| Pub. 42004-615L2 |
Model 670-801-EX and 670-801-UL SmartSeries Amplifiers | Page: 13 of 15 |
Software Configuration
The unit has the following versions of software:
PCBA | Device | Part Number |
Base-16 PCBA | U2 | 50086-014 |
FSK modem PCBA | U1 | 49023-030 |
The SmartSeries Amplifier has software on U2 of the Base-16 PCBA and on U1 of the FSK Modem PCBA. This software provides the following standard programmable features, accessible from the SST Configuration screen when the station is in an ADVANCE system:
•Page Priority VLC Mode—determines the condition for setting the speaker amplifier output to the User Page Priority VLC (Volume Level Control) Output Level by comparing the incoming page’s Page Priority Level with the station’s Page Priority Level (VLC Page Priority). Default setting: disabled.
•Page Trip Level for Speaker Amplifier—the minimum trip level for detecting a page in progress. Default setting: 0.44 Vpeak.
•Pass Level for Speaker Amp HC—the minimum expected test tone voltage level for supervision of the speaker amplifier. Default setting: 0.2 Vpeak.
•Pass Level for Speaker/Wire HC—the minimum expected ambient level for supervision of the speaker wire. Default setting: 35 dB SPL.
•Smart Party Line EOL—enables or disables the station as an end-of-line device for supervision of party line 1, for a station configured either as a Smart Handset Dual Party Select device or a Smart Handset Party Select device. Default setting: disabled.
•SmartSeries Station RTU Monitored Input Process—selects the input mode for each IDC. Default setting: disabled.
•SmartSeries Station RTU Power Relay Process—selects the relay group and zone associated with an indicating appliance circuit (IAC). Default setting: disabled.
•Speaker Amplifier Clip Level—the maximum output level of the speaker amplifier. Default setting: 2.16 Vpeak.
•System VLC Control—enables or disables VLC Mode. Default setting: disabled.
•System VLC Group—the group number for VLC operation. Default setting: 0.
•VLC Page Priority—the station’s incoming Page Priority Level. Default setting: 0.
The following standard programmable features are also accessible from the User Level Adjustment control on the front panel:
•User Minimum Page Output Level (or Minimum Level)—the minimum page output level of the speaker amplifier. Default setting: 4 watts.
•User Offset Added to Ambient (or Offset Level)—the amount of gain added to the ambient level so that an incoming page is not lost in the noise. Default setting: 9 dB.
•User Page Priority VLC Output Level (or VLC Level)—the page output level of the speaker amplifier when the station is in VLC Mode. Default setting: 1 watt.