Generac Power Systems 04758-1, 04759-1, 04760-1 Fuel Requirements Recommendations, 1 7 KW, 410CC

Page 9

Section 1 — General Information

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

1.6FUEL REQUIREMENTS

AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal

system. This type of system uses the vapors formed above the liquid fuel in the storage tank.

The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See Section 1.8 for instructions on reconfiguration of the fuel system.

Recommended fuels should have a Btu content of at least 1,000 BTU’s per cubic foot for natural gas; or at least 2,520 BTU’s per cubic foot for LP gas. Ask the fuel supplier for the BTU content of the fuel.

Fuel pressure for both natural gas and liquid propane set ups should be 11 inches to 14 inches of water column (0.6 psi) at all load ranges.

NOTE:

A separate gas line and regulator may be needed to assure proper gas pressure (11-14”) to the gen- erator. Low gas pressure can cause hard starting and could affect engine durability.

1.7FUEL CONSUMPTION

 

Model #

Nat. Gas (*)

LP Vapor (**)

 

 

 

1/2 Load

Full Load

1/2 Load

Full Load

 

 

04758

74

105

0.91/33

1.21/44.1

 

 

04759

114

185

1.34/48.9

2.17/79.0

 

 

04760

148.5

240

1.73/63.2

2.80/102.3

 

3.Disconnect wire #0 and wire #14 from the gas solenoid located on the top of the demand regu- lator.

4.Remove the demand regulator by rotating coun- terclockwise.

5.Remove the brass hose fitting from the outlet port of the demand regulator.

6.Remove the brass metering jet (loosen counter- clockwise) from the housing port of the demand regulator located on the side of the regulator.

7.Install new LP metering jet (tighten clockwise) in the outlet port of the demand regulator.

8.Refit the brass hose fittings to the outlet port of the demand regulator.

9.Reverse procedure steps 1-4 to reinstall demand regulator.

10.Reverse the procedure to convert back to natural gas.

Figure 1.3 – Demand Regulator

 

FUEL HOSE

FUEL HOSE

BRASS HOSE

 

FITTING

BRASS HOSE

FITTING

OUTLET

PORT

FUEL JET

REGULATOR

HOUSING PORT

NG FUEL SYSTEM

LP FUEL SYSTEM

NOTE:

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

DANGER

Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.

1.8RECONFIGURING THE FUEL SYSTEM

1.8.1 7 KW, 410CC

To reconfigure the fuel system from NG to LP, follow these steps:

1.Turn the main gas supply off.

2.Remove the carburetor fuel hose from the outlet port of the demand regulator (Figure 1.3).

The natural gas adjustment screw is preset during installation and should not need any further adjustment.

1.8.2 12KW AND 15KW, 990CC ENGINES

To reconfigure the fuel system from NG to LP, follow these steps:

NOTE:

The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres- sure of 11 to 14 inches of water column (0.6 psi) to the fuel inlet of the generator MUST BE SUP-

PLIED.

1.Turn OFF the main gas supply.

2.Remove the engine air in baffle located on the left hand side of the battery compartment. Two M6 screws are located on top of the baffle and two M6 screws are located on the inside of the baffle towards the back.

Generac® Power Systems, Inc. 7

Image 9
Contents Installation Introduction Maintenance Post Installation Start-up AdjustmentsTroubleshooting Introduction Inside Front CoverGeneral Hazards ‹ Standards Index Electrical HazardsUNPACKING/INSPECTION Protection SystemsSystem SET LED 7 kW, Single Cylinder GH-410 Engine GeneratorSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Requirements Recommendations Reconfiguring the Fuel SystemFuel Consumption 1 7 KW, 410CCLocation Transfer SwitchGenerator 2.1 7 kW, 12 kW and 15 kW UnitsBattery Battery InstallationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units Voltage Regulator Adjustment BREAK-IN Procedure2 12 KW and 15 KW Units Sequence of Automatic Operation Automatic Transfer Operation‹ 3.2.1 Auto Position ‹ 3.2.2 OFF PositionManual Transfer Operation ‹ 3.5.2 Transfer Back to Utility Power Source‹ 3.7.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 3.7.2 High Temperature Switch ‹ 3.7.3 OvercrankChecking the Engine OIL Level Changing the Engine OIL‹ 4.3.1 Engine OIL Recommendations ‹ 4.3.2 OIL Change Procedure Changing the OIL Filter‹ 4.5.1 7 KW, 12 KW and 15 KW Generators Spark Plugs Battery MaintenanceCooling System Adjusting Valve Clearance‹ 4.12.2 Return to Service OUT of Service Procedure‹ 4.12.1 Removal from Service Corrosion ProtectionSYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Customer Battery SCR Electrical Data Connection BCR SW1 Exploded Views and Parts Lists Part NO.QTY. Description Exploded Views and Parts Lists Part NO. QTY. Description 140 Part NO. QTY Description Exploded Views and Parts Lists QTY Description 14 20 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome For GT 760 Engine only CASTING, Twin Regulator Housing Mounting Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators California and Federal Emission Control Warranty Statement Emission Control System Warranty Warranty Schedule

04758-1, 04759-1, 04760-1 specifications

Generac Power Systems is a leading manufacturer of power generation equipment, particularly known for its innovative solutions in backup and portable power. Among its impressive product lineup, the Generac models 04758-1, 04759-1, and 04760-1 stand out for their reliability and advanced features, making them ideal choices for residential and commercial applications.

The Generac 04758-1 is a robust standby generator that delivers a powerful output of 22kW. It is designed to automatically kick in during power outages, ensuring that homes remain powered without the need for manual intervention. One of its main features is the innovative Mobile Link app, which allows users to monitor their generator's status remotely through their smartphones. This model also incorporates Generac's G-Force engine, which is designed with durability in mind, providing longer run times and enhanced performance.

The 04759-1 model builds on its predecessor's strengths by enhancing its power capabilities. With a 24kW output, it efficiently supplies power to larger homes or small businesses that require reliability during outages. Its True Power Technology ensures clean power output, making it suitable for sensitive electronics. The 04759-1 also boasts advanced diagnostic features, allowing for self-testing and maintenance alerts, which contribute to its user-friendly design.

Moving up in the lineup, the Generac 04760-1 generator further amplifies power output, reaching an impressive 26kW. This model is tailored for those who demand the utmost in power reliability, featuring an aluminized steel enclosure that enhances durability and rust resistance. The 04760-1 is equipped with Wi-Fi connectivity, enabling real-time updates and notifications directly to users’ mobile devices. Its superior sound attenuated design operates quietly, ensuring minimal disruption during operation.

All three models are equipped with the Quiet-Test technology, which allows for a low-decibel exercise cycle that reduces noise levels without sacrificing performance. Additionally, Generac back them with a comprehensive warranty and customer support, assuring consumers of their long-term reliability and effectiveness. With advanced features, superior performance, and innovative technology, the Generac 04758-1, 04759-1, and 04760-1 models offer dependable solutions for power generation needs, catering to a diverse range of applications while ensuring peace of mind during power interruptions.