTest 37 Check Choke Solenoid Install Rocker ARM CoverTest 36 Check Carburetion 43. Connector Adjust the regulated pressure on the gauge to 80 psi Down Test / Compression TestRepeat Steps 1 through 8 on remaining cylinder Check CompressionIf all steps check GOOD, go to Test Test 39 Check OIL Pressure SwitchTest 40 Test OIL Temperature Switch Short to Ground Test 41 Test Choke HeaterTest 42 Check LPG Fuel Solenoid 49. Fuel Solenoid Major Disassembly ENCLOSURE/PANEL RemovalStator Removal Rotor RemovalStarter Removal Belt TensioningEngine Removal FLYWHEEL/MAGNETO Removal Page Section Exploded Views / Part Numbers Part NO. QTY Description Enclosure Drawing No E1011-B QTY Description Sheet Metal Drawing No E1012-E QTY Description Flywheel Assy GT-990Control Panel Drawing No E1013-A Wire ASM GRD STD Conn Switch Spdt ON-MOM-ONSwitch 6A Spdt Not Shown PANEL, TOP ControlTwin Engine Drawing No E1014-B ASSEMBLY, Crankcase RV ASSEMBLY, BreatherASSEMBLY, Head #1 ASSEMBLY, OIL Fill CAPLP Regulator Drawing No E1530 CASTING, Twin Regulator Housing Washer Flat M4SOLENOID, Twin Regulator SPRING-SOLENOID PlungerSpecifications & Charts Generator Specifications Nominal Resistances of Generator Windings AT 68FEngine Speeds and Voltage Specifications Page Electrical Data Electrical Data PO BOX 297 WHITEWATER, WI

65, 75, 55 specifications

Generac Power Systems has established itself as a leader in power generation, offering a range of high-performance generators suited for residential and commercial applications. Among its lineup, the Generac 55, 65, and 75 kW generators stand out for their reliability, efficiency, and advanced features.

The Generac 55 kW generator is designed to provide a powerful backup solution for medium to large homes or small businesses. It features a robust engine that delivers dependable performance while maintaining fuel efficiency. One of its key characteristics is the True Power Technology, which produces clean and stable power, ensuring that sensitive electronic devices run smoothly without risk of damage. This generator is equipped with a fully automatic transfer switch, allowing for seamless power transition during outages, with minimal disruption.

Moving to the 65 kW model, it offers increased capacity while retaining the fundamental qualities of the 55 kW version. This unit is particularly suited for larger homes or commercial applications that require greater power demands. The 65 kW generator utilizes Generac’s G-Force engine, known for its durability and reduced maintenance needs. Advanced features such as remote monitoring capabilities allow users to check the generator's status from anywhere, providing peace of mind and convenience.

The 75 kW generator takes performance to the next level, making it ideal for even more significant power needs. It is engineered for both quiet operation and enhanced performance, accommodating a wide range of requirements from residential to larger commercial operations. The 75 kW model includes a full-load voltage regulation system that maintains stable power output under varying loads, safeguarding appliances and equipment.

All three models incorporate advanced air-cooled technology, which enhances their efficiency and operational lifespan. Additionally, their corrosion-resistant enclosures ensure durability even in harsh weather conditions, making them suitable for diverse environments. The intuitive LCD display on each unit provides critical information, including runtime hours and maintenance reminders, empowering users with easy access to the generator's performance data.

Overall, Generac Power Systems' 55, 65, and 75 kW generators represent a commitment to quality, reliability, and innovation in backup power solutions. They are designed to meet the demands of modern power consumption while ensuring peace of mind through robust engineering and advanced technology. Whether for home use or commercial applications, these generators provide an effective means to stay prepared for unexpected power outages.