Standby Generator Sets Engine Protective Devices

ENGINE PROTECTIVE DEVICES

The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.

NOTE:

Engine protective switches and sensors are men- tioned here for the reader’s convenience. Also refer to the applicable control panel manual for additional automatic engine shutdown informa- tion.

‹HIGH COOLANT TEMPERATURE SWITCH

This switches contacts close if the temperature should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.

‹LOW COOLANT LEVEL SENSOR

Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut- down. To prevent such overheating, the engine has a low coolant level sensor. If the level of engine coolant drops below the level of the low coolant level sensor, the engine automatically shuts down.

‹OVERCRANK SHUTDOWN

After a prespecified duration of cranking, this func- tion ends the cranking if the engine has failed to start. The overcrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control board.

NOTE:

If the fault is not corrected, the overcrank feature will continue to activate.

Approximate Crank Cycle Times

15 seconds ON

7 seconds OFF

7 seconds ON

7 seconds OFF

Repeat for 45 seconds Approximately 90 seconds total.

‹OVERSPEED SHUTDOWN

A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine overspeed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.

‹RPM SENSOR LOSS SHUTDOWN

If the speed signal to the control panel is lost, engine shutdown will occur.

‹LOW OIL PRESSURE SWITCH

This switch has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.

‹DC FUSE

This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)

4-1

08/05

0 .Rev EngProt001

Image 8
Contents 6L 20/25/30 kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ Operation and Maintenance ‹ HOW to Obtain ServiceIntroduction ‹ Read this Manual ThoroughlyIdentification Record ‹ Data LabelCoolant Recommendations Equipment DescriptionEngine OIL Recommendations Engine Protective Devices Fuel System ‹ Fuel Requirements‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Reconfiguring the Fuel System ‹ Cold Weather KITAlternator Power Winding Connections ‹ FOUR-LEAD, SINGLE-PHASE Stator‹ 3-PHASE Alternators Generator AC Lead ConnectionsInitial Inspection for Genset Startup InstallationPreparation Before START-UP START-UP Checklist ‹ Preparation for START-UPOperating Unit with Manual Transfer Switch Generator Control Operation‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownChecking Fluid Levels Maintenance Performed by Service FacilitiesCooling System ‹ Battery Fluid ‹ Check Battery‹ Exercise System ‹ Inspect Cooling System‹ Spark Plugs ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Changing Engine OIL Miscellaneous Maintenance Service Schedule Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Guide Problem Cause CorrectionStandby Generator Sets Standby Generator Sets Standby Generator Sets Standby Generator Sets Page Housing Blower LG Pilot Page Screw Phtt M4-0.7 X 12 ZYC Page Components Included in 0G4577E Page Radiator Support LH Side 1.6L Page Mounting Base 1.6L 2007 C1 Page Battery TRAY, C1 & C2 Page Engine Generac 1.6L NG Page ASM Motor Stepper Page Elbow 90D 3/4 NPT Page Rear Intake Wrap 1.6L C1 Page Muffler C1 Page Page Page Page Page Page Page Page Page Page Page Page Page Page 04/07 a .Rev BackPg001

25, 30, 20 specifications

Generac Power Systems is a leading manufacturer of backup power generation products and tools, known for their reliability and innovation. Among their diverse lineup are the Generac 20kW, 25kW, and 30kW home standby generators. These models are designed to provide seamless power during an outage, allowing homeowners to maintain their everyday activities without interruption.

The Generac 20kW generator is particularly popular for residential use. It can power essential circuits as well as larger appliances, making it an ideal choice for homes with moderate electricity needs. One of its standout features is the Smart Management Module, which allows homeowners to manage energy consumption effectively, ensuring that they can run necessary appliances without overwhelming the system. Additionally, the 20kW generator is equipped with a durable enclosure, offering long-lasting protection against the elements.

Moving up in capacity, the Generac 25kW model caters to homes with higher electricity demands. This generator combines efficiency with strength, providing enough power for a wider range of home appliances and systems. It features a TruePower Technology that delivers clean power, crucial for sensitive electronics. Moreover, the 25kW model operates quietly, contributing to a comfortable home environment even during power outages.

The Generac 30kW generator is designed for larger homes or light commercial applications. It provides an impressive power output while maintaining high efficiency. Its features include advanced digital control, allowing for easy monitoring and maintenance. The 30kW model also offers an automatic transfer switch, which ensures that power is restored quickly and safely when utilities fail.

All three models utilize Generac's G-Force engine, known for its low maintenance requirements and high performance. They come with a five-year limited warranty, providing peace of mind for users. Furthermore, with Wi-Fi monitoring capabilities, homeowners can keep track of their generator's status from anywhere, ensuring they are always prepared for any power interruption.

In summary, the Generac 20kW, 25kW, and 30kW generators are excellent options for homeowners seeking reliable backup power. Their advanced features, durable construction, and efficient operation make them stand out in the market. Whether for essential home use or larger applications, Generac's lineup delivers dependable performance and innovative technology.